INSTALLATION INSTRUCTIONS for | Form 7514 rev. 0 |
HeatManager™ 2.5 model 7514 |
|
LIGHT COMMERCIAL HYDRONIC HEATING SYSTEM ECONOMIZER |
|
|
|
Description
The HeatManager™2.5 is a patented microprocessor- controlled
Operation
After installation, setting the toggle switch on the unit to the ‘ON’ position activates the device. The LCD display indicates the various ‘modes’ of the device, and sensed temperatures. The possible messages and their explanation are:
‘STANDBY MODE’ - The boiler is operating under its own internal aquastat, which has turned the burner off. This occurs for a period of time after the burner has shut down.
‘ECONOMIZER MODE’ - The boiler aquastat has requested the burner to come on but the HeatManager™ has sensed that there is available heat which can be used without burning fuel. The burner will remain off and useful heat will be delivered from the boiler’s existing supply of hot water.
‘HEATING MODE’ – The burner is allowed to fire.
‘HEATING LOW LIMIT’ - The unit has switched the burner on due to an increase in load. This condition may occur occasionally. If this message appears frequently, the boiler aquastat is set at too low a temperature. It should be increased in 2º F increments until the condition stops.
During normal operation, one of the above messages will be alternated with the message(s) below.
‘HEAT TEMP = ‘ - The measured value of the boiler outflow water temperature is displayed in degrees F.
‘DOM. TEMP = ‘ - The measured value of the domestic hot water outflow temperature is displayed in degrees F. *
*Note: This message will only appear if the boiler supplies domestic hot water and the optional second sensor is installed (see Sensor Section of these instructions).
In the event that a sensor fails, the HEATMANAGER™ will return full control of the burner to the boiler aquastat, the ‘Power/Normal’ indicator will blink, and the following message will be display:
‘SENSOR FAILURE ‘
If this message appears, see the instructions under Service and Troubleshooting or call your installer for service.
Installation
The HEATMANAGER™ unit is electrically installed in series with the boiler aquastat as shown in the wiring diagram (Fig. 1a or Fig.1b on the reverse side of this page). Check the shipping box label for correct model. The HEATMANAGER™ can be used with 24, 115 and 220 Volts AC (see Fig. 1a or Fig. 1b for wiring details) for power and control.
For safety, power to the boiler should be shut off during installation.
To ensure maximum savings, it is recommended that the Aquastat be set to a minimum of 170˚F.
Positioning
The unit can be mounted in any position. For readability of the display, the vertical position is preferred. Depending on the boiler’s configuration, the unit can be mounted on an electric junction box or directly on an external aquastat. Remove a knockout from the junction box or aquastat and mount the unit using the standard ½’ electrical fitting on the case, and the supplied
Wiring
All wiring and connections must comply with Local and National Electrical Codes. The unit should be wired as shown in the wiring diagram (Fig. 1a or Fig. 1b) on the reverse side.
NOTE: All unused leads should be trimmed and individually taped.
Sensors
Insert the sensor connector into the ‘Heating Water Sensor’ jack in the side of the unit. Attach the sensor to the boiler outflow pipe using
For boilers which also supply domestic hot water, install a second sensor in the ‘Domestic Water Sensor’ jack and attach the sensor end to the domestic hot water
If any of the sensor leads are too short, they can be extended by using standard ‘modular telephone’ wire and connectors (see Fig. 4).
Checkout
Recheck wiring one last time and make sure that the temperature sensor(s) is plugged into the proper jack(s). The sensor(s) are only detected during
Service and Troubleshooting
After installation, the HeatManager™ requires no maintenance and will provide years of trouble free operation. The unit may be disconnected at any time by putting the switch to the ‘OFF/BYPASS’ position. In this position, the unit has no effect on the system and the boiler functions as it was prior to the IntelliCon installation. This allows service personnel to diagnose any boiler problems without the unit intervening.
If at any time the ‘SENSOR FAILURE’ message appears on the front panel display, a sensor is not operating and the unit automatically returns full control to the Boiler’s aquastat. To correct this, leave the power switch in the ‘ON’ position and unplug each sensor from the unit (one at a time) and reconnect them. If the error message remains, a sensor is defective and must be replaced. Since it is improbable for two sensors to fail at the same time, a new sensor should be swapped with the existing sensor(s), one at a time, to determine which sensor has failed.
Here again, the power switch must be left in the ‘ON’ position while changing the sensors.
NOTE: Installer, please leave these instructions with the unit for future reference.
R.W. Beckett Corporation, Elyria, Ohio USA