Bard W12A2-A installation instructions Wiring Main Power, Wiring LOW Voltage Wiring

Page 12

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” of “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

For wiring size and connections, refer to Wiring Manual 2100-507.

WIRING – LOW VOLTAGE WIRING

230/208, 1 phase equipment use dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the

240 and 208V taps are:

Tap Range

240253 - 216

208220 - 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

Manual

2100-509E

Page

12 of 17

Image 12
Contents W12A2-A W12A1-K Contents Getting Other Information and Publications Wall Mount General Information AIR Conditioner Wall Mount Model NomenclatureElectric Heat Table Unit Dimensions Back ViewElectrical Heat Specifications Single Circuit Shipping DamageGeneral Duct Work FiltersFresh AIR Intake Condensate DrainInstallation Instructions Wall Mounting InformationMounting the Unit Mounting Instructions Wall Mounting Instructions Common WALL-MOUNTING Installations Wiring Main Power Wiring LOW Voltage WiringSafety Practices Start UPTopping OFF System Charge Important Installer Note Service HintsHigh & LOW Pressure Switch Sequence of OperationAdjustments Pressure Service PortsAdjustable Delay on Make and Delay on Break Timer Typical Settings for Dual Unit InstallationTroubleshooting FAN Blade Setting DimensionsRefrigerant Charge Optional Field Installed Accessories Pressure TableW12Aà

W12A2-A specifications

The Bard W12A2-A is a cutting-edge piece of equipment that has gained significant attention in the industrial sector for its innovative design and advanced features. Renowned for its efficiency and reliability, the W12A2-A is an essential tool for various applications, particularly in manufacturing and performance-heavy operations.

One of the standout features of the Bard W12A2-A is its powerful engine, which provides exceptional torque and horsepower, allowing it to operate seamlessly under demanding conditions. This engine is paired with an advanced transmission system that ensures smooth and responsive acceleration, making it a preferred choice for professionals who require precision in their work.

In terms of technology, the Bard W12A2-A integrates state-of-the-art automation systems that enhance productivity and reduce operational costs. The onboard computer system is equipped with real-time monitoring capabilities, allowing users to track performance metrics and conduct diagnostics with ease. This level of intelligence not only assists in preventive maintenance but also optimizes the overall uptime of the machine.

The Bard W12A2-A also incorporates advanced safety features designed to protect operators and prevent accidents. Its robust structural design is complemented by a suite of sensors that continuously monitor the machine's performance, alerting users to any potential hazards before they escalate into significant issues. This focus on safety is critical in high-stakes environments.

Furthermore, the W12A2-A is recognized for its superior build quality, utilizing durable materials that withstand the rigors of industrial use. This ensures longevity and minimizes the need for frequent repairs or replacements, offering excellent value for investment.

Ergonomically designed, the Bard W12A2-A prioritizes user comfort, with an intuitive control panel and customizable settings that cater to a wide range of operational preferences. This thoughtful approach to design enhances the user experience and boosts overall productivity.

Overall, the Bard W12A2-A stands out in the market for its combination of power, advanced technology, safety features, and user-friendly design. Whether used in manufacturing, logistics, or any performance-based industry, the W12A2-A promises to deliver high efficiency and exceptional reliability, making it a formidable asset for any operation seeking to enhance productivity and maintain high standards.