Accessory Return Smoke Detectors
Installation Instructions
Part No. CRSMKDET002C00
CONTENTS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Check Package Contents. . . . . . . . . . . . . . . . . . . . . . . . . 2
Return Air Smoke Detector Installation. . . . . . . . . . . 2
48/50A Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
48/50Z Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Configuring the ComfortLink™ Controller. . . . . . . . 5
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Filter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Board Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .5,6
Smoke Entry Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
•AIRFLOW TEST
•SMOKE RESPONSE TEST
Standby, Alarm and Sensitivity Tests. . . . . . . . . . . . . 6
•STANDBY AND TROUBLE TEST
•ALARM TEST
•SENSITIVITY TEST
GENERAL
An HVAC (heating, ventilation and
The smoke detector utilizes photoelectric technology for the detection of smoke. This detection method, when combined with an efficient ducting design, samples air passing through the unit. If sufficient smoke is sensed, an alarm signal is initiat- ed and the ComfortLink controls will shut down the unit. With the unit shut down, the unit will not blow toxic smoke and fire gases throughout the areas served by the duct system.
SAFETY CONSIDERATIONS
Installation and servicing of
Untrained personnel can perform the basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per- sonnel. When working on
Follow all safety codes. Wear safety glasses and work gloves. Use care when handling and installing the accessory.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PRO- TECTION as a means of providing life safety. Nor are they a substitute for early warning in a building’s regular fire detection system. Carrier supports this position and strongly recommends that the user read NFPA Standards 90A, 72, and 101. This smoke detector is listed per UL 268A.
This device will not operate without electrical power. Fire situations may cause an interruption of power. The system safeguards should be discussed with your local fire protection specialist.
This device will not sense smoke unless the ventilation sys- tem is operating and the cover is installed.
For this detector to function properly, it MUST be installed according to the instructions in this manual. Furthermore, the detector MUST be operated within ALL electrical and environmental specifications listed in this manual. Failure to comply with these requirements may prevent the detec- tor from activating when smoke is present in the air duct.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book | 1 | 1 | PC 111 | Catalog No. | Printed in U.S.A. | Form | Pg 1 | Replaces: New | |
Tab | 1a | 1b |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|