Ducane (HVAC) (2/4)SH13 warranty Defrost Control Board Diagnostic LEDs

Page 8

the timing selector jumper is not in place, the control defaults to a 90-minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.

A test option is provided for troubleshooting. The test mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at power up, the control will ignore the test pins. When the jumper is placed across the TEST pins for 2 seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5-second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the addi- tional 5-second period has elapsed, the defrost will termi- nate and the test option will not function again until the jumper is removed and reapplied.

Compressor Delay

The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is removed.

NOTE: The 30-second “off” cycle is not functional when jumpering the TEST pins.

Time Delay

The timed-off delay is 5 minutes long. The delay helps to protect the compressor from short cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.

Pressure Switch Circuit

The defrost control includes LO-PS terminals to connect an optional low pressure (loss of charge pressure) switch. A high pressure switch (optional) can be connected to the HI PS terminals (see Figure 8 on page 7).

During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch wired to the control board. In addition, the diagnostic LEDs will indicate a locked-out pressure switch after the fifth occurrence of an open pressure switch (see Table 3).The unit will remain locked out until power to the board is interrupted, then re-established, or until the jumper is applied to the TEST pins for 0.5 seconds.

NOTE:The defrost control board ignores input from the low pressure switch terminals as follows:

During the TEST mode

During the defrost cycle

During the 90-second start-up period

For the first 90 seconds each time the reversing valve switches heat/cool modes

If the TEST pins are jumpered and the 5-minute delay is being bypassed, the LO PS terminal signal is not ignored during the 90-second start-up period.

Diagnostic LEDs

The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition as shown in Table 3.

Defrost Control Board

Diagnostic LEDs

Mode

Green LED

Red LED

(DS2)

(DS1)

 

 

 

 

No Power

Off

Off

to Board

 

 

 

 

 

Normal Operation/

Simultaneous Slow Flash

Power to Board

 

 

 

 

 

Anti-Short Cycle

Alternating Slow Flash

Lockout

 

 

 

 

 

Low Pressure

Off

Slow Flash

Switch Fault

 

 

 

 

 

Low Pressure

Off

On

Switch Lockout

 

 

 

 

 

High Pressure

Slow Flash

Off

Switch Fault

 

 

 

 

 

High Pressure

On

Off

Switch Lockout

 

 

 

 

 

Table 3

Circulating Air Blower

The circulating air blower is controlled by a timing circuit in the blower control.Timings are not adjustable.

There is no blower “on” delay after a call for heating or cooling. Blower “off” delay is 90 seconds after the thermo- stat is satisfied.

Page 8

# 48369K005

Image 8
Contents Installation Maintenance Instructions Table of ContentsLocation InstallationInspection of Shipment Typical Condensate Drain Connection Using Accessory Lift KitRoof Curb Assembly Minimum Clearance Requirements Removing Bottom Duct Covers Minimum Required Surface Area For Disposable FiltersElectrical Access Typical Wiring ConnectionsHeater Kit Accessory Installation Heater Kit Accessory if usedThermostat CompressorDefrost Control Timing Pins OperationDefrost Control Board Sequence of OperationDefrost Control Board Diagnostic LEDs Liquid Subcooling Cooling System PerformanceLiquid Subcooling Size @ ARI Conditions OD 80 IDDB/67 Idwb R22 410AMaintenance Electrical SHOCK, Fire Or Explosion Hazard Owner RecordMotors Outdoor CoilBlower Speed Chart Limited Warranty

(2/4)SH13 specifications

The Ducane (HVAC) 2/4SH13 is a versatile heat pump designed to provide efficient heating and cooling solutions for residential and light commercial applications. Renowned for its reliability and performance, the 2/4SH13 units come equipped with advanced features that ensure a comfortable indoor environment throughout the year.

One of the standout characteristics of the Ducane 2/4SH13 is its impressive Seasonal Energy Efficiency Ratio (SEER) and Heating Seasonal Performance Factor (HSPF) ratings. With a high SEER rating, the heat pump maximizes cooling efficiency, resulting in lower energy bills and reduced environmental impact. The HSPF rating also highlights its effectiveness in heating mode during colder months. This combination of efficiency and effectiveness makes the 2/4SH13 an excellent choice for homeowners looking to minimize energy consumption.

The 2/4SH13 utilizes a scroll compressor, which is recognized for its quiet operation and reliability. This type of compressor works efficiently under various load conditions and contributes to the overall longevity of the unit. Additionally, the heat pump is equipped with a durable cabinet that features a baked-on powder coat finish, ensuring protection against the elements and prolonging the life of the system.

For enhanced comfort, the Ducane 2/4SH13 employs a two-stage heating system that provides consistent heating performance during fluctuating temperatures. This capability minimizes the temperature swings often associated with single-stage systems, allowing for a more stable and comfortable indoor climate.

Furthermore, the heat pump integrates advanced refrigerant management technology, utilizing environmentally friendly R-410A refrigerant. This refrigerant not only meets current environmental regulations but also supports improved system efficiency and lower refrigerant leakage.

Installation and maintenance of the Ducane 2/4SH13 are straightforward, thanks to its compact design and accessible service panels. The unit’s compatibility with smart thermostats allows homeowners to achieve optimal control over their heating and cooling schedules, further enhancing energy savings.

Ducane backs the 2/4SH13 with a robust warranty, providing peace of mind for customers who invest in this efficient heat pump solution. Overall, the Ducane 2/4SH13 stands out in the HVAC market for its blend of efficiency, reliability, and user-friendly features, making it a preferred choice for many seeking optimal indoor comfort.