NOVATION™ Coil Cleaning and Maintenance —

To clean the NOVATION condenser coil, chemicals are NOT to be used; only water is approved as the cleaning solution. Only clean potable water is authorized for cleaning NOVATION condensers.

Clean the coil as follows:

1.Turn off unit power.

2.Remove screws holding rear corner posts and top cover in place. Pivot top cover up 12 to 18 in. (305 to 457 mm) and support with a rigid support. See Fig. 21.

Fig. 21 — Pivot and Support Top Cover

3.Carefully remove any foreign objects or debris attached to the coil face or trapped within the mounting frame and brackets.

4.Using a high pressure water sprayer, purge any soap or industrial cleaners from hose and/or dilution tank prior to wetting the coil.Clean condenser face by spraying the coil core steadily and uniformly from top to bottom, directing the spray straight into or toward the coil face. Do not exceed 900 psig or a 45 degree angle; nozzle must be at least 12 in. (30 cm) from the coil face. Reduce pressure and use caution to prevent damage to air centers (fins). Do not fracture the braze between air centers and refrigerant tubes. Allow water to drain from the coil core and check for refrigerant leaks prior to start−up.

5.Replace top cover and rear corner posts.

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury or equipment damage.

Chemical cleaning should NOT be used on the aluminum microchannel condenser. Damage to the coil may occur. Only approved cleaning is recommended.

Repairing NOVATION Condenser Tube Leaks

RCD offers service repair kit Part Number 50TJ660007 for repairing tube leaks in the NOVATION coil crosstubes. This kit includes approved braze materials (aluminum fluxcore braze rods), a heat shield, a stainless steel brush, replacement fin segments, adhesive for replacing fin segments, and instructions specific to the NOVATION aluminum coil. See EPIC for instruction sheet 99TA526379.

The repair procedure requires the use of MAPP gas and torch (must be supplied by servicer) instead of conventional oxyacetylene fuel and torch. While the flame temperature for MAPP is lower than that of oxyacetylene (and thus provides more flexibility when working on aluminum), the flame temperature is still higher than the melting temperature of aluminum, so user caution is required. Follow instructions carefully. Use the heat shield.

Replacing NOVATION Condenser Coil

The service replacement coil is preformed and is equipped with transition joints with copper stub tubes. When brazing the connection joints to the unit tubing, use a wet cloth around the aluminum tube at the transition joint. Avoid applying torch flame directly onto the aluminum tubing.

Field Refrigerant Access Ports

Field service access to refrigerant pressures is through the access ports located at the service valves (see Fig. 6). These ports are ¼-in SAE Flare couplings with Schrader check valves and service caps. Use these ports to admit nitrogen to the field tubing during brazing, to evacuate the tubing and evaporator coil, to admit initial refrigerant charge into the low-side of the system and when checking and adjusting the system refrigerant charge. When service activities are completed, ensure the service caps are in place and secure; check for leaks. If the Schrader check valve must be removed and re-installed, tighten to 2-3 in-lbs (23-34 N-cm).

Factory High-Flow Access Ports

There are two additional access ports in the system - on the suction tube between the compressor and the suction service valve and on the liquid tube near the liquid service valve (see Fig. 6). These are brass fittings with black plastic caps. The hose connection fittings are standard ¼-in SAE Male Flare couplings.

The brass fittings are two-piece High Flow valves, with a receptacle base brazed to the tubing and an integral spring- closed check valve core screwed into the base. (See Fig. 22.) This check valve is permanently assembled into this core body and cannot be serviced separately; replace the entire core body if necessary. Service tools are available from RCD that allow the replacement of the check valve core without having to recover the entire system refrigerant charge. Apply compressor refrigerant oil to the check valve core's bottom o-ring. Install the fitting body with 96 ±-10 in-lbs (1085 ±23 N-cm) of torque; do not overtighten.

22

Image 22
Contents Contents Safety ConsiderationsInstallation Guideline Replacement /Retrofit R22 to Puron38AUZ*07-14 Unit Dimensions Compressor Unit Size 38AURefrigerant Type Condenser FansNominal Capacity kW Operating Weight kg Aluminum-Fin Coils StandardPressurestat Settings kPa High Cutout Operating Charge, Typical kg† Shipping Charge kgType of Coil Service OptionsModel Type Refrigerant OptionsInstallation Liquid Line Data 38AUZ*07-14 60 Hz Units Refrigerant Piping Sizes 38AUZ*07-14 60 Hz UnitsComplete Electrical Connections Install AccessoriesField Power Supply Refrigerant Specialities Part NumbersConvenience Outlets Units Without Factory-Installed DisconnectUnits with Factory-Installed Disconnect All unitsUnit Connect Primary Transformer Installing Weatherproof CoverConnections Terminals Weatherproof Cover Installation ThermostatElectrical Data 38AUZ*07-14 Hz Units START-UP PRE-START-UPSystem Check Advanced Scroll Temperature Protection Label 38AUZ*07 Charging Chart 38AUZ*14 Charging Chart Operating Sequence Routine System MaintenanceBase Unit Controls Comfort Alert Diagnostic Module ServiceInput LED Status Codes LockoutCompressor Protection Cadm TroubleshootingLubrication Field Refrigerant Access Ports Novation Coil Cleaning and MaintenanceRepairing Novation Condenser Tube Leaks Factory High-Flow Access PortsCompressor Stops on HIGH-PRESSURE Switch TroubleshootingProblem Solution Compressor does not RUN Fastener Torque ValuesUnit Operates TOO Long or Continuously Problem Solution Compressor Cycles on LOW-PRESSURE SwitchCompressor Running but Cooling Insufficient System is NoisyAppendix Catalog No 38AU-01SI Preliminary Information CUT Along Dotted Linecut Along Dotted Line

38AUZ specifications

The Carrier 38AUZ series is a line of air conditioning systems specifically designed to deliver optimal comfort and energy efficiency for both residential and commercial applications. Known for their advanced technology and robust performance, these units are ideal for a variety of climate conditions, ensuring consistent cooling and heating throughout the year.

One of the standout features of the Carrier 38AUZ series is its inverter technology, which allows the unit to adjust its cooling or heating output in real-time based on the ambient conditions. This results in lower energy consumption and reduced operating costs, making the system not only environmentally friendly but also budget-conscious. By minimizing temperature fluctuations, the inverter design promotes a more stable and comfortable indoor environment.

The 38AUZ units are equipped with high-efficiency compressors that enhance the system’s performance. These compressors operate quietly and efficiently, contributing to a lower noise level that is ideal for residential settings. Furthermore, they come with variable speed fan motors which offer precise airflow control, allowing users to customize their comfort level while ensuring energy savings.

In terms of build quality, the Carrier 38AUZ is constructed using durable materials designed to withstand harsh weather conditions. Its compact design allows for easy installation and maintenance, making it an ideal choice for urban environments where space is limited. Additionally, the system features a corrosion-resistant cabinet that extends its lifespan and maintains aesthetic appeal.

The 38AUZ series also includes a range of advanced control options. Users can benefit from smart technology integration, allowing for remote temperature control and scheduling through mobile devices. This feature not only enhances convenience but also provides users with complete control over their energy usage.

Moreover, the Carrier 38AUZ units come with various capacity options, catering to different space requirements. With a focus on energy efficiency, these systems often meet or exceed industry standards, including SEER ratings, ensuring optimal performance without sacrificing energy consumption.

In summary, the Carrier 38AUZ series is an exemplary choice for anyone looking to invest in a reliable, efficient, and advanced air conditioning system. With its inverter technology, high-efficiency compressors, smart control options, and durable construction, the 38AUZ not only delivers exceptional comfort but also promotes energy conservation, making it a smart choice for sustainable living.