START HERE
Using This Quick Start Manual
Use this Quick Start Manual to get your High Performance Process Indicator up and running. These instructions use the factory default settings of current input and 24 Vdc sensor excitation. To start your unit you:
• | connect ac power |
• | wire the sensor |
2
Wiring a Current Transmitter
Follow these steps to wire a current input sensor with sensor excitation.
1.Locate connectors P3 & P9 on the
2.Attach the wires and tighten the retaining screws. Tug gently on the wires to verify the connection.
Wiring Example: Current Input with Sensor Excitation
3
Quick Start Setup
Quick Start Setup scales your meter to read 0 to 100.0 for a 4 - 20mA input. This setup procedure is actually a series of short tasks. To complete Quick Start Setup successfully, it is important to perform all tasks in the order outlined in the Quick Start Setup.
4
Set Reading Scale Factor and Reading Offset
1. Press /MIN to display the scale factor | 1.00000 |
value. Change the value, if necessary, |
|
to read “1.00000” (Use /MIN to scroll |
|
through digits and /MAX to change | SETPTS /MAX /MIN MENU RESET |
| |
the digit’s value). |
|
• configure the meter, using the front panel buttons and the |
configuration menus |
Before You Begin
(+)+E
|
| 1 |
+S | P9 | |
| 2 | |
|
|
Select Input Range
1. Press MENU until the meter displays: |
INPUT
2.Press MENU. The meter stores changes (if applicable) then displays “RDG.OF”:
Check the serial label on the top of the meter case. The model number’s last 3 digits indicate if the meter is set up for voltage or current. C1 - C2 are current ranges and DC1 - DC10 are voltage ranges. This quick start manual uses the C2 (4 - 20mA) range. If your meter is setup for a range other than C2, consult the reference manual.
Your unit should have the following parts:
•Meter
•Front panel button cover
3 | ||
N/C |
| |
| 1 | |
JUMPER |
| |
N/C | P3 | |
USER |
| 2 |
PROVIDED | RTN | 3 |
|
|
3. Apply ac power. The front panel of the unit flashes RESET2. |
If it does not: |
a. Remove ac power. |
b. Verify the P1 power and P3 and P9 input connections. |
c. Check your power source. |
2. Press /MIN until the meter flashes: |
Press MENU and “CURRNT” stops |
flashing. |
Press /MIN to display a flashing |
input range of |
Press /MAX until the meter displays |
SETPTS /MAX /MIN MENU RESET
CURRNT
SETPTS /MAX /MIN MENU RESET
stored
SETPTS /MAX /MIN MENU RESET
3.Press /MIN to display the offset value. Change the value, if necessary, to read “000000” (Use /MIN to scroll through digits and /MAX to change the digit’s value).
rdg.of
SETPTS /MAX /MIN MENU RESET
000000
SETPTS /MAX /MIN MENU RESET
GASKET
•Panel mounting gaskets
•ac Power Connector (orange
| d. Check your signal source. |
4. | Replace the rear cover. Thread the sensor wires through |
| the slots on the side of the cover. Replace the rear cover |
| screw. |
5. | Apply ac power once again. |
3.Press MENU. The meter stores changes (if applicable), then displays “RDG.CNF”:
stored | rdg.CNF |
4.Press MENU. The meter stores change, if applicable, then displays “IN CNF”.
Contact the nearest Customer Service Department using the numbers listed on the front of this quickstart manual if any of these parts are missing, or if you have questions . In addition to the unit and related parts, you will need the following items to set up your unit:
Configure the Meter
Use the front panel buttons to access the configuration menus, to either verify or set the unit values. The function of each button is described below:
SETPTS /MAX | /MIN | MENU | RESET | SETPTS | /MAX | /MIN | MENU | RESET |
|
|
|
|
Set Up Reading Configuration
stored
SETPTS /MAX /MIN MENU RESET
CNTBY
SETPTS /MAX /MIN MENU RESET
•ac power, as listed on meter’s Product/ID
•
•1/8” Phillips head screwdriver
•1/8” flat blade screwdriver
Connect ac Power
1. | Remove the rear protective cover and set it aside. |
| The cover is secured with a |
2. | Locate connector P1 on the |
| The connector has three |
3. | Insert the correct wire in each terminal and tighten the |
| lockdown screw. Tug gently on each wire to verify the |
Meter Button Descriptions
Press This Button To:
| sequentailly recall previous setpoint |
| settings (run mode only), store new |
SETPTS | setpoint values. |
| |
|
|
| access the configuration program |
| menus and move from one menu |
MENU | to the next. |
|
|
| enter and scroll through a submenu. |
1.Press /MIN to display “RDG.1”. Press /MAX until the meter displays “RDG.1=0”. Selecting “RDG.1=0” enables direct formatting.
2.Press /MIN to display “RDG.2”. Press /MAX until the meter displays “RDG.2=1”. Selecting “RDG.2=1” enables an active decimal point.
RDG.1=0
SETPTS /MAX /MIN MENU RESET
RDG.2=1
SETPTS /MAX /MIN MENU RESET
Set Default Input Scale and Offset
1.Press /MIN until the meter flashes. Change the value, if necessary, to read “INP.6=0” (Use /MIN to scroll through INP submenu choices and /MAX to select 0 as the value). Setting “INP.6=0” disables input scale and offset.
INp.6=0
SETPTS /MAX /MIN MENU RESET
connection. |
/MIN |
2.Press MENU. The meter stores changes, if applicable, then displays “IN.SC.OF”.
~AC Line |
| P1 |
~AC Neutral | 1 | L |
EARTH GROUND | 2 | N |
3 |
| |
|
| |
| P1 Connector |
| change the value of a submenu. |
/MAX |
|
| move backward one menu (press |
| once) or exit the configuration |
RESET | menus (press twice). |
3.Press MENU. The meter stores changes (if applicable), then displays “RDG SC”:
stored | rdg sc |
SETPTS /MAX /MIN MENU RESET | SETPTS /MAX /MIN MENU RESET |
|
stored | IN.SC.OF |
SETPTS /MAX /MIN MENU RESET | SETPTS /MAX /MIN MENU RESET |