Specifications
Sentry Model
Power Supply
Nominal operating voltages: 120V units
Permissible voltage variation: ± 6% of nominal
Nominal operation frequency:
DC Charge Output
Maximum current ADC: 5
Nominal voltage VDC: 12
Guardian Model
Power Supply
Nominal operating voltages: 120VAC ± 6%
Permissible voltage variation: 120VAC ± 6%
Nominal operation frequency:
DC Charge Output
Maximum current ADC: 20/20
Nominal voltage VDC: 24/12
Float/Boost Voltages
Battery Type | Float Volts (VDC) | Boost Volts (VDC) |
12V Lead Acid (6 cells) | 13.6 | 14.1 |
Charge Fail Output
| Relay type: volt free SPDT contacts; relay |
Float/Boost Voltages
Battery Type
12V Lead Acid (6 cells)
24V Lead Acid (12 cells)
Charge Fail Output
Float Volts (VDC) Boost Volts (VDC)
13.614.1
27.228.2
Contact rating: 1A at 30V, DC (resistive load) |
General
Operating temperature: +14 to +131°F
EMC emission/immunity: EN
Model Info
Relay type: volt free SPDT contacts; relay
Contact rating: 1A at 30V, DC (resistive load)
| Normal Output VDC | ||
| 12 |
| 24 |
Under Volts Alarm | 12.5 |
| 25 |
Over Volts Alarm | 15.5 |
| 31 |
Delay on under volts |
| 120 | seconds |
General
Operating temperature: +14 to +131°F
EMC emission/immunity: EN
Mounting hole dimensions:
Width (between holes): 6.8” (173mm)
Height (between holes): 10” (255mm)
Mounting holes ∅=0.2” (6mm)
Model Info
Warranty - A limited warranty on materials and workmanship is given with this FW Murphy product. A copy of the warranty may be viewed or printed by going to www.fwmurphy.com/support/warranty.htm