C.What happens when the replace battery LED does not clear? If the self test fails:
■If the battery capacity is greater than 75%, turn the unit off and restart it. When you turn a Smart- UPS on, it will initiate a
■If the unit fails the
phone:
V.Increasing ‘Runtime Remaining’ of the
Discharging and recharging a
A.Initiating a runtime calibration
The runtime calibration option is accessible using Powerchute PLUS software or an APC SmartSlot Accessory. Once the battery capacity reaches 100%, select this option. The unit will run on battery until battery capacity is 25%. At that point, the unit will return to utility power and begin recharging itself. If the runtime as seen through Powerchute PLUS or SmartSlot Accessory does not increase, then follow the instructions in the next section.
Note: APC recommends that a runtime calibration be initiated once every six months at a maximum.
B.Disconnect from utility
By disconnecting the UPS from utility, a premature low battery signal can be prevented. It is recom- mended that the power to the circuit be turned off at the distribution panel. Unplugging the
Note: The
If experiencing low runtime or premature low battery signal issues, contact APC Customer Support (email: support.apcc.com or phone: