Replacement Battery Cartridge(RBC) Addendum
RBC5, RBC6, RBC7, RBC8, RBC9, RBC11, RBC12, RBC22, RBC23, RBC24, RBC25, RBC27, RBC28, RBC5I, RBC6I, RBC7I, RBC8I, RBC9I, RBC11I, RBC12I, RBC22I, RBC23I, RBC24I, RBC25I, RBC5J, RBC6J, RBC7J, RBC8J, RBC11J, RBC12J,
This addendum does not apply to
I. Installation
Follow the installation illustration on the accompanying sheet.
Note: Small sparks at the battery connectors are normal during connection.
II.Post-Installation
Once installed,
allow the unit to charge for five hours. If the unit is an XL model, allow it to charge for
24 hours.
Note: The
III. Clearing the Replace Battery LED
A.In order for the replace battery LED to be cleared, it is necessary to run a valid self test. For a self test to be considered valid, the following conditions must be satisfied:
■battery capacity must be greater than 75%(minimum of four battery bar graph LEDs illuminated) or
■
B.Ways to initiate a self test
A self test can be initiated in any one of five ways:
■Start up of the UPS
■
■Powerchute PLUS software
■SmartSlot Accessory
■ Automatic timer- every two weeks from turn on (see APC owners manuals for details)
IV. Verifying Operation
A.What happens during a self test?
When a self test is initiated, the unit supports the load while operating on battery for approximately
B.When should the self test be performed?
After the unit has charged for five hours, a self test can be performed.