Sierra Monitor Corporation PF5M instruction manual DIN rail mounting using ZS-33-R, Piping

Page 8

Mounting and Installation (continued)

DIN rail mounting (using ZS-33-R)

•The tightening toque for DIN rail mounting screws and joint screws should be 0.4 0.05N·m.

Through hole

Bracket

Joint screw

DIN rail mounting bracket

DIN rail mounting screw

Note) Not applicable if the thread type is F02.

Piping

•Keep the tightening torque when piping for the female thread. •Refer to the following table for the appropriate torque values.

Nominal size of

Appropriate torque

screws

N·m

Rc1/8

7 to 9

 

 

Rc1/4

12 to 14

 

 

•Hold the metal part with the spanner when piping.

•For one-touch fitting, insert the tube to the end so that

it is not pulled off. •Insertion with excess force

lead to cause breakage. •Ensure no leakage after piping.

•Use this flow sensor within the specified

operating pressure range and operating temperature range. •Withstand pressure are 1.0MPa.

12

13

Image 8
Contents Digital Flow Sensor PFM5 Series Contents Safety Instructions Important MessagesPrecaution on Handling Power source display green Turns on when power is supplied Names and Functions of Individual PartsPFM Model Indication MethodBracket mounting Mounting and InstallationHow to mount Panel Mount mounting DIN rail mounting using ZS-33-R PipingWiring Connection Output circuitError Indication Error indication function