Carrier SYSTXCC4ZC01 Additional Damper Control Board Setup, Transformer Requirements

Page 5

NOT required for regular use. Traditionally, the LAT/HPT sensors were required for temperature / equipment monitoring. The Infin- ity Zoning System does not require these because the User Interface algorithms will perform temperature and airflow man- agement without use of these sensors. If desired, one or both sensors may be used in monitoring leaving air temperature and / or indoor coil air temperature. Consideration and / or flexibility will now permit using one of these sensors in the return air duct giving the dealer an option to view both entering and leaving air temperature at the User Interface. If applied, connect sensors to the LAT / HPT terminals (See Fig. 9, System Wiring, for connection to Infinity Damper Control). LAT is monitored by both AC and HP systems. LAT and HPT are both monitored only in HP systems.

To install - Locate LAT sensor in main supply trunk after heating and cooling coil and before first branch. The LAT sensor is radiant shielded to prevent heat from affecting correct air temperature.

1.Drill a 1/4 inch hole at location in supply trunk where sensor will be installed.

2.Insert sensor in hole and use as a template to mark the 2 mounting holes.

3.Drill two 1/16 inch holes to accept No. 6 screws through pre-drilled holes in duct temperature sensor back plate.

4.Use two No. 6 sheet metal screws to mount duct temperature sensor to unit.

5.Connect sensor to 2-conductor wire using provided wire nuts.

The HPT sensor (in heat pump applications) measures the tem- perature of the air leaving the indoor coil. The sensor is installed downstream of the indoor coil but before the electric heaters. It can be installed through the wall of the fan coil or may be located entirely inside the fan coil near the blower inlet. Anchor firmly in place with cable ties so that it cannot interfere with the blower wheel (See Fig. 9).

LED INDICATORS — Under normal operation, the Yellow and Green LEDs will be on continuously (solid). If the Infinity Damper Control does not receive communications with the User Interface, the Green LED will not be on. If there are faults present, the Yellow LED indicator will blink a two-digit status code. The first digit will blink at a fast rate, the second at a slow rate.

STATUS CODE

DESCRIPTION

16 =

Communication Failure

24 =

Damper Fuse Failed

45 =

Board Failure

46 =

Low Input Voltage

FUSE — A 1-amp automotive type fuse is used to protect the Infinity Damper Control from over current on the damper drive outputs. If this fuse fails, damper wiring should be inspected for shorts. Also, no more than five damper motors should be con- nected to a single damper output. Fuse should always be replaced with an identical 3 amp automotive fuse.

Step 6—ADDITIONAL DAMPER CONTROL BOARD SETUP

If you have more than four zones, a second Infinity Damper Control must be used and both dip switch settings on the second board supporting zones 5 through 8 must be moved to the right. The ABCD bus connector must be wired between both Infinity Damper Controls.

Step 7—Transformer Requirements

The Infinity Zoning System has a lower power draw from the system transformer than previous controls. It also drives only 2 zone damper outputs at a time. As a result, up to 8 zones each with up to 5 dampers, plus a smart sensor, can be handled without increasing the size of the system transformer or adding a second zoning transformer.

Use of the transformer provided in the furnace or fan coil is recommended without change in all zoning applications except those having a System Access Module (SAM). The SAM requires a separate transformer.

For those who still want more transformer capacity, a 60 VA system transformer may be used in place of the supplied 40 VA part.

Step 8—System Start-Up

Follow the system start-up process outlined in the Infinity Zone Control Installation Instructions for details.

5

Image 5
Contents Safety Considerations Table of ContentsInstallation Considerations IntroductionComponent Location and Wiring Consider- ations InstallationCheck Equipment and Job Site Locating Infinity Damper ControlInstall Zone Dampers Install ComponentsDamper 24-vac Connections Final WiringSystem Start-Up Additional Damper Control Board SetupTransformer Requirements Zoning System Wiring Diagram Zones 5 Troubleshooting Book Tab

SYSTXCC4ZC01 specifications

The Carrier SYSTXCC4ZC01 is an advanced thermostat designed to enhance the comfort and efficiency of residential heating and cooling systems. This device offers a blend of cutting-edge technology and user-friendly features, making it an ideal choice for homeowners looking to optimize their indoor climate.

One of the standout features of the SYSTXCC4ZC01 is its Wi-Fi connectivity. This allows users to control their HVAC systems remotely through a smartphone app, providing convenience and flexibility. Whether you’re at home, work, or on vacation, you can adjust the temperature, set schedules, and monitor energy consumption in real-time from virtually anywhere. This remote access not only enhances comfort but also supports energy savings by allowing homeowners to manage their heating and cooling efficiently.

The thermostat also boasts a sleek, modern design with a colorful touchscreen display. The intuitive interface makes it easy to navigate and customize settings. Furthermore, the SYSTXCC4ZC01 is equipped with advanced diagnostics capabilities. This feature not only helps in troubleshooting any potential issues but also assists homeowners in maintaining their systems more effectively, promoting longevity and reducing maintenance costs.

In terms of technology, the Carrier SYSTXCC4ZC01 is compatible with various heating and cooling systems, including single-stage and multi-stage setups. It supports heat pumps, gas furnaces, and air conditioning systems, offering versatility to meet different homeowner needs. The thermostat’s ability to handle multiple zones also allows for precise temperature control in larger homes, ensuring that each room maintains its desired level of comfort.

Energy efficiency is a core focus of the SYSTXCC4ZC01. The thermostat is designed to work in conjunction with Carrier’s Infinity system, integrating seamlessly to optimize performance and reduce energy costs. By using advanced algorithms, the thermostat learns the homeowner's preferences and schedules to minimize energy use without sacrificing comfort.

Additionally, the SYSTXCC4ZC01 includes smart alerts that notify users of filter changes, system maintenance, and extreme temperature fluctuations. This proactive feature empowers homeowners to make informed decisions about their HVAC systems, leading to increased efficiency and cost savings over time.

In summary, the Carrier SYSTXCC4ZC01 thermostat is a comprehensive solution for modern home climate control. With its Wi-Fi connectivity, intuitive interface, advanced diagnostics, compatibility with various systems, and focus on energy efficiency, it stands out as a leader in home comfort technology.