Page 20

a48-2524

Fig. 18 — Field Gas Piping

IMPORTANT: Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg.

Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.

OPTIONAL STAGED GAS UNITS — See Table 7 for staged gas information. Staging pattern is selected during controls start-up.

For complete information and service instructions for Staged Gas Control Units, see Control Operation and Trouble- shooting literature.

Table 7 — 48A Series Staged Gas Control

MODEL NUMBER POSITION

NUMBER OF

HEAT SIZE

5

6,7,8

STAGES

 

 

020

 

 

 

025

 

 

 

027

 

 

 

030

 

 

S

035

 

Low

 

036

 

 

 

040

5 stages

 

 

041

 

 

050

 

 

 

035

 

 

 

036

 

 

T

040

 

High

 

041

 

 

 

050

 

 

 

020

 

 

T

025

7 stages

High

027

 

 

 

 

030

 

 

T

051,060

9 stages

High

S

051,060

11 stages

Low

Step 8 — Make Electrical Connections

POWER WIRING — Units are factory wired for the voltage shown on the unit nameplate.

Provide a unit safety disconnect switch in the main power supply to each unit (see Fig. 19). Select switch size and mount- ing location in accordance with applicable local codes or National Electrical Code (NEC). If combining the functions of safety disconnect with maximum overcurrent protection (MOCP) fuses (“fused disconnect”), coordinate safety switch size with MOCP size data as marked on unit informative plate.

Unit may be equipped with optional factory-installed non- fused disconnect switch (see Fig. 19). Provide maximum overcurrent protection devices (fuses or HACR breakers, per

local codes) in branch circuit wiring remote from unit. Observe requirements of NEC Article 440. Install service switch upstream of remote fuses if required.

The main power terminal block is suitable for use with aluminum or copper wire. See Fig. 19. Units have circuit breakers for compressors, fan motors, and control circuit. The unit must be electrically grounded in accordance with local codes, or in absence of local codes, with NEC, ANSI C1-latest year.

FIELD POWER SUPPLY — Unit is factory wired for volt- age shown on unit nameplate. See Tables 8A and 8B for elec- trical data.

Field wiring can be brought into the unit from bottom (through basepan and roof curb) or through side of unit (corner post next to control box).

A 31/2-in. NPT coupling for field power wiring and a 3/4-in. NPT coupling for 24-v control wiring are provided in basepan. In the side post, there are two 21/2-in. (48A020-035) or 3-in. (48A036-060) knockouts for the field power wiring. See Fig. 4-9. If control wiring is to be brought in through the side of unit, a 7/8-in. diameter hole is provided in the condenser side post next to the control box.

Do not route control wiring in the same conduit as power wiring.

If disconnect box is mounted to corner post, be careful not to drill or screw into the condenser coil.

 

 

 

TB1

 

 

FIELD

21

 

PERDISCONNECTNEC

11

SUPPLIEDFIELD

POWER

22

12

 

 

 

 

SUPPLY

23

 

 

13

 

 

EQUIP GND

 

 

FIELD-INSTALLED DISCONNECT

 

 

 

OPTIONAL

 

 

FACTORY-INSTALLED

 

 

DISCONNECT

WIRING

11

21

12

22

POWERFIELD

13

23

 

 

 

 

GND

 

 

FACTORY-INSTALLED DISCONNECT

a48-6977

LEGEND

GND — Ground

NEC — National Electrical Code

TB — Terminal Block

Fig. 19 — Field Power Wiring Connections

20

Image 20
Contents Installation Instructions Make Unit Duct Connections Instructions onRoof Curb 48AJ,AK020-035 Units Roof Curb 48AJ,AK036-050 Units Roof Curb 48AJ,AK051 and 060 Units Base Unit Dimensions 48AJ,AK020-035 A48-8235Base Unit Dimensions 48AJ,AK036-050 A48-8236Base Unit Dimensions 48AJ,AK051 Base Unit Dimensions 48AW,AY020-035 A48-8380Base Unit Dimensions 48AW,AY036-050 Base Unit Dimensions 48AW,AY051 A48-8240Center of Gravity and Weights 48AJ,AK,AW,AY051,060 A50-8102Physical Data 48AJ,AK,AW,AY Units Compressor035 036 040 041 Nominal Capacity tons 050 051 060 Nominal Capacity tons Rigging Information A48-8246Constant Volume Fan Motor Weights Unit Operating WeightsOption and Accessory Weights Evaporator Fan Motor Data Air Distribution Thru-the-BottomInstall Flue Hood A48-3712A48-3823 A48-3714A48-2524 Make Electrical Connections48A Series Staged Gas Control Unit Voltage 48A Min Max 46.2 203.6 225 Unbalanced 3-Phase Supply Voltage Electrical Data 48AJ,AK,AW,AY Units with Convenience Outlet FLA MCA030 040 Hacr Size Stage A48-8243 A48-6854CCN Connection Approved Shield Cable Color Code RecommendationsMake Outdoor-Air Inlet Adjustments Adding Seal Strip to Top of Hood Sides48-1104 48-1105A48-4328 A48-8499A48-3808 Route VAV Static Pressure SensorsA48-8244 Field Modifications Pressure Transducer LocationsSide Return Air Conversion A48-8245
Related manuals
Manual 118 pages 46.64 Kb

48AJ specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.