Omega Vehicle Security PX548 manual Installation

Page 4

Installation

CAUTION:

1.INCORRECT ELECTRICAL CONNECTIONS CAN, IN CERTAIN CIRCUMSTANCES, DESTROY THE ELECTRONIC OUTPUT CIRCUIT.

2.BEFORE APPLYING ELECTRICAL POWER, MAKE SURE THE SUPPLY VOLTAGE IS TO THE CORRECT RATING.

3.THIS A VERY SENSITIVE SENSOR, ONLY APPLY PRESSURE WITHIN THE PRESSURE RANGE.

Mounting

Two M5 threaded holes in the base of the sensor provide mounting points.

Note: The screws must not enter the holes more than 0.4" into the sensor body.

The installed position of the sensor should be away from sudden temperature variations, shocks and vibrations and should not be close to strong electromagnetic fields (transformers, motors etc.). The sensor can be mounted in any position, but mounting at an angle may require zero adjustment. For very low pressure sensors (less than 2.0 inH2O) the recommended mounting is horizontal.

PX548 Series (Unidirectional voltage output)

Minimum load 2 kW

Note: Connections 5 and 6 are common

If the output cable passes through an area of electrical disturbance, use a recommended load impedance of between 2 kW and 10 kW . Connect the load resistance between the wires corresponding to signal and - terminal at a point furthest from the sensor.

zero adjustment (fine)

zero adjustment (coarse)

square root output selection switch (optional)

gland nut (cable entry)

span adjustment

filter time response selector switch

terminal connector block

pressure connector

PX548 Series bidirectional operation using bipolar power supply (±12 Vdc) with bidirectional output (0±5 Vdc or 0±2.5 Vdc)

Connect the power supply to + for positive, - for negative, and 0 for neutral; connect the output to signal for positive and 0 for negative signal.

Minimum load 1 kW

Pressure connections

The high pressure connector is marked + and the low pressure connector is marked .

Purging or de-gasing the sensor

Two 5 mm hexagonal socket bleed screws are located on the outer casing and can be loosened to bleed the two pressure connectors. Make sure that these screws are tightened after this operation.

Internal detail

Electromagnetic Interference

To avoid electrical interference, use shielded cable with the shield connected to the earth ground at both ends. The ground of the sensor can be the casing or the ground terminal screw.

Electrical connections

PX548 Series (current output)

The maximum allowable load resistance is calculated to formula:

R Max = 0.05 (V supply - 10) kW

Where: R Max in kW and V in Volts

Note: It is possible to changeover the bleed screws and pressure connectors enabling easier access or permitting installation in a difficult position.

Square root output option

This option only applies to the LPX 5000 sensor with 4 to 20 mA two wire connection and the square root electronics assembly fitted. A switch next to the terminal block selects the output mode.

Switch

Output mode

 

 

OFF

Linear

ON

Square root

Filter response time

The filter response time of the sensor, additional to the built-in response time of 10 milliseconds (approximately), can be set using the three switches next to the terminal connector. Using combinations of the switches can set different times.

Switch

Filter response time

 

A

200 milliseconds

Example:

B

400 milliseconds

Switch A+B = 600 milliseconds

C

1 second

 

 

 

 

Note: A hollow point is visible when a switch is in the 'on' position.

Image 4