7 Programming
I.THE 3 CONFIGURATIONS
A.Configuration A: Single Loop Detector
B.Configuration B: Dual Loop Detector in Independent Mode with Dipswitch #10 OFF
C.Configuration C: Dual Loop Detector in Combined Mode with Dipswitch #10 ON
Dip Switch | Configuration A | Configuration B | Configuration C | ||||
| Single loop | Dual loop in independent mode | Dual loop in combined mode | ||||
| OFF |
| ON | OFF | ON | OFF | ON |
DS#1 | See next table | High (loop A) | Low (loop A) | High (loop A) | Low (loop A) | ||
|
|
|
|
| [High |
| [High |
DS#2 |
|
|
| High (loop B) | Low (loop B) | High (loop B) | Low (loop B) |
|
|
|
|
| [High |
| [High |
DS#3 | Active mode |
| Passive mode | Active mode | Passive mode | Active mode | Passive mode |
DS#4 | ASB OFF |
| ASB ON | ASB OFF | ASB ON | ASB OFF | ASB ON |
DS#5 | Relay A : |
| Relay A : | Relay A : | Relay A : | Not used | Not used |
| Presence on |
| Pulse on loop | Presence on loop A | Pulse on loop A |
|
|
| loop A |
|
|
|
|
|
|
DS#6 | Relay A : |
| Relay A : | Relay A : | Relay A : | Relay B : | Relay B: |
| Pulse on loop |
| Pulse on loop A | Pulse on loop A | Pulse on loop A | Directional A→B | |
| A |
| exit | entry | Exit | mode | mode |
| entry |
|
|
|
|
|
|
DS#7 | Relay B : |
| Relay B : | Relay B : | Relay B : | Relay B : | Relay B : |
| Presence on |
| Pulse on loop A | Presence on loop B | Pulse on loop B | Pulse on loop B | Pulse on loop A |
| loop A |
|
|
|
|
|
|
DS#8 | Relay B : |
| Relay B : | Relay B : | Relay B : | Relay B : | Relay B : |
| Pulse on loop |
| Pulse on loop A | Pulse on loop B | Pulse on loop B | Pulse on loop entry | Pulse on loop exit |
| A |
| exit | entry | exit |
|
|
| entry |
|
|
|
|
|
|
DS#9 | 100 ms |
| 500 ms | 100 ms | 500 ms | 100 ms | 500 ms |
DS#10 | Not used |
| Not used | Independent | Combined mode | Independent | Combined mode |
II. POTENTIOMETERS
A Potentiometer for Adjustment of the Maximum Duration of a Presence Detection: from 1 min to Infinity (See PRESENCE TIME)
A Potentiometer for Adjustment of the Linear Sensitivity (Δf) for the Loop A: from 0.005% to 0.5% (See SENSITIVITY)
A Potentiometer for Adjustment of the Linear Sensitivity (Δf) for the Loop B: from 0.005% to 0.5% (See SENSITIVITY)
PRESENCE TIME
1 min 10 min1 hr
MIN
2 hr
MAX
Infinity 20 hr 5 hr
SENSITIVITY
0.5% 0.44%0.34% MIN
0.25%
MAX
0.005% 0.1% 0.18%
III. RELAY CONFIGURATION (DIPSWITCH #3)
A 10 position dip switch is located on the front of the Matrix single detector. Dip switch 3, 5, 6, 7 and 8 configure the relay, while dip switch 9 controls the duration of the pulse when the Matrix is configured for pulse operation, (as opposed to presence). Configurations are as follows:
DIPSWITCH 3:
OFF=
ON =
| DETECTION STATUS |
|
| ||
|
|
| (Relay is not energized upon | ||
|
|
|
|
| DIPSWITCH 3 = OFF |
| NO DETECTION |
| The COM and NO terminals are OPEN. | ||
| COM and NC terminals are CLOSED. | ||||
|
|
|
| The relay is | |
| DETECTION |
|
| The COM and NO terminals are CLOSED. | |
|
| COM and NC terminals are OPEN. | |||
| Same | ||||
|
| The relay is energized. | |||
|
|
|
|
| The COM and NO terminals are OPEN. |
| UPON POWER LOSS |
| |||
| COM and NC terminals are CLOSED | ||||
|
|
|
| The relay is |
(Relay becomes energized upon
DIPSWITCH 3 = ON
The COM and NO terminals are CLOSED. COM and NC terminals are OPEN.
The relay is energized.
The COM and NO terminals are OPEN. COM and NC terminals are CLOSED. The relay is
The COM and NO terminals are OPEN. Same COM and NC terminals are CLOSED.
The relay is
75.1046.04 EN 20080505 | Page 3 of 5 |