EMI WLCA Maintenance, Filter Removal and Cleaning, FAN Removal, Condensate Tray Removal

Page 17

MAINTENANCE

EVERY 3 MONTHS: Check the air filter condition and clean if necessary (see below).

EVERY 6 MONTHS: Same as 3 months plus clean conden- sate tray with biocide suitable for polystyrene and clean fas- cia.

EVERY 12 MONTHS: Same as 6 months plus check all electrical connections for security, check condensate pump operation, and check the heating and cooling action to en- sure proper operation.

FILTER REMOVAL AND CLEANING

1.Ensure the unit is isolated from the electrical sup- ply and ensure that the fan(s) has come to a com- plete stop.

2.Unclip the catches along the edge of each grille and allow them to hang from the fascia by the molded plastic hinges located along the opposite edge.

3.If desired, the grilles can be removed from the fas- cia completely.

4.The filter can now be easily slid out of the small plastic retaining clips on the back of each grille.

5.Gently vacuum clean the filters on a medium power vacuum.

6.Replace filters by reversing steps 2 to 4.

NOTE: EMI recommends you keep at least one full set of cassette air filters as spares.

FAN REMOVAL

CAUTION: Isolate from the electrical supply before commencing work!!

1.Unclip the grille catches and remove the grille(s) from the fascia.

2.For medium and large-sized units, remove the M6 screws from the black plastic inlet ring and pull the inlet ring downwards from the condensate tray. For small units only, remove the fascia by loosening the four fascia mounting bolts and then slide the fascia horizontally until it releases from the chas- sis. Drain the condensate tray by removing the small black rubber drain plug, catching the con- densate (if any) in a suitable container. Remove the self tapping screws securing the two insulated metal condensate tray support channels and pull the channels away from the condensate tray. Pull the condensate tray downwards away from the chas- sis.

3.Remove the electrical panel lid and disconnect the fan connections from within the electrical panel.

4.Rotate the fan by hand until two M6 nuts are visible through the fan mounting access holes. Remove the two nuts.

5.Rotate the fan 90° until the remaining two nuts are visible and remove while supporting the fan to pre- vent it from falling. The fan can now be dropped down from the unit.

CONDENSATE TRAY REMOVAL

1.Unclip the grille catches and remove the grille(s) from the fascia.

2.Remove the fascia by loosening the fascia mount- ing bolts and sliding the fascia horizontally until it releases from the chassis. If unit is micropro- cessor controlled, remove display panel cable from within the electrical panel before remov- ing the fascia.

3.Remove electrical panel lid by unscrewing the single self tapper and pull the lid horizontally away from the control box.

4.On medium and large sized units, disconnect the main wiring from the incoming terminal block and disconnect the fan wires from their connection points within the electrical panel. Separate any two part connectors coming from the electrical panel.

5.Drain the condensate tray by removing the small black rubber drain plug, catching any condensate in a suitable container.

6.Remove the self tapping screws securing the two insulated metal condensate tray support channels and pull the channels away from the condensate tray. Pull the condensate tray, complete with inlet ring (on medium and large sized units only) down- wards away from chassis.

CONDENSATE PUMP REMOVAL

1.Disconnect condensate pump and float switch wires from inside electrical panel.

2.Unscrew the three M4 screws holding the pump inspection plate in place and pull the pump and mounting bracket away from the chassis while feed- ing the pump wires between condensate tray and insulation.

ENVIROMASTER INTERNATIONAL LLC

17

EMI@ENVIROMASTER.COM

Image 17
Contents Controls and Components General StatementProduct Description Positioning Site InstallationCabinet Electrical Data Refrigeration System DX Units Start UP ProceduresEMI Cassette CAH/W, CAF/4 EMI Cassette Mechanical Data Cabinet DimensionsSmall Cabinet EMI Cassette DimensionsLarge Cabinet Medium CabinetInfrared Receiver & Fascia Display Panel Microprocessor ControllerInfrared Transmitter Display IndicatorsHOW to SET the Present Time Setting UP the BUILT-IN Time ClockControl Circuit Checks DX Units Unit Start UP Indoor UnitUnit will not Operate Troubleshooting SectionPossible CAUSES/REMEDIES Water Leaking from UnitNo Heating Heat Pump Coil FreezeNo Cooling Electric Overheat Fans will not RUNPossible CAUSES/REMEDIES Filter Removal and Cleaning MaintenanceFAN Removal Condensate Tray RemovalAppendix a Wiring Charts and Instructions Appendix B Exploded Unit Drawing and Parts List Large Cabinet Appendix C Exploded Unit Drawing and Parts List

WLCA specifications

EMI WLCA, or Electromagnetic Interference Wireless Lightning Control Architecture, represents a groundbreaking evolution in the realm of electromagnetic interference mitigation technologies. Designed to safeguard sensitive electronic systems from the potentially detrimental effects of electromagnetic disturbances, EMI WLCA integrates a host of advanced features and characteristics that empower both industries and consumers.

One of the primary features of EMI WLCA is its ability to operate across various frequencies. This versatility ensures that it can mitigate interference from a wide range of sources, whether they originate from industrial machinery, communication devices, or environmental factors. By effectively filtering out these unwanted signals, the technology facilitates more stable and reliable performance in electronic systems.

At the heart of EMI WLCA lie several state-of-the-art technologies that enhance its efficiency. Adaptive filtering is a key component, allowing the system to dynamically adjust its response based on the detected interference levels. This real-time adjustment capability ensures optimal performance, minimizing lag and improving responsiveness in critical applications, such as aviation, telecommunications, and medical devices.

Another notable characteristic of EMI WLCA is its modular design. This allows for easy integration into existing systems, enabling manufacturers to incorporate the technology without necessitating an overhaul of their current infrastructure. The modularity also facilitates future upgrades, ensuring that systems can adapt to changing standards and emerging interferences.

In addition to its impressive technical specifications, EMI WLCA is designed with user-friendliness in mind. Comprehensive monitoring tools provide users with insightful data on interference levels and the effectiveness of the mitigation strategies being employed. This transparency not only aids in troubleshooting but also enhances overall system performance by allowing users to make informed adjustments as needed.

Moreover, EMI WLCA is built to meet stringent regulatory compliance standards. This ensures its broad applicability across various sectors, including aerospace, automotive, and consumer electronics. As technology continues to advance, the RF environment becomes increasingly crowded, making solutions like EMI WLCA not only desirable but essential.

In conclusion, EMI WLCA stands out as a significant advancement in electromagnetic interference control technology. With its adaptive filtering capabilities, modular design, user-friendly monitoring tools, and compliance with industry regulations, EMI WLCA promises to enhance the reliability and performance of electronic systems across diverse applications. As the demand for interference-resistant technology grows, innovations like EMI WLCA will undoubtedly play a critical role in shaping the future of electronic design and implementation.