Friedrich MS24Y3F specifications Error Contents outdoor unit

Page 13

ERROR CONTENTS (outdoor unit)

1.Make a TEST RUN in accordance with the in- stallation instruction sheet for the indoor unit.

2.OUTDOOR UNIT LEDS

When a malfunction occurs in the outdoor unit, the LED on the circuit board lights to indicate the error. Refer to the fol- lowing table for the description of each error according to the LED.

LED

Error contents

1 flash

Communication error

(Indoor unit - Outdoor unit)

 

 

 

2 flash

Discharg pipe temperature sensor

 

 

3 flash

Outdoor heat exchanger temperature sensor

 

 

4 flash

Outdoor temperature sensor

 

 

7 flash

Compressor temperature sensor

 

 

8 flash

Heat sink temperature sensor

 

 

9 flash

Pressure switch abnormal

 

 

12 flash

IPM error

 

 

13 flash

Compressor rotor position cannot detect

 

 

14 flash

Compressor cannot operate

 

 

15 flash

Outdoor fan abnormal (upper fan)

 

 

16 flash

Outdoor fan abnormal (lower fan)

 

 

lighting

No error

 

 

2.When the product is operating:

1 Press the PUMP DOWN switch on the outdoor unit. The LED on the outdoor unit circuit board lights, and operation stops. At this point, recovery has not been completed, so do not close the two- and three-way valves.

2The pump down operation (cooling operation) be- gins after three minutes. Close the three-way valve (liquid) after operation starts.

3After 2 - 3 minutes, operation stops. Close the three- way valve (gas) within one minute after operations stops.

4The LED will go out three minutes after it stops. Dis- connect the power supply after confirming that the LED has gone out.

*When the pump down operation is repeated, temporarily disconnect the power supply after opening the closed valves (both liquid and gas). Reconnect the power supply after 2 - 3 minutes and perform the pump down operation.

*When the start of the operation after pump down operation has been completed, temporarily disconnect the power supply after opening the closed valves (both liquid and gas).

Reconnect the power supply after 2-3 minutes and be sure to perform a test operation for cooling.

3-way valve (Liquid)

SPECIAL INSTALLATION SETTING

PUMP DOWN (Refrigerant collecting operation)

Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit.

1. When the product is stopped:

1Press the PUMP DOWN switch on the outdoor unit. (The LED on the outdoor unit circuit board lights.)

2The pump down operation (cooling operation) be- gins right away. After oparation starts, close the three-way valve (liquid).

3After 2 - 3 minutes, operation stops. Close the three- way valve (gas) within one minute after operations stops.

4The LED will go out three minutes after it stops.Dis- connect the power supply after confirming that the LED has gone out.

3-way valve (Gas)

PUMP DOWN SW (SW2)

DANGER

This part (Choke coil) generates high voltages. Never touch this part.

2006.02.14

12

Image 13
Contents Floor Console Under Ceiling ContentsElectrical Data SpecificationsOutline and Dimensions Outdoor Unit Outdoor Unit Indoor Unit Refrigerant System DiagramAssy Circuit DiagramActive Indoor PCB Circuit Diagram Outdoor PCB Circuit Diagram Controller PCB Assembly Power Supply PCB Assembly Error Contents Indoor unit Error Contents outdoor unit Disassembly Assembly 439 983 416 385 417 771 488 472 443 473 Optional Parts 2006.06.13 500 506 Outdoor Unit Outdoor Unit Outdoor Unit Outdoor Unit Parts List Outdoor Unit Indoor Unit Accessories Standard AccessoriesRemote Control Unit 0605G3090