Bryant 538J-18-1 manual START-UP Preliminary Checks, II. Leak Test, III. Evacuate and Dehydrate

Page 7

Table 2 — American/European Wire Conversions

 

AMERICAN

EUROPEAN

Industry

 

American Conversion

Industry Standard

Standard Size

 

(mm)

Size (mm2)

18 AWG

 

0.82

1.0

16 AWG

 

1.30

1.5

14 AWG

 

2.08

2.5

12 AWG

 

3.30

4.0

10 AWG

 

5.25

6.0

8 AWG

 

6.36

10.0

6 AWG

 

13.29

16.0

4 AWG

 

21.14

25.0

3 AWG

 

26.65

2 AWG

 

33.61

35.0

1 AWG

 

42.39

50.0

1/0 AWG

 

53.49

2/0 AWG

 

67.42

70.0

3/0 AWG

 

85.00

95.0

4/0 AWG

 

107.19

120.0

250 kcmil

 

126.64

150.0

300 kcmil

 

151.97

350 kcmil

 

177.90

185.0

400 kcmil

 

202.63

240.0

500 kcmil

 

253.29

300.0

600 kcmil

 

303.95

LEGEND

AWG — American Wire Gage kcmil — Thousand Circular Mils

START-UP

I.PRELIMINARY CHECKS

1.Check that all internal wiring connections are tight and that barriers, covers, and panels are in place.

2.Make certain field electrical power source agrees with unit nameplate rating.

3.Open all service valves.

II. LEAK TEST

Field piping and fan coil must be leak tested by the pressure method. Use R-22 at approximately 25 psig (172 kPa) backed up with an inert gas to a total pressure not to exceed 245 psig (1690 kPa).

III. EVACUATE AND DEHYDRATE

Field piping and fan coil must be evacuated and dehydrated.

IV. CHARGE SYSTEM

Release factory charge into system by opening (backseating) liquid and suction line service valves. Add charge amount as required for the total system. Refer to separate indoor unit installation instructions for the required total system charge when connected to the indoor unit.

V. TO START UNIT

NOTE: When using 538J unit in conjunction with 619 series fan coils, refer to start-up instructions included with fan coil for correct start-up procedures.

Be sure that field disconnect is closed. Set room thermostat below ambient temperature. Operate unit for 15 minutes, then check system refrigerant charge. See Refrigerant Charging section on page 8.

Unit compressor starts after a 5-minute delay if equipped with accessory Time Guard® II device.

SERVICE

WARNING: Before performing recommended main- tenance, be sure unit main power switch is off. Failure to do so may result in electrical shock or injury from rotat- ing fan blade.

I. OUTDOOR FAN

A reinforced wire mount holds the outdoor fan assembly in place. See Fig. 7 for proper mounting positions.

UNIT 538J DIMENSIONS — in. (mm)

018

024-036

048-060

0.433 (11)

0.709 (18)

0.16 (4)

Fig. 7 — Condenser Fan Mounting Positions

II. HIGH-PRESSURE RELIEF VALVE

Valve is located in compressor. Relief valve opens at a pressure differential of approximately 450 ± 50 psig (3100 ± 345 kPa) between suction (low side) and discharge (high side) to allow pressure equalization.

III.INTERNAL CURRENT AND TEMPERATURE SENSITIVE OVERLOAD

Control resets automatically when internal compressor motor temperature drops to a safe level (overloads may require up to 45 minutes to reset). When an internal over- load is suspected of being open, check by using an ohmmeter or continuity tester.

IV. PUMPDOWN PROCEDURE

The system may be pumped down in order to make repairs on low side without losing complete refrigerant charge.

To pump down:

1.Attach pressure gage to suction service valve gage port.

2.Frontseat the liquid line valve.

CAUTION: The 538J unit coils hold only the factory-designated amount of refrigerant. Additional refrigerant may cause units to relieve pressure through compressor internal pressure relief valve (indicated by sudden rise of suction pressure) before suction pressure reaches 5 psig (34 kPa). If this occurs, shut off unit immediately, then frontseat the suction valve and remove and reclaim excess refrigerant fol- lowing accepted practice.

3.Start unit and run until suction pressure reaches 5 psig (34 kPa).

4.Shut unit off and frontseat suction valve.

5.Depressurize low side of unit and recover refrigerant following accepted practice.

7

Image 7
Contents Safety Considerations ContentsInstallation Complete PRE-INSTALLATION Checks 538J018-060 Dimensional Drawing Rigging II. RIG and Mount UnitMounting on Ground Mounting on RoofIV. Make Electrial Connections Accessory InstallationPhysical Data SI Physical Data EnglishIFR IFMSTART-UP Preliminary Checks Service Outdoor FANIII. Internal Current and Temperature Sensitive Overload IV. Pumpdown ProcedureVIII. Refrigerant Charging LOW Pressure SwitchVI. Service Valves VII. Accurater Bypass Type DeviceOutdoor Indoor Coil Entering AIR F WB Temp F Subcooling Method Cooling, TXVRequired Liquid Line Temperature C SI At Service Valve Maintenance LubricationIII. Cleaning Coils Required Liquid Line Temperature F English At Service ValveTroubleshooting Troubleshooting Chart Cooling Cycle Copyright 2002 Bryant Heating & Cooling Systems

538J-18-1 specifications

The Bryant 538J-18-1 is a high-performance air conditioning unit designed to provide optimal comfort and efficiency in residential and light commercial settings. This model is notable for its advanced technology and robust design, catering to the needs of modern consumers looking for reliable climate control solutions.

One of the main features of the Bryant 538J-18-1 is its energy-efficient operation. Equipped with a SEER (Seasonal Energy Efficiency Ratio) rating that exceeds the minimum standards, this unit helps homeowners save on energy costs while reducing their environmental footprint. The unit’s compressor utilizes variable speed technology, allowing it to adjust its operation based on cooling demand. This not only enhances energy efficiency but also contributes to quieter performance.

The Bryant 538J-18-1 is constructed with durable materials to endure various weather conditions. Its cabinet is made with galvanized steel, ensuring longevity and resistance to rust. Additionally, the unit features a powder-coated finish that protects against UV rays and other environmental stressors, enhancing both aesthetics and durability.

Smart technologies are integrated into the Bryant 538J-18-1, making it compatible with advanced climate control systems. The unit can be seamlessly connected to smart thermostats, allowing users to monitor and adjust settings remotely through mobile applications. This feature promotes convenience and allows for precise temperature control, ensuring optimal comfort throughout the home.

The unit's refrigerant choice also reflects a commitment to environmental responsibility. The Bryant 538J-18-1 utilizes R-410A refrigerant, which is known for its lower impact on the ozone layer compared to older refrigerants. Furthermore, the unit is designed for easier serviceability, with access panels that simplify maintenance and repairs.

In terms of specifications, the Bryant 538J-18-1 boasts a cooling capacity of 1.5 tons, making it suitable for a variety of indoor environments. The operational sound levels are minimal due to its innovative design, which incorporates sound-dampening features, ensuring a peaceful atmosphere.

Overall, the Bryant 538J-18-1 stands out as a reliable, efficient, and technologically advanced air conditioning solution, making it an excellent choice for those seeking comfort without compromising on sustainability or performance. With its array of features and innovative technologies, this unit is well-equipped to meet the diverse needs of modern living spaces.