Goodman Mfg 10.3 EER specifications Electric Heat AIR Temperature Rise, HKCB20 HKCB30 HKCB40

Page 8

PRODUCT SPECIFICATIONS

ELECTRIC HEAT AIR TEMPERATURE RISE

Heater Model

HKCB20

HKCB30

HKCB40

Number of Stages

2

2

2

 

 

 

 

 

Output (MBH)

67.9

135.8

135.8

 

2,600

24.2

36.2

-

 

 

 

 

 

 

2,800

22.5

33.6

-

 

 

 

 

 

 

3,000

21.0

31.4

-

 

3,200

19.7

29.4

39.3

 

 

 

 

 

 

3,400

18.5

27.7

37.0

 

3,600

17.5

26.2

34.9

 

 

 

 

 

 

3,800

16.5

24.8

33.1

 

 

 

 

 

 

4,000

15.7

23.5

31.4

CFM

4,200

15.0

22.4

29.9

 

 

 

 

4,400

14.3

21.4

28.6

 

 

4,600

13.7

20.5

27.3

 

 

 

 

 

 

4,800

13.1

19.6

26.2

 

 

 

 

 

 

5,000

12.6

18.8

25.2

 

5,200

12.1

18.1

24.2

 

 

 

 

 

 

5,400

11.6

17.4

23.3

 

5,600

11.2

16.8

22.5

 

 

 

 

 

 

5,800

10.8

16.2

21.7

 

 

 

 

 

 

6,000

10.5

15.7

21.0

Notes

Maximum air temperature rise of 40° must not be exceeded.

See table for Electric Heat Kit Availability in various unit sizes.

Air temperature rise is for total heating capacity. Temperature rises at other conditions may be calculated by using the formula:

Temperature Rise = Output Capacity - BTU/h

1.08x ft3/min. Airflow

For altitudes over 2,000’, air temperature rise must be calculated using the formula: Temperature Rise = Output Capacity - BTU/h

14.4x ft3/Min. Airflow x Specific Weight of Air

Operation at less than nominal voltages must be derated by the following factors: 460 volt-0.92; 230 volt-0.92; 208 volt-0.75.

HEAT KIT AVAILABILITY

Unit Size

HKCB20

HKCB30

HKCB40

 

 

 

 

X

X

X

10

X

X

X

X - Heat Kit Available

N/A - Heater Not Available

8

www.goodmanmfg.com

SS-GPCC

 

 

 

Image 8
Contents 10.3 EER Packaged AIR ConditionerAccessories NomenclatureSpecifications Dimensions DIMENSIONS-ELECTRICAL Connections PCC090-X PCC120-X 22⅛Component Pressure Drops CFMAMB. ˚F Evap EAT Mbht MbhsCooling Capacity Data CONT. PCC120-X @ 4,000 CFM STDElectric Heat AIR Temperature Rise HKCB20 HKCB30 HKCB40FAN Performance Data Wiring is subject to DiagramChange. Always refer to the wiring diagram on UnitIs subject to WiringWiring Diagram Wiring Diagram PCC60 20283201 REV