501 Insulation Tester
The model 501 can be used for general purpose insulation tests that require voltages from 50V to 1000V only.
The Instrument is equipped with AC and DC measuring ranges up to 1000V. This is advantageous for testing for the absence of voltage and the discharge of capacitive devices under test.
The 501 features a quick testing signal lamp within the test probe that illuminates the work area. The signal lamp can also be used for quick Pass/Fail evaluations of insulation resistances. Minimum values for insulation resistances are present if the lamp lights up.
Comes equipped with
•Five Test Voltages: 50, 100, 250, 500, and 1000 VDC
•Voltage Measurement to 1000 V AC/DC
•Test Probe Signal Lamp Illuminates Work Area and Indicates Pass/Fail of Insulation Resistance
•Battery Powered with Battery Test and Battery Charge Indicator
•Rugged Tester Design for Industrial Applications with Leatherette Carrying Case
Measuring Ranges
INSULATION RESISTANCE
Measuring |
|
|
|
|
|
|
| Lamp in Test Prod 1) | ||
Range | Uo | Internal Resistance R i |
| Lights for Resistance | ||||||
0…50KΩ |
|
|
|
| 30KΩ |
|
| > 100KΩ | ||
20KΩ…1MΩ | 60V |
|
| 10KΩ |
|
|
| |||
200KΩ…20MΩ |
|
|
|
| 40KΩ |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
0…100KΩ |
|
|
|
| 60KΩ |
|
| > 200KΩ | ||
40KΩ…2MΩ | 120V |
|
| 20KΩ |
|
|
| |||
400KΩ…40MΩ |
|
|
|
| 80KΩ |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
0…250KΩ |
|
|
|
| 150KΩ |
|
| > 500KΩ | ||
100KΩ…5MΩ | 300V |
|
| 50KΩ |
|
|
| |||
1MΩ…100MΩ |
|
|
|
| 200KΩ |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
0…500KΩ |
|
|
|
| 300KΩ |
|
| > 1MΩ | ||
200KΩ…10MΩ | 600V |
|
| 100KΩ |
|
|
| |||
2MΩ…200MΩ |
|
|
|
| 400KΩ |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
0…1MΩ |
|
|
|
| 600KΩ |
|
| > 2MΩ | ||
400KΩ…20MΩ | 1200V |
|
| 200KΩ |
|
|
| |||
4MΩ…400KΩ |
|
|
|
| 800KΩ |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
0…4KΩ | 9V |
|
| - |
| - | ||||
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| (1) Switching Accuracy | |
DIRECT AND ALTERNATING CURRENT |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| ||
Measuring |
|
|
| Internal |
| Maximam |
|
| ||
Range |
| Frequency |
| Resistance |
| Overload |
| Intrinsic Error (1) | ||
0 to 1000V |
| 0 or 40 to 200Hz |
| 900KΩ |
| 1200V AC/DC |
| ±2.5% | ||
AC/DC |
|
|
|
|
|
| Continuous |
|
| |
|
|
|
|
|
|
|
|
| (1) Referring to scale length |
Ordering Information
ACCESSORIES | Catalog No. |
501 Insulation Tester, 1000 V | 12501 |
|
|
Specifications
REFERENCE CONDITIONS
Ambient Temperature: 73°F (23°C) ± 4°F (2°C)
Relative Humidity: 45 to 55%
Measurement Magnitude Frequency:
Line Voltage Waveform: Sine, deviation between effective and rectified value < .5%
Battery Voltage: 9V ± .5V
Operating Position: Horizontal
ELECTROMAGNETIC COMPATIBILITY EMC
Interference Emission:
EN
Interference Immunity:
EN
ELECTRICAL SAFETY
Designed to IEC
Protection Class: II
Test Voltage: 5.55Kv
Overvoltage Classification: II
Pollution Degree: 2
Protection: Housing IP52
AMBIENT CONDITIONS
Operating Temp. Range: 32°F (0°C) to 104°F (40°C)
Storage Temp. Range:
Relative Humidity: Max.
MECHANICAL DESIGN Dimensions: W 6.50” (165mm) x D 4.33” (110mm) x H 4.92” (125mm) Weight: 3.5 lbs. (1.6kg) (with batteries)
POWER SUPPLY
Standard or Storage Battery: 6 ea. 1.5V “D” size batteries
Working Range: 7V to 10V
Battery Service Life: Number of possible measurements with 1 set of “D” size
batteries (with lamp in test prod switched off): at least 3,000 measurements of an insulation resistance of 1MΩ (Nominal Voltage of1000 V, 5 sec. Measurement duration, switched off for 25 sec. etc.)
rev_1 11/2/04