Page 1 of 3
20" (508 mm) to 30" (762 mm)
|
| ||
15" (381mm) | |||
|
|
|
|
|
|
|
|
(270 mm)
Top View
(Electronic Ballast)
20" (508 mm) to 30" (762 mm)
15" (381mm)
(270 mm)
Top View
(Magnetic Ballast)
Ceiling Cutout: 8” (203mm) Dia.
7" Aperture, PAR38 Ceramic Metal Halide
1 | 5 | 8 | 1 | 3 | 4 | 2 | 6 | 9 | 7 | C7P38 |
117/8"
(302 mm)
Vertical Adjustment: 3/4" (25 mm) to 2 7/8" (73 mm)
5/8" (16 mm) |
|
|
| 7" (178 mm) Dia. |
| 1 1/8" (29 mm) max. |
|
|
|
| |||
|
|
| ||||
|
|
| Ceiling Thickness | |||
|
|
|
| |||
|
|
|
|
|
|
|
Reflector Trim |
|
| Lamp (Ceramic MH) |
| |
C7P38MHA CLW | Specular Clear, White Painted Flange. | C7A70P38E1 Electronic 120V / C7A70P38E2 Electronic 277V | 70W PAR38 | ||
CLP | Specular Clear, Matching Flange. | C7A10P38E1 Electronic 120V / C7A10P38E2 Electronic 277V | 100W PAR38 | ||
CCDW | Comfort Clear Diffuse, White Painted Flange. | C7A15P38E1 Electronic 120V / C7A15P38E2 Electronic 277V | 150W PAR38 | ||
CCDP | Comfort Clear Diffuse, Matching Flange. | C7A70P38U | Magnetic 120V/277V | 70W PAR38 | |
CCZW | Champagne Bronze, White Painted Flange. | C7A10P38U | Magnetic 120V/277V | 100W PAR38 | |
CCZP | Champagne Bronze, Matching Flange. | C7A15P38U | Magnetic 120V/277V | 150W PAR38 | |
|
|
|
|
|
|
Features
1.Reflector Trim: Low brightness,anodized aluminum with integral flange in painted white or polished to match inside of cone.
2.Lamp Holder Assembly: Unitized optics insure alignment of lamp and aper- ture cone. Integral
3.Trim Adjustment Mechanism: Provides 45° vertical tilt, 360°+ horizontal rotation; lockable. Patented
4.Socket: Medium base porcelain socket with nickel plated screwshell,
pulse rated.
5.Frame Housing: Steel, 0.029"
6.Frame Vertical Adjustment Mechanism: Accommodates mounting to vir- tually any ceiling system using
7.Mounting Bars: Galvanized steel, 0.048"
8.Retention Springs: Rust resistant springs secure trim for quick,
9.Ballast / Cover Assembly: Accessible from below and removable without tools for inspection and ballast replacement .
10.Junction Box: 0.059"
11.Thermal Protector: (Not Shown) Meets NEC and UL requirements. Do not install insulation above nor within 3" (76mm) of any part of the luminaire.
Electrical
Electronic Ballast: 120V or 277V, 50/60 Hz., encased, high power factor, T.H.D. <15%, thermally and transient protected, RMI/RFI complies with FCC part 18
Electrical (cont.)
Ballast | ANSI Code | Voltage | Max. Amps | Input Watts |
70W MH | M98/M143 | 120/277 | 0.67/0.28 | 78 |
100W MH | M90/M140 | 120/277 | 0.90/0.43 | 110 |
150MWH | M102 | 120/277 | 1.40/0.61 | 167 |
Magnetic Ballast: 120/277V dual voltage, 60 Hz., encased and potted,
Ballast | ANSI Code | Voltage | Max. Amps | Input Watts |
70W MH | M98/M143 | 120/277 | 1.90/0.80 | 94 |
100W MH | M90/M140 | 120/277 | 2.40/1.10 | 125 |
150W MH | M102 | 120/277 | 3.70/1.60 | 180 |
Options and Accessories
Fuse (magnetic ballast): Add suffix F1 or F2 to
Chicago Plenum: Consult Factory.
Labels: UL (Suitable For Damp Locations), CSA (magnetic ballast only), I.B.E.W.
For 150W, install fixtures with minimum spacing: 2 feet from
of adjacent luminaries; 1/2 inch from top of luminaire to overhead building member; 1 foot from luminaire center to side building member.
Job Information | Type: |
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier a Genlyte Thomas Companywww.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508)
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • A0504