Emerson TCDVTM manual Electrical data-50 and 60 Hz, VFD condensers for indoor units, 50 and 60Hz

Page 6

 

Introduction

Figure 2 Major electrical control components

 

 

Liebert’s

Variable

Transient

Voltage

Frequency

Surge

Drive control

Suppression

Locking

Disconnect

Table 1

Electrical data—50 and 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model #

 

 

165, 205

 

 

251, 308

 

 

415, 510

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of Fans

 

 

2

 

 

3

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage

Ph

Hz

 

Motor Hp

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

 

 

60

 

 

7.2

8.1

15

10.7

11.6

15

14.2

15.1

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

 

3

 

0.75

3.5

4.0

15

5.2

5.7

15

6.9

7.4

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200/230

 

50

 

7.2

*

*

10.7

*

*

14.2

*

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380/415

 

 

 

 

3.5

*

*

5.2

*

*

6.9

*

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA = Full Load Amps; WSA = Wire Size Amp; OPD = Maximum Overcurrent Protection Device Rating

 

 

 

* = Follow local electrical code to determine WSA and OPD

 

 

 

 

 

 

 

Table 2

VFD condensers for indoor units, 50 and 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R-22

 

 

 

R-407C

 

 

 

 

 

 

 

 

 

 

 

Outdoor Design Ambient Temperature

 

Indoor Unit

 

 

 

 

 

 

 

95°F (35°C)

100°F (38°C)

105°F (41°C)

 

95°F (35°C)

100°F (38°C)

105°F (41°C)

 

 

 

 

 

 

 

 

 

DH/VH75A

 

N/A

N/A

TCDV165

 

N/A

N/A

N/A

 

 

 

 

 

 

 

 

DH/VH114A

TCDV165

TCDV165

TCDV205

 

N/A

N/A

N/A

 

 

 

 

 

 

 

 

DH/VH125A

TCDV165

TCDV165

TCDV205

 

N/A

N/A

N/A

 

 

 

 

 

 

 

 

DH/VH199A

TCDV205

TCDV308

TCDV308

 

N/A

N/A

N/A

 

 

 

 

 

 

 

 

DH/VH245A

TCDV308

TCDV308

TCDV415

 

N/A

N/A

N/A

 

 

 

 

 

 

 

 

DH/VH290A

TCDV308

TCDV415

TCDV415

 

N/A

N/A

N/A

 

 

 

 

 

 

 

 

DH/VH380A

TCDV415

TCDV510

N/A

 

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

DS/VS028A

 

TCDV165

TCDV165

TCDV205

 

TCDV205

TCDV205

TCDV251

 

 

 

 

 

 

 

 

 

DS/VS035A

 

TCDV165

TCDV205

TCDV205

 

TCDV205

TCDV205

TCDV251

 

 

 

 

 

 

 

 

 

DS/VS042A

 

TCDV205

TCDV205

TCDV308

 

TCDV205

TCDV251

TCDV308

 

 

 

 

 

 

 

 

 

DS/VS053A

 

TCDV205

TCDV308

TCDV308

 

TCDV251

TCDV308

TCDV415

 

 

 

 

 

 

 

 

 

DS/VS070A

 

TCDV308

TCDV415

TCDV415

 

TCDV308

TCDV415

TCDV415

 

 

 

 

 

 

 

 

 

DS/VS077A

 

TCDV308

TCDV415

TCDV510

 

TCDV308

TCDV415

TCDV510

 

 

 

 

 

 

 

 

 

DS/VS105A

 

TCDV415

TCDV510

N/A

 

TCDV415

N/A

N/A

 

 

 

 

 

 

 

 

 

2

Image 6
Contents Liebert VFD Condenser Model Tcdv Page Figures Page Description Locking Disconnect Electrical data-50 and 60 HzVFD condensers for indoor units, 50 and 60Hz Model #Sound Number 16.7C 13.9C 11.1CDBA Qty Condenser performance, 50Hz Sound Fan Number 16.7C 13.9C 11.1CDBA Qty Refrigerant Physical data-VFD control condensers, 50 and 60Hz Number Net Weight Model # Fans Lb kgUnit Anchor Plan Typical FootprintElectrical field connections, VFD control condensers General Ti n Ne tIti That