Greenheck Fan VSU manual Maintenance Routine, Belt Drives, Motors, Wheels, Filters

Page 18

Maintenance - Routine

Caution

Lock-out the gas and the electrical power to the unit before performing any maintenance or service operations to this unit.

V-Belt Drives

V-belt drives must be checked on a regular basis for wear, tension, alignment, and dirt accumulation.

Check the tension by measuring the deflection in the belt as shown below.

Check the alignment by using a straight edge across both sheaves as shown below.

important

Premature or frequent belt failures can be caused by improper belt tension or misaligned sheaves.

Abnormally high belt tension or drive misalignment will cause excessive bearing loads and may result in failure of the fan and/or motor bearings.

Abnormally low belt tension will cause squealing on start-up, excessive belt flutter, slippage, and overheated sheaves.

important

Do not pry belts on or off the sheave. Loosen belt tension until belts can be removed by simply lifting the belts off the sheaves.

important

When replacing V-belts on multiple groove drives, all belts should be changed to provide uniform drive loading.

important

Do not install new belts on worn sheaves. If the sheaves have grooves worn in them, they must be replaced before new belts are installed.

Deflection = Belt Span 64

Belt Span

Belt Tension

Drive Alignment

18Model VSU Make-Up Air

Motors

Motor maintenance is generally limited to cleaning and lubrication (where applicable).

Cleaning should be limited to exterior surfaces only. Removing dust and grease build-up on the motor assures proper motor cooling.

Motors supplied with grease fittings should be greased in accordance with the manufacturer’s recommendations.

important

Do not allow water or solvents to enter the motor or bearings. Motors and bearings should never be sprayed with steam, water or solvents.

important

Greasing motors is only intended when fittings are provided. Many motors are permanently lubricated, requiring no additional lubrication.

Wheels

Wheels require little attention when moving clean air. Occasionally oil and dust may accumulate on the wheel causing imbalance. When this occurs the wheel and housing should be cleaned to assure proper operation.

Filters

Filter maintenance is generally limited to cleaning and replacement.

Aluminum mesh filters can be washed in warm soapy water.

An adhesive spray can be added to aluminum mesh filters to increase their efficiency.

IMPORTANT

When reinstalling filters, be sure to install them with the airflow in the correct direction. An airflow direction arrow is located on the side of the filters.

IMPORTANT

Replacement filters should be from the same manufacturer and the same size as the original filters provided with the unit.

®

Image 18
Contents General Safety Information Model VSUUnpacking Inspection and Maintenance during StorageReceiving HandlingTable of Contents InstallationInstall Ductwork Complete InstallationBurner/Blower Section Dimensional Data Upblast DischargeDetermine the Supply Gas Requirements Installation of Direct Gas PipingInstall Additional Regulator if Required Connect the Supply Gas LinePipe the Optional Vent Line Test the System for LeaksStart-Up Blower Air Volume Measurement & Check Set-up Optional ComponentsSet the Burner Air Pressure Differential Start-Up Direct GasCheck the Supply Gas Pressure Check the Pilot Gas PressureSet the Minimum Firing Rate Set the Maximum Firing RateRegulators and Modulating Valves Maxitrol Series 14 7 terminalsSet the Unit’s Operating Temperature Flame Signal CheckMaxitrol Series Operation Electrical Terminals R and X? TroubleshootingBlower Does Not Operate Terminals G and X?Heater Does Not Operate Does not attempt to light No visible sparkAttempts to light, but no pilot visible spark Visible pilot Motors Maintenance RoutineBelt Drives WheelsStart-Up Maintenance FallBearings High LimitReference Typical Control Center LayoutTypical Gas Train Layout Start-Up Checklist Maintenance Log Date Time AM/PMMaintenance Log Warranty

VSU specifications

Greenheck Fan VSU, or Variable Speed Unit ventilators, represent a significant advancement in the field of HVAC technology. Designed to enhance air quality and energy efficiency, these units are particularly suited for commercial applications such as schools, offices, and industrial facilities. They provide a reliable solution for both heating and cooling, ensuring optimal comfort and productivity in diverse environments.

One of the hallmark features of the VSU is its variable speed motor. This innovation allows the fan speed to adjust according to the specific demands of the space, leading to substantial energy savings compared to traditional fixed-speed units. By operating at reduced speeds during lower load conditions, the VSU minimizes energy consumption while maintaining comfortable indoor conditions. This adaptive capability not only lowers utility bills but also contributes to a reduced environmental footprint.

In addition to energy efficiency, the VSU is equipped with advanced controls that provide precise temperature management and air distribution. These controls can be integrated into existing building management systems, giving facility managers the ability to monitor and fine-tune operations remotely. The ability to set specific schedules and program temperature settings enhances overall building performance and ensures that spaces are only conditioned when necessary.

The VSU is designed with a robust and durable construction, featuring corrosion-resistant materials that prolong the unit's lifespan. This reliability is further enhanced by its easy accessibility for maintenance, making it a cost-effective solution for long-term use. Users can expect a quiet operation due to the fan’s advanced design, which significantly reduces noise levels compared to traditional models.

Furthermore, the VSU supports a variety of custom configurations, allowing it to meet the specific needs of different applications. Whether it's integrating with other HVAC components or adapting to varied ceiling heights, the flexibility of the Greenheck Fan VSU makes it a versatile choice for engineers and building owners alike.

In conclusion, the Greenheck Fan VSU stands out for its combination of energy efficiency, advanced control options, durability, and adaptability. As the demand for sustainable and effective HVAC solutions continues to grow, the VSU positions itself as a top choice for those seeking to enhance indoor air quality while minimizing operational costs.