Carrier 38HDR018-060 specifications 38HDF018-036 Physical Data

Page 4

Only use factory specified liquid-line filter driers with rated working pressures less than 600 psig.

NOTE: Do not install a suction-line filter drier in liquid line.

MAKE PIPING SWEAT CONNECTIONS — Remove plastic caps from liquid and suction service valves. Use refrigerant grade tubing. Service valves are closed from the factory and are ready for brazing. After wrapping the service valve with a wet cloth, the tubing set can be brazed to the service valve using ei- ther silver bearing or non-silver bearing brazing material. Con- sult local code requirements. Refrigerant tubing and the indoor coil are now ready for leak testing.

NOTE: Unit is shipped with R-410A factory charge indicated on nameplate.

Pass nitrogen or other inert gas through piping while braz- ing to prevent formation of copper oxide.

To avoid damage while brazing, service valves should be wrapped with a heat-sinking material such as a wet cloth.

When brazing tubing sets to the service valves, a brazing shield MUST be used to prevent damage to the painted unit surface.

PROVIDE SAFETY RELIEF — A fusible plug is located in unit suction line; do not cap this plug. If local code requires additional safety devices, install as directed.

Table 1A — 38HDF018-036 Physical Data

 

UNIT 38HDF

018

 

024

 

030

 

036

NOMINAL CAPACITY (Tons)

1.5

 

2.0

 

2.50

 

3.0

OPERATING WEIGHT (lb)

166

 

176

 

187

 

250

REFRIGERANT TYPE

 

 

 

 

R-410A

 

METERING DEVICE

 

 

AccuRater (Located at Fan Coil)

 

CHARGE (lb)*

4.8

 

5.3

 

5.0

 

7.1

OUTDOOR FAN

 

 

 

 

 

 

 

Rpm/Cfm

840/1720

 

840/1720

 

840/1720

 

850/1720

 

 

 

Diameter (in.)

18

 

18

 

18

 

24

No. Blades

3

 

3

 

3

 

3

Motor (hp)

1/8

 

1/8

 

1/8

 

1/4

OUTDOOR COIL

 

 

 

 

 

 

 

Face Area (sq ft)

5.82

 

7.27

 

7.27

 

12.1

 

 

 

No. Rows

2

 

3

 

3

 

2

FPI

20

 

20

 

20

 

20

HIGH PRESSURE SWITCH

 

 

 

 

 

 

 

Cut-In (psig)

420 ± 25

 

420 ± 25

 

420 ± 25

 

420 ± 25

 

 

 

Cutout (psig)

650 ± 10

 

650 ± 10

 

650 ± 10

 

650 ± 10

LOW PRESSURE SWITCH

 

 

 

 

 

 

 

Cut-In (psig)

45 ± 25

 

45 ± 25

 

45 ± 25

 

45 ± 25

 

 

 

Cutout (psig)

20 ± 5

 

20 ± 5

 

20 ± 5

 

20 ± 5

REFRIGERANT LINES

 

 

 

 

 

 

 

Connection Type

 

 

 

 

Sweat

 

Liquid Line (in.) OD

3/

 

3/

 

3/

 

3/

 

 

 

Vapor Line (in.) OD

8

 

8

 

8

 

8

5/8

 

5/8

 

3/4

 

3/4

Max Length (ft)

200

 

200

 

200

 

200

Max Lift (ft)

65

 

65

 

65

 

65

Max Drop (ft)

150

 

150

 

150

 

150

COMPRESSOR

 

 

 

 

 

 

 

Type

 

 

 

 

Scroll

 

Model

ZP16K5E-PFV

 

ZP21K5E-PFV

 

ZP25K5E-PFV

 

ZP34K5P-PFV

 

 

 

Oil Charge (POE - oz)

25.0

 

25.0

 

25.0

 

42.0

Accumulator

 

 

 

 

Yes

 

 

CONTROLS

 

 

 

 

 

 

 

Fusible Plug (F)

 

 

 

210

 

 

Control Voltage†

 

 

 

 

24 vac

208/230 v, Single and 3 Phase,

System Voltage

208/230 v

 

208/230 v

 

208/230 v

 

 

 

 

460 v, 3 Phase

 

 

 

 

 

 

 

 

FINISH

 

 

 

 

Gray

 

 

LEGEND

 

 

*Unit shipped with full factory charge. See ARI (Air Conditioning and

FPI

Fins Per Inch

 

 

Refrigeration Institute) capacity table for proper charge and piston

 

 

for each fan coil type.

 

POE

Polyol Ester

 

 

 

 

 

†24 v and a minimum of 40 va is provided in the fan coil unit.

 

 

 

 

4

Image 4
Contents Installation, Start-Up Service Instructions 38HDF,HDR Unit Dimensions Rig and Mount Unit Lifting Unit with Sling38HDF018-036 Physical Data 38HDR018-060 Physical Data Unit 38HDRMake Electrical Connections Typical Control Circuit Connections38HDF Electrical Data 38HDR Electrical Data 38HDRCAP CchtGND HPSComp CLOEquip Preliminary Checks Condenser-Fan Mounting PositionsRefrigerant Charging Pressure vs. Temperature Chart Puron Refrigerant R-410A Pressure Temperature PsigLubrication Required Liquid Line Liquid Pressure Temperature FSubcooling Charging Table Troubleshooting the Cooling Cycle Copyright 2006 Carrier Corporation

38HDR018-060, 38HDF018-036 specifications

Carrier is a renowned name in HVAC technology, and their 38HDR018-060 and 38HDF018-036 models showcase the fine craftsmanship and innovation typical of the brand. These rooftop units are designed to deliver reliable heating and cooling solutions, making them an ideal choice for commercial spaces and industrial applications.

One of the main features of the Carrier 38HDR and 38HDF series is their ability to provide efficient climate control. The units are equipped with high-efficiency scroll compressors, which ensure reduced energy consumption while maintaining optimal performance. This efficiency translates into significant cost savings on energy bills, making these units an environmentally conscious choice as well.

In terms of design, the 38HDR and 38HDF models boast a rugged construction that can withstand various weather conditions. They are built with a galvanized steel cabinet that resists corrosion, ensuring durability and longevity. The compact design of these rooftop units allows for easy installation and integration into existing structures, offering flexibility for building owners and operators.

Advanced technology is at the heart of these Carrier units. The inclusion of a microprocessor-based control system enables precise temperature management and system monitoring. This technology not only optimizes performance but also provides valuable data for maintenance planning, ultimately reducing the risk of unexpected failures.

The units also come with variable air volume capabilities, which enhances comfort by allowing for customizable airflow to meet specific environmental needs. The 38HDR and 38HDF series is designed to be compatible with multiple zoning systems, allowing facilities to better adapt to changing occupancy and usage patterns.

With sound levels minimized through advanced acoustic engineering, these rooftop units operate quietly, ensuring minimal disruption to occupants. This is especially important in commercial settings, where a peaceful environment is crucial to productivity.

Moreover, both series support enhanced indoor air quality features. With the option for advanced filtration systems, they can effectively remove airborne contaminants, contributing to a healthier indoor environment.

In summary, Carrier's 38HDR018-060 and 38HDF018-036 rooftop units are a powerful combination of efficiency, durability, and advanced technology. Their ability to provide customized heating and cooling solutions makes them an excellent investment for any commercial or industrial application, ensuring comfort and performance for years to come.