Carrier 39LH03-25, 39LB Water and Steam Coil Piping Recommendations, Coil Freeze-Up Protection

Page 14

Water and Steam Coil Piping Recommendations

GENERAL — Use straps around the coil casing or the lifting holes (see Fig. 17) to lift and place the coil.

To prevent damage to the coil or coil headers: Do not use the headers to lift the coil. Support the piping and coil con- nections independently. Do not use the coil connections to support piping. When tightening coil connections, use a backup wrench on the nozzles.

Piping practices are outlined in the Carrier System Design Manual, Part 3, Piping Design. See Tables 4-6 for circuiting data.

WATER COILS — Typically, coils are piped by connecting the supply at the bottom and the return at the top. See Fig. 17. This is not always the case, especially if the coil hand has been changed in the field. Coils must be piped for counterflow; oth- erwise, a capacity reduction of 5% for each coil row will result. To ensure counterflow, chilled water coils are piped so that the coldest water meets the coldest air. Hot water coils are piped so that the warmest water meets the warmest air.

STEAM COILS — Position the steam supply connection at the top of the coil, and the return (condensate) connection at the bottom. The coil tubes must incline downwards toward the return header connection for condensate drainage. See Fig. 18-22.

Figure 18 illustrates the normal piping components and the suggested locations for high, medium, or low-pressure steam coils. The low-pressure application (zero to 15 psig) can dispense with the ¼-in. petcock for continuous venting located above the vacuum breaker (check valve).

Fig. 17 — Coil Connections and Lifting Points

Note the horizontal location of the 15-degree check valve, and the orientation of the gate/pivot. This valve is intended to relieve any vacuum forming in the condensate outlet of a condensing steam coil, and to seal this port when steam pressure is again supplied to the coil. It must not be installed in any other position, and should not be used in the supply line.

For coils used in tempering service, or to preheat outside air, install an immersion thermostat in the condensate line ahead of the trap. This will shut down the supply fan and close the out- door damper whenever the condensate falls to a predetermined point, perhaps 120 F.

NOTE: Do NOT use an immersion thermostat to override a duct thermostat and open the steam supply valve.

For vacuum return systems, the vacuum breaking check valve would be piped into the condensate line between the trap and the gate valve instead of open to the atmosphere.

Figure 19 illustrates the typical piping at the end of every steam supply main. Omitting this causes many field problems and failed coils.

Figure 20 shows the typical field piping of multiple coils. Use this only if the coils are the same size and have the same pressure drop. If this is not the case, an individual trap must be provided for each coil.

Figure 21 shows a multiple coil arrangement applied to a gravity return, including the open air relief to the atmosphere, which DOES NOT replace the vacuum breakers.

Figure 22 illustrates the basic condensate lift piping.

Following the piping diagrams in Fig. 18-22, make all con- nections while observing the following precautions:

Install a drip line and trap on the pressure side of the inlet control valve. Connect the drip line to the return line downstream of the return line trap.

To prevent scale or foreign matter from entering the con- trol valve and coil, install a 3/32-in. mesh strainer in the steam supply line upstream from the control valve.

Provide air vents for the coils to eliminate noncondens- able gases.

Select a control valve according to the steam load, not the coils supply connection size. Do not use an oversized control valve.

Do not use bushings that reduce the size of the header return connection. The return connection should be the same size as the return line and reduced only at the downstream trap.

To lift condensate above the coil return line into over- head steam mains, or pressurized mains, install a pump and receiver between the condensate trap and the pressurized main. Do not try to lift condensate with modulating or on-and-off steam control valves. Use only 15-degree check valves, as they open with a lower water head. Do not use 45-degree or vertical-lift check valves.

Use float and thermostatic traps. Select the trap size according to the pressure difference between the steam supply main and the return main.

Load variations can be caused by uneven inlet air distri- bution or temperature stratification.

Drain condensate out of coils completely at the end of the heating season to prevent the formation of acid.

Coil Freeze-Up Protection

WATER COILS — If a chilled water coil is applied with out- side air, provisions must be made to prevent coil freeze-up. Install a coil freeze-up thermostat to shut down the system if any air temperature below 36 F is encountered entering the water coil. Follow thermostat manufacturer’s instructions.

14

Image 14
Contents Contents → Safety ConsiderationsIntroduction Unit IdentificationPage Preinstallation Service Area Requirements SizePhysical Data Unit SizeUnit Rigging Details Mixing Box Damper Operating Torque In.-lb InstallationMixing Box 39L Unit Size TorqueRecommended Actuators Page Install Sheaves on Motor and Fan Shafts IGV Actuator Bracket InstallationDetermining Sheave-Shaft Overhang PD Range Belt Small Deflection Force LB SheaveCross SectionWater and Steam Coil Piping Recommendations Coil Freeze-Up ProtectionLow, Medium or High Pressure Coil Piping Dripping Steam Supply to Condensate Return Chilled Water Coil Circuiting Data Steam Coil Connection Sizes Face Split Coil Suction Line Piping Direct Expansion Coil Circuiting Data Small Face Area 39LB, 39LC, 39LF Unit Size Circuiting Type ROW COIL††Side Connector Hot Gas Bypass Data Distributor Part Numbers= 1.68 x .33 x Face Split Coil Manifolding Typical Electric Heater Installation Typical Electric Heater Wiring Schematic Electric Heater Data Steps FLAWire Size Load Amps Fan Discharge Positions, Fans without IGVsSTART-UP Bolt Size TorqueCoil Cleaning ServiceFan Motor Replacement GeneralField-Installed Coils 39LA,LD Only Coil RemovalHorizontal Unit Slant Coil Removal 39LA Units Sizes Vertical Unit Slant Coil Removal 39LD Units Sizes Page Changing Coil Hand DX and ALL Water Coils Steam Coils Only FiltersFan Shaft Bearing Removal Filter Data Filter Arrangement, 2-in. and 4-in. FlatManufacturer Lubricant LubricationLubricant Data 39L Unit Size Cutoff Cutoff ClearanceMetric Conversion Chart Copyright 2004 Carrier Corporation

39LG, 39LH03-25, 39LD, 39LE, 39LB specifications

The Carrier 39 series, encompassing models 39LA, 39LF, 39LC, 39LB, and 39LE, represents a prominent line of rooftop packaged units that combine robust performance, energy efficiency, and advanced technology for commercial applications. Designed to provide reliable heating and cooling solutions, these units stand out for their versatility and innovative features.

The 39LA model offers high efficiency and flexibility, making it ideal for various building types. It incorporates advanced economizer capabilities that enhance indoor air quality while reducing energy costs. The unit is equipped with a dual-walled cabinet, which not only improves durability but also ensures quiet operation, making it suitable for noise-sensitive environments.

The 39LF model further enhances energy savings, featuring a unique hybrid heat pump system. This system allows for both heating and cooling through an integrated design, reducing the need for separate systems and streamlining maintenance requirements. The 39LF also boasts high Seasonal Energy Efficiency Ratio (SEER) ratings, contributing to lower operating costs without compromising comfort.

The 39LC variant excels in humid climates, employing advanced dehumidification technologies that effectively manage indoor moisture levels. This model is often utilized in environments such as gyms, restaurants, and hotels where humidity control is vital. Its variable-speed compressors adjust output based on demand, optimizing energy consumption while maintaining consistent comfort levels.

The 39LB model focuses on enhanced filtration and air quality improvements. Its engineered design accommodates high-efficiency particulate air (HEPA) filters, crucial for spaces that require stringent air quality standards. This model also includes smart controls that allow for precise temperature adjustments, ensuring optimal comfort in any setting.

Finally, the 39LE unit emphasizes user-friendly interfaces and smart technology integration. The built-in Wi-Fi capability enables remote monitoring and operation, allowing managers to adjust settings from anywhere, improving overall energy management. Additionally, the 39LE’s compatibility with Building Management Systems (BMS) facilitates seamless integration into existing setups.

In summary, the Carrier 39 series 39LA, 39LF, 39LC, 39LB, and 39LE present a comprehensive array of features designed for various commercial heating and cooling applications. With an emphasis on energy efficiency, advanced air quality management, and user-friendly technology, these units continue to set the standard for rooftop packaged units in the industry. Their innovative characteristics not only enhance comfort but also promote sustainability, making them a smart choice for modern commercial environments.