Environmental
Operating | One shock pulse in the positive z axis (one pulse on |
| each side of the system) of 31 G for 2.6 m in the |
| operational orientation. |
Storage
Altitude
Operating
Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 m.
NOTE: For altitudes above 2950 ft, the maximum operating temperature is derated 1.8 ºF/1000 ft.
Storage | Up to 12,000 m ( 39,370 ft). |
Operating Altitude | Up to 35 °C (95 °F) maximum temperature is reduced |
| by 1 °C/300 m (1 °F/547 ft) above 950 m (3,117 ft) |
| 35 °C to 40 °C (95 °F to 104 °F) maximum temperature |
| is reduced by 1 °C/175 m (1 °F/319 ft) above 950 m |
| (3,117 ft) |
| 40 °C to 45 °C (104 °F to 113 °F) maximum temperature |
| is reduced by 1 °C/125 m (1 °F/228 ft) above 950 m |
| (3,117 ft) |
Particulate Contamination
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment it may be necessary for you to remediate the environmental conditions that are causing the damage and/or failures. Remediation of environmental conditions will be the responsibility of the customer.
Air Filtration
NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.
Conductive Dust
NOTE: Applies to data center and
Corrosive Dust
Data center air filtration as defined by ISO Class 8 per ISO
NOTE: Air entering the data center must have MERV11 or MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
•Air must be free of corrosive dust.
•Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
9