Carrier 30GX080-265 manual Certified Dimension Print

Page 9

CUT ALONG DOTTED LINECUT ALONG DOTTED LINE

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

CERTIFIED DIMENSION PRINT

 

TOTAL OPERATING

TOTAL OPERATING

UNIT

WEIGHT

WEIGHT

30GX

Aluminum Fin

Copper Fin

 

lb

kg

lb

kg

206

12,794

5,815

14,462

6,574

226

12,974

5,897

14,642

6,655

250

13,194

5,997

14,862

6,755

NOTES:

 

1.

Unit must have clearances for air ¯ow as follows:

 

Top

Ð Do not restrict in any way

 

Ends

Ð (1524 mm) 5 ft (from solid surface)

 

Sides Ð (1829 mm) 6 ft

2.

Unit with sound hoods requires clearances for air ¯ow

 

as follows:

 

Top

Ð Do not restrict in any way

 

Ends Ð (1829 mm) 6 ft

 

Sides Ð (2134 mm) 7 ft

3.

Center of gravity shown is for aluminum ®n coil. See in-

 

stallation instructions for all other values.