One shock pulse in the positive z axis (one pulse on

 

each side of the system) of 31 G for 2.6 m in the

 

operational orientation.

Storage

Altitude

Operating

Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 m.

–30.5 m to 3048 m (–50 to 10,000 ft).

NOTE: For altitudes above 2950 ft, the maximum operating temperature is derated 1.8 ºF/1000 ft.

Storage

Up to 12,000 m ( 39,370 ft).

Operating Altitude De-rating

Up to 35 °C (95 °F) maximum temperature is reduced

 

by 1 °C/300 m (1 °F/547 ft) above 950 m (3,117 ft)

 

35 °C to 40 °C (95 °F to 104 °F) maximum temperature

 

is reduced by 1 °C/175 m (1 °F/319 ft) above 950 m

 

(3,117 ft)

 

40 °C to 45 °C (104 °F to 113 °F) maximum temperature

 

is reduced by 1 °C/125 m (1 °F/228 ft) above 950 m

 

(3,117 ft)

Particulate Contamination

NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment it may be necessary for you to remediate the environmental conditions that are causing the damage and/or failures. Remediation of environmental conditions will be the responsibility of the customer.

Air Filtration

NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.

Conductive Dust

NOTE: Applies to data center and non-data center environments.

Corrosive Dust

Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.

NOTE: Air entering the data center must have MERV11 or MERV13 filtration.

Air must be free of conductive dust, zinc whiskers, or other conductive particles.

Air must be free of corrosive dust.

Residual dust present in the air must have a deliquescent point less than 60% relative humidity.

9

Image 9
Contents Regulatory Model E08J Series Regulatory Type E08J001 Page Unpacking a Rack System Installation And ConfigurationOpening And Closing The Disk Drawer Installing The Physical DisksSecuring The Power Cables Connecting The Power CablesInstalling The Bezel Turning On The SystemOther Information You May Need Obtaining Technical Assistance Technical Specifications Tested Environmental Operating