Bard P1148A1 Adjustments, Alarm Output, Adjustable DELAY-ON-MAKE and DELAY-ON-BREAK Timer

Page 15

ALARM OUTPUT

Alarm terminal is output connection for applications where alarm signal is desired. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.

ADJUSTMENTS

ADJUSTABLE DELAY-ON-MAKE AND DELAY-ON-BREAK TIMER

The potentiometer is used to select Delay-on-Break time from 30 seconds to 5 minutes. Delay-on-Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay-on-Break (DOB) setting:

0.5 minute

(30 seconds)

DOB

=

123 second DOM

1.0 minute

(60 seconds)

DOB

=

126 second DOM

2.0 minute

(120 seconds)

DOB

=

132 second DOM

3.0 minute

(160 seconds)

DOB

=

138 second DOM

4.0 minute

(240 seconds)

DOB

=

144 second DOM

5.0 minute

(300 seconds)

DOB

=

150 second DOM

Manual 2100-324 Page 13

Image 15
Contents Installation Instructions Single Package AIR Conditioners Contents Getting Other Information and Publications Electrical Data Htr. KW Optional FIELD-INSTALLED Electric Heater TableGeneral Field Installed Heater Packages OptionalGeneral Instructions Shipping Damage44-7/8 Field Fabricated CurbingAir Conditioning Roof Hood Unit ModelRated CFM External Static Pressure ESP WET Coil Cooling InstallationTypical Installations LocationElevated Mounting Platforms Airflow and Service Access ClearancesRoof TOP Application Slab Mounting AT Ground Level Above 32 F Outside TemperatureCondensate Drain Trap Condensate Drain TrapAIR Filters Recommended FiltersThermostats Wiring Main PowerWiring 24V LOW Voltage Control Circuit Transformer TapsLOW Voltage Wiring Start UP Notes Three Phase Scroll Compressor Start UP InformationStart UP and Operation Sequence of OperationAdjustments Alarm OutputAdjustable DELAY-ON-MAKE and DELAY-ON-BREAK Timer Service and Troubleshooting Brazing Diagram Return Air Pressure 100 105 110 115 Model TemperaturePressure Table Manual Manual Manual Manual Manual Manual

P1060A1, P1142A3, P1148A1 specifications

Bard P1148A1, P1142A3, and P1060A1 are high-performance vascular access products designed to meet the diverse needs of medical professionals in various healthcare settings. These devices, developed by Bard, are renowned for their innovative technologies and superior characteristics that enhance patient care and facilitate clinical procedures.

The Bard P1148A1 is a peripherally inserted central catheter (PICC) designed for long-term intravenous therapy, including chemotherapy and antibiotics. Its key features include a strong yet flexible design that allows for easy insertion and maintenance of the catheter over extended periods. The P1148A1 utilizes advanced materials that minimize the risk of thrombosis and infection, pivotal considerations in central line management. The catheter is equipped with a specialized tip configuration that promotes optimal blood flow and reduces complications.

Moving to the Bard P1142A3, this device serves a similar purpose but incorporates unique technologies that enhance its usability. The P1142A3 boasts a hydrophilic coating which facilitates smoother insertions and reduces friction during catheter placements. This is particularly valuable in pediatric and geriatric populations, where gentler approaches are essential. Additionally, the P1142A3 is engineered with multiple lumens, allowing simultaneous administration of fluids, medications, and blood products. This multipurpose functionality enhances efficiency in clinical settings, reducing the need for multiple venipunctures.

On the other hand, the Bard P1060A1 is designed with a focus on short-term vascular access. This catheter is particularly effective for emergency situations and critical care, offering rapid placement and reliable performance. One of its main characteristics is a streamlined design that minimizes the overall footprint, making it an ideal choice for patients with limited vein access. The P1060A1 is also equipped with a safety mechanism that reduces the risk of accidental needlesticks, addressing a critical safety concern in medical environments.

Overall, Bard's P1148A1, P1142A3, and P1060A1 products exemplify innovation in vascular access technology. With features designed to enhance insertion techniques, improve patient outcomes, and ensure safety in healthcare settings, these catheters stand as key tools in modern medical practice. Their robust design and advanced materials align with the needs of both healthcare providers and patients, making them essential components of effective vascular access strategies.