Goodman Mfg CPC/CPH installation instructions Electrical Wiring, Rigging Removal

Page 8

CAUTION

TO PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT, DO NOT FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED.

Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, care should be taken to center the unit. Check for proper alignment and orientation of supply and return open- ings with duct.

RIGGING REMOVAL

CAUTION

TO PREVENT DAMAGE TO THE UNIT, DO NOT ALLOW CRANE HOOKS AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT.

Remove spreader bars, lifting cables and other rigging equip- ment.

ELECTRICAL WIRING

WARNING

HIGH VOLTAGE!

DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

WARNING

HIGH VOLTAGE!

TO AVOID PERSONAL INJURY OR DEATH DUE TO

ELECTRICAL SHOCK, DO NOT TAMPER WITH FACTORY

WIRING. THE INTERNAL POWER AND CONTROL WIRING

OF THESE UNITS ARE FACTORY-INSTALLED AND HAVE

BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT.

CONTACT YOUR LOCAL REPRESENTATIVE IF

ASSISTANCE IS REQUIRED.

CAUTION

TO PREVENT DAMAGE TO THE WIRING, PROTECT WIRING FROM SHARP EDGES. FOLLOW NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND ORDINANCES. DO NOT ROUTE WIRES THROUGH REMOVABLE ACCESS PANELS.

CAUTION

CONDUIT AND FITTINGS MUST BE WEATHER-TIGHT TO PREVENT WATER ENTRY INTO THE BUILDING.

For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.

All line voltage connections must be made through weather- proof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit.

The main power supply wiring to the unit and low voltage wiring to accessory controls must be done in accordance with these instructions, the latest edition of the National Electrical Code (ANSI/NFPA 70), and all local codes and ordinances. All field wiring shall conform with the temperature limitations for Type T wire (63°F/35°C rise).

The unit is factory wired for the voltage shown on the unit’s data plate. Refer to model nomenclature in Appendix D for voltage requirement for your unit.

NOTE: If supply voltage is 208V, lead on primary of trans- former must be moved from the 230V to the 208V tap. Refer to wiring diagram on unit for details.

Main power wiring should be sized for the minimum wire ampacity shown on the unit’s data plate. Size wires in accor- dance with the ampacity tables in Article 310 of the National Electrical Code. If long wires are required, it may be neces- sary to increase the wire size to prevent excessive voltage drop. Wires should be sized for a maximum of 3% voltage drop.

CAUTION

TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE ONLY COPPER CONDUCTORS.

CAUTION

LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING

CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND

DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER

SERVICING.

NOTE: A weather-tight disconnect switch, properly sized for the unit total load, must be field installed. An external field supplied disconnect may be mounted on the exterior panel.

Ensure the data plate is not covered by the field-supplied disconnect switch.

Some disconnect switches are not fused. Protect the power leads at the point of distribution in accordance with the unit’s data plate.

The unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code (ANSI-NFPA 70). A ground lug is provided for this purpose. Size grounding conductor in accordance with Table 250-95 of the National Electrical Code. Do not use the ground lug for connecting a neutral conductor.

Remove plug in panel located at the condenser end of unit and route conduit to control box. Remove plug in control box and connect power wiring to the contactor closest to the entrance. If Single Point kit is used, refer to Installation Instructions supplied with kit.

8

Image 8
Contents TON 6 TON CPC/CPH Series Replacement Parts Safety InstructionsGeneral Information High VoltageUnit Location Roof Curb POST-INSTALLATION Checks ClearancesRigging Details Roof TOP Duct ConnectionsWeights shown are belt drive with no accessories Electrical Wiring Rigging RemovalSupply Venting Condensate Drain Connection STARTUP, ADJUSTMENTS, and ChecksCirculating AIR and Filters Belt Drive Models only Drive Belt Tension Adjustment Air Flow Adjustments Heat Pump OperationMotor AIR Flow AdjustmentsPSC Motor Drive Adjustments Motor Sheave Adjustments MaintenanceService Valve Body Damaged Replace valveCPC/H036 Direct Drive Down Shot CPC/H036 Direct Drive HorizontalCPC/H048 Direct Drive Down Shot CPC/H048 Direct Drive HorizontalCPC/H060 Direct Drive Down Shot 790CPC/H060 Direct Drive Horizontal CPC/H036 Standard Belt Drive Down Shot CPC/H048 Standard Belt Drive Down ShotCPC/H060 Standard Belt Drive Down Shot CPC/H072 Standard Belt Drive Down ShotCPC/H036 High Static Belt Drive Down Shot CPC/H048 High Static Belt Drive Down ShotCPC/H060 High Static Belt Drive Down Shot CPC/H072 High Static Belt Drive Down ShotCPC/H036 Standard Belt Drive Horizontal CPC/H048 Standard Belt Drive HorizontalCPC/H060 Standard Belt Drive Horizontal CPC/H072 Standard Belt Drive HorizontalCPC/H036 High Static Belt Drive Horizontal CPC/H048 High Static Belt Drive HorizontalCPC/H060 High Static Belt Drive Horizontal CPC/H072 High Static Belt Drive HorizontalAppendix B Electrical Data Minimum AIR Flow for Electric Heat Unit Heater KIT Minimum CFM Model NumberAppendix C Unit Dimensions 2010,2012 Goodman Manufacturing Company, L.P

CPC/CPH specifications

Goodman Manufacturing, a prominent name in the HVAC industry, offers a range of products designed for efficiency, reliability, and affordability. Among their various offerings, the Goodman CPC (Commercial Packaged Condensing) and CPH (Commercial Packaged Heat Pump) systems stand out due to their advanced features and innovative technologies.

The Goodman CPC and CPH units are designed for commercial applications, providing effective heating and cooling solutions for diverse settings such as restaurants, warehouses, and retail spaces. One of the main features of these systems is their high energy efficiency, which allows businesses to save on energy costs while reducing their carbon footprint. These units typically feature SEER (Seasonal Energy Efficiency Ratio) ratings that comply with or exceed industry standards, ensuring optimal performance throughout the year.

Equipped with high-performing scroll compressors, Goodman’s CPC and CPH systems deliver consistent cooling and heating performance, enhancing overall system reliability. The scroll compressor technology is known for its durability and quieter operation, making it an excellent choice for environments where noise reduction is crucial.

Another significant characteristic of Goodman’s systems is their robust construction. Built with commercial-grade materials, the CPC and CPH units are designed for long-term performance, capable of withstanding harsh weather conditions and heavy usage. The all-aluminum microchannel coils used in these units provide excellent heat exchange efficiency and resist corrosion, ensuring a longer lifespan.

Smart technology integration is another highlight of Goodman’s offerings. The CPC and CPH systems can be equipped with advanced controls, including smart thermostats and remote monitoring capabilities, allowing businesses to optimize their HVAC performance. These technologies enable precise temperature control and energy management, leading to increased comfort and cost savings.

Furthermore, Goodman emphasizes ease of installation and maintenance in the design of their CPC/CPH systems. The compact design and simplified access to key components ensure that service technicians can perform maintenance promptly, minimizing downtime in commercial settings.

Ultimately, Goodman Manufacturing’s CPC and CPH systems represent a blend of energy efficiency, advanced technology, and durability, making them an excellent choice for businesses seeking reliable HVAC solutions. With a commitment to quality and customer satisfaction, Goodman continues to be a leader in the HVAC industry, providing products that meet the needs of today’s diverse commercial environments.