3-7. Electrical Service Guide
Input Voltage | 230 V − 60 Hz | |
220 V − 50 Hz | ||
| ||
|
| |
Input Amperes At Rated Output | 47.5 | |
|
| |
Max Recommended Standard Fuse Rating In Amperes |
| |
Circuit Breaker 1, | 50 | |
Normal Operating 3 | 70 | |
Min Input Conductor Size In AWG 4 | 12 | |
Max Recommended Input Conductor Length In Feet (Meters) | 87 (27) | |
|
| |
Min Grounding Conductor Size In AWG 4 | 12 |
Reference: 2005 National Electrical Code (NEC) (including article 630)
1Choose a circuit breaker with
2
3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).
4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
3-8. Connecting Input Power
1 | Y | Disconnect and lockout/tag- |
| out input power before instal- | |
|
| ling receptacle. |
| Y Have only qualified persons | |
| =GND/PE Earth Ground | make this installation. See |
| rating label in Section | |
|
| |
|
| be sure to supply correct in- |
|
| put power. |
| 1 | Proper Receptacle |
|
| (NEMA |
|
| |
| Receptacle must comply with appli- | |
| cable codes. | |
| 2 | Input And Grounding |
| 3 | Conductors | |
| See size and length using Section | ||
| |||
| applicable codes. | ||
| 3 | ||
| Select type and size of | ||
| protection using Section | ||
2 | 4 | Plug (NEMA | |
Connect plug to properly installed | |||
|
1
4
receptacle.
Close and secure door on discon- nect device. Remove lockout/tagout device, and place switch in the On position.
Ref. 802