APC SURM2U, SU700RM2U, SU1000RM2U, SU1400RM2U manual Battery Replacement Procedure

Page 1

SURM2U Replacement Battery Cartridge installation Guide

This UPS has an easy to replace hot-swappable battery tray. Battery replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and the protected equipment on for the following procedure. See your dealer or www.apcc.com for more information.

 

Smart-UPS Model

Replacement Battery Cartridge

 

 

SU700RM2U

RBC22

 

 

 

 

 

 

SU1000RM2U

RBC23

 

 

 

 

 

 

SU1400RM2U

RBC24

 

 

 

 

 

 

SU1400RMJ2U

RBC24J

 

 

 

 

 

Please read before replacing the battery tray:

Once the battery is disconnected, the connected equipment is not protected from power outages.

Battery Replacement Procedure

1. The battery tray is accessible from the front of the UPS.

2. Be careful removing the battery tray – it is heavy.

3. This procedure requires a Phillips head screwdriver.

4. Small sparks at the battery connectors are normal during re-connection.

￿

 

￿

 

￿

￿

￿

￿

1.Face the front of the UPS and, using both hands, insert each index finger behind the lip of the curved section of the front panel bezel and pull towards you. The front panel bezel will unsnap.

2.Set the bezel aside.

3.Take out the white cord, which is tucked into the space above the battery connector ￿. Grasp the cord and pull firmly towards you to disconnect the battery.

4.Use a Phillips head screwdriver to remove the four (4) screws ￿ that secure the battery tray. Set the screws aside.

5.Use the battery tray handle ￿ to slide the tray out halfway. Then hold the tray from the sides and slide it out to the maximum extended position. A stop tab ￿ on the bottom of the tray will prevent the tray from coming out completely.

￿

990-#### Rev.01 11/01

6.Carefully lift the tray up so that the stop tab ￿ clears the ledge on the unit.

7.Return the battery tray to APC using the package in which your replacement tray shipped .

The battery replacement kit includes a new battery tray.

8.Hold the new tray on the sides and align it with the opening.

9.Raise the back of the tray up slightly to position the stop tab on the inside of the opening. Then level the tray and push it in completely.

10.Remove the tape on the new battery tray connector to expose the cable connector.

11.Locate the UPS battery connector ￿ which is to the right of the battery tray and recessed. Connect the battery cable connector to the UPS connector. Press firmly to ensure that the connection is tight. You will hear a “snap” when the connector is properly seated.

12.Replace the four (4) screws removed in step 4.

13.Tuck the white battery cable cord neatly into the space above the UPS connector.

14.Hold the front panel bezel with the cutout section on the right. Align the tabs on the side of the bezel with the slots on the front of the UPS ￿ and firmly snap it into place.

Image 1
Contents SURM2U Replacement Battery Cartridge installation Guide Battery Replacement Procedure
Related manuals
Manual 2 pages 19.59 Kb

SU1000RM2U, SURM2U, SU1400RM2U, SU700RM2U specifications

The APC SU700RM2U, SU1400RM2U, SURM2U, and SU1000RM2U are part of APC's Smart-UPS series, renowned for their reliability and innovative features tailored for both small businesses and larger enterprises. These uninterruptible power supplies (UPS) are designed to provide a dependable power backup to ensure that critical systems remain operational during power outages or fluctuations.

One of the standout features across these models is the pure sine wave output. This technology is crucial for sensitive electronics as it ensures that devices receive clean and stable power, preventing potential damage and operational disruptions. The Smart-UPS series also includes automatic voltage regulation (AVR), which stabilizes voltage fluctuations, maintaining the proper voltage levels to connected devices and enhancing their longevity.

The APC SU700RM2U provides 700VA/490W of pure sine wave output and is well-suited for protecting smaller servers, networking devices, and other essential equipment. It features a compact 2U rack-mount design, making it an ideal choice for space-constrained environments. Additionally, its built-in LCD interface allows users to easily monitor the unit's status and receive real-time updates on battery levels and load conditions.

Stepping up in capacity, the APC SU1400RM2U delivers 1400VA/980W, making it suitable for more robust applications. This model, like its counterparts, boasts scalable runtime and is compatible with external battery packs. This scalability means that users can extend battery runtime easily, ensuring that crucial operations can continue even during extended outages.

The APC SURM2U, although less commonly referenced, is often included in discussions of rack-mount solutions, providing essential management features and centralized control for multiple units in a data center environment. It complements the other models by offering network management capabilities, which include SNMP and web interface options.

Meanwhile, the SU1000RM2U with 1000VA/670W output power provides an ideal balance for growing businesses. Its management features, including hot-swappable batteries, make maintenance hassle-free without disrupting connected loads.

In conclusion, the APC SU700RM2U, SU1400RM2U, SURM2U, and SU1000RM2U represent a diverse range of solutions in the Smart-UPS series. With cutting-edge technologies like pure sine wave output, AVR, and seamless scalability, these UPS systems are designed to protect sensitive equipment from power-related issues, ensuring consistent and reliable operation across various applications.