Product Specifications
Heat Kit Electrical Data (Blower Only, Heat Mode)
Model & Heat |
| Circuit #1 | Circuit #2 | Actual kW / | ||
Kit Usage | MCA ¹ | MOP ² | MCA ¹ | MOP ² | BTU@ 240V | |
GPH1524M41A* | 4.3 | / 4.3 | ||||
24 | / 27 | 30 / 30 | 4.75 / 16,200 | |||
34 | / 39 | 40 / 40 | 7.0 / 23,800 | |||
45 | / 52 | 60 / 60 | 9.5 / 32,400 | |||
GPH1530M41A* | 4.3 | / 4.3 | ||||
24 | / 27 | 30 / 30 | 4.75 / 16,200 | |||
34 | / 39 | 40 / 40 | 7.0 / 23,800 | |||
45 | / 52 | 60 / 60 | 9.5 / 32,400 | |||
45 | / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 | |
GPH1536M41A* | 4.3 | / 4.3 | ||||
24 | / 27 | 30 / 30 | 4.75 / 16,200 | |||
34 | / 39 | 40 / 40 | 7.0 / 23,800 | |||
45 | / 52 | 60 / 60 | 9.5 / 32,400 | |||
45 | / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 | |
GPH1542M41A* | 4.3 | / 4.3 | ||||
24 | / 27 | 30 / 30 | 4.75 / 16,200 | |||
34 | / 39 | 40 / 40 | 7.0 / 23,800 | |||
45 | / 52 | 60 / 60 | 9.5 / 32,400 | |||
45 | / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 | |
GPH1543M41A* | 2.9/2.9 | |||||
HKR05A,CA | 24 | / 27 | 30 / 30 | 4.75 / 16,200 | ||
HKR08A,CA | 34 | / 39 | 40 / 40 | 7.0 / 23,800 | ||
HKR10A,CA | 45 | / 52 | 60 / 60 | 9.5 / 32,400 | ||
HKR15A,CA | 45 | / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 |
GPH1548M41A* | 5.8 | / 5.8 | ||||
25 | / 28 | 30 / 30 | 4.75 / 16,200 | |||
38 | / 40 | 40 / 40 | 7.0 / 23,800 | |||
49 | / 56 | 60 / 60 | 9.5 / 32,400 | |||
49 | / 56 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 | |
49 | / 56 | 60 / 60 | 43 / 49 | 60 / 60 | 19.5 / 66,500 | |
GPH1549M41A* | 2.9/2.9 | |||||
HKR05A,CA | 25 | / 28 | 30 / 30 | 4.75 / 16,200 | ||
HKR08A,CA | 34 | / 40 | 40 / 40 | 7.00 / 23,800 | ||
HKR10A,CA | 46 | / 53 | 60 / 60 | 9.50 / 32,400 | ||
HKR15A,CA | 46 | / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 |
HKR20A,CA | 46 | / 52 | 60 / 60 | 43 / 49 | 60 / 60 | 19.50 / 66,500 |
GPH1560M41A* | 7.0 | / 7.0 | ||||
29 | / 30 | 30 / 30 | 4.75 / 16,200 | |||
39 | / 40 | 40 / 40 | 7.0 / 23,800 | |||
51 | / 58 | 60 / 60 | 9.5 / 32,400 | |||
51 | / 58 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 / 48,600 | |
51 | / 58 | 60 / 60 | 43 / 49 | 60 / 60 | 19.5 / 66,500 |
¹ Minimum Circuit Ampacity @ 460 V
²Maximum Overcurrent Protection device @ 460 V
* Revision level that may or may not be designated
C Circuit Breaker option
www.goodmanmfg.com | 35 |