Carrier 40GXC, 40GXQ, 38GXQ, 38GXC System Vacuum and Charge, Using Vacuum Pump

Page 9

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. Always break a vacuum with dry nitrogen.

SYSTEM VACUUM AND CHARGE

Using Vacuum Pump

1.Completely tighten flare nuts A, B, C, D, connect manifold gage charge hose to a charge port of the low side service valve. (See Fig. 15.)

2.Connect charge hose to vacuum pump.

3.Fully open the low side of manifold gage. (See Fig. 16)

4.Start vacuum pump

5.Evacuate using either deep vacuum or triple evacuation method.

6.After evacuation is complete, fully close the low side of manifold gage and stop operation of vacuum pump.

7.The factory charge contained in the outdoor unit is good for up to 25 ft. (8 m) of line length. For refrigerant lines longer than 25 ft (8 m), add 0.1 oz. per foot of extra piping up to the maximum allowable length.

8.Disconnect charge hose from charge connection of the low side service valve.

9.Fully open service valves B and A.

10.Securely tighten caps of service valves.

Outdoor Unit

Refrigerant

Indoor Unit

Low Side

 

 

C

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

High Side

 

 

 

 

 

Service Valve

 

 

 

 

 

 

 

 

 

 

 

 

A07360

Fig. 15 ---Service Valve

Manifold Gage

500 microns

 

Low side valve

High side valve

Charge hose

Charge hose

 

Vacuum pump

Low side valve

A07361

Fig. 16 ---Manifold

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 17)

5000

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

4000

 

 

 

 

 

LEAK IN

3500

 

 

 

 

 

 

 

 

 

 

SYSTEM

3000

 

 

 

 

 

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

MICRONS2000

 

 

 

 

 

VACUUM TIGHT

1500

 

 

 

 

 

 

 

 

 

 

TOO WET

1000

 

 

 

 

 

 

 

 

 

 

TIGHT

500

 

 

 

 

 

 

 

 

 

 

DRY SYSTEM

 

 

 

 

 

 

0

1

2

3

4

5

6

7

 

 

 

MINUTES

 

 

 

 

 

 

 

 

 

 

A95424

Fig. 17 ---Deep Vacuum Graph

Triple Evacuation Method

The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water.

Refer to Fig. 18 and proceed as follows:

1.Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.

2.Close service valves and shut off vacuum pump.

3.Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.

4.Close service valve and allow system to stand for 1 hr. Dur- ing this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture.

5.Repeat this procedure as indicated in Fig. 18. System will then be free of any contaminants and water vapor.

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

CHECK FOR TIGHT, DRY SYSTEM (IF IT HOLDS DEEP VACUUM)

RELEASE CHARGE INTO SYSTEM

A95425

Fig. 18 ---Triple Evacuation Method

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.

38/40GXC(Q)

9

Image 9
Contents Table of Contents Installation Instructions38GXCQ / 40GXCQ 009, 012, 018 and 024 Parts List Parts ListConnecting Power and Control Cable Safety ConsiderationsGeneral System RequirementsDimensions Outdoor Dimensions IndoorClearances Outdoor Clearances IndoorInstallation Guide Indoor Unit InstallationInstall Mounting Plate If piping is going through the right or left side Outdoor Unit InstallationField Wiring System Vacuum and Charge Using Vacuum PumpSystem Checks START-UPIndoor Unit Outdoor Unit38GXC/GXQ 40GXC/GXQ 009-024 Diagnostic Codes TroubleshootingCatalog No 40GX---4SI

38GXC, 38GXQ, 40GXC, 40GXQ specifications

Carrier's 40GXQ, 38GXQ, 38GXC, and 40GXC series are a testament to the brand’s commitment to innovation and excellence in HVAC technology. These units are designed to meet the diverse needs of commercial and residential applications while ensuring optimal performance, energy efficiency, and sustainability.

The 40GXQ model stands out for its advanced cooling capabilities and high efficiency. This rooftop unit employs a high-efficiency scroll compressor that enhances performance while minimizing energy consumption. With a cooling capacity ranging from 3 to 20 tons, the 40GXQ is ideal for larger spaces requiring significant cooling load management. It also features a user-friendly interface, allowing for easy adjustments and monitoring through a digital display.

The 38GXQ is particularly notable for its versatility and robust design. Featuring an integrated economizer, the 38GXQ allows for enhanced energy savings by leveraging outdoor air for free cooling when conditions permit. This model is equipped with high-efficiency filters that improve indoor air quality, making it suitable for applications in schools, offices, and healthcare facilities.

The 38GXC variant is designed for residential applications and emphasizes whisper-quiet operation without compromising performance. Its high SEER (Seasonal Energy Efficiency Ratio) rating means homeowners can enjoy substantial savings on their energy bills. The 38GXC is also equipped with Carrier's Greenspeed intelligence, which enables the system to modulate its output, maintaining comfort levels while reducing energy consumption.

The 40GXC model represents innovation in temperature control systems. With its sleek design and advanced variable-speed compressor, the 40GXC can adapt to changing conditions while maintaining efficiency and performance. This model also incorporates advanced monitoring systems that provide real-time data on performance and diagnostics, ensuring optimum efficiency throughout its lifecycle.

All these Carrier models are equipped with advanced refrigerant management systems, supporting environmentally friendly refrigerants that adhere to current environmental regulations. They not only provide effective cooling solutions but also contribute to a sustainable future, aligning with Carrier’s broader commitment to reducing carbon footprints.

In summary, the Carrier 40GXQ, 38GXQ, 38GXC, and 40GXC are engineered to deliver exceptional performance, energy efficiency, and versatility across various applications. With advanced technologies and a commitment to sustainability, these units set a high standard in the HVAC industry. Whether for commercial or residential use, these models provide reliable and efficient climate control solutions.