Energy Tech Laboratories DHG240 Checking GAS Input, GAS Rate Cubic Feet PER HOUR1, Natural GAS

Page 24

035-17233-000-C-0702

FIGURE 20 : PRESSURE DROP ACROSS A DRY INDOOR COIL VS. SUPPLY AIR CFM

ADJUSTMENT OF TEMPERATURE RISE

The temperature rise (or temperature difference between the return air and the heated air from the furnace) must lie within the range shown on the ETL rating plate and the data in Table 2.

After the temperature rise has been determined, the cfm can be calculated as follows:

BtuhbInput 0.8

-------------------------------------------------------

CFM = 1.08 ⋅ °FbTempbRise

After about 20 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts (about six feet from the furnace) where they will not be affected by radiant heat. Increase the blower cfm to decrease the temperature rise; decrease the blower cfm to increase the rise. Refer to Table 11 for blower motor and drive data.

BELT DRIVE BLOWER

All units have belt drive single-speed blower motors. The vari- able pitch pulley on the blower motor can be adjusted to obtain the desired supply air CFM. Tighten belts enough to prevent slipping. but do not over tighten. Belt deflection should be between 1/4" and 1/2" per foot. Refer to Table 15 for blower motor and drive data.

CHECKING GAS INPUT

NATURAL GAS

1.Turn off all other gas appliances connected to the gas meter.

2.With the furnace turned on, measure the time needed for one revolution of the hand on the smallest dial on the meter. A typical gas meter usually has a 1/2 or a 1 cubic foot test dial.

3.Using the number of seconds for each revolution and the size of the test dial increment, find the cubic feet of gas consumed per hour from Table 18.

If the actual input is not within 5% of the furnace rating (with allowance being made for the permissible range of the regu- lator setting), replace the orifice spuds with spuds of the proper size.

NOTE: To find the Btu input, multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in your particular locality (contact your gas company for this information - it varies widely from city to city.)

TABLE 18: GAS RATE - CUBIC FEET PER HOUR1

SECONDS FOR 1 REV.

SIZE OF TEST DIAL

 

 

 

1/2 Cu. Ft.

1 Cu. Ft.

 

 

 

4

450

900

 

 

 

6

300

600

 

 

 

8

228

450

 

 

 

10

180

360

 

 

 

12

150

300

 

 

 

14

129

257

 

 

 

16

113

225

 

 

 

18

100

200

 

 

 

20

90

180

 

 

 

22

82

164

 

 

 

24

75

150

 

 

 

26

69

138

 

 

 

28

64

129

 

 

 

1Example: By actual measurement, it takes 13 seconds for the hand on the 1-cubic foot dial to make a revolu- tion with just a 300,000 Btuh furnace running. Read across to the column in the table above, headed “1 Cubic Foot”, where you will see that 278 cubic feet of gas per hour are consumed by the furnace at that rate. Multiply 278 X 1050 (the Btu rating of the gas obtained from the local gas company). The result is 292,425 Btuh, which is close to the 3000,000 Btuh rating of the furnace.

SECURE OWNER’S APPROVAL

When system is functioning properly, secure the owner’s approval. Show him the location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature settings within the limitations of the system.

24

Unitary Products

Image 24
Contents Installation Instruction Table of Contents General Safety Considerations Product NomenclatureInstallation Agency ApprovalsInspection Location Rigging and HandlingDuctwork Fixed Outdoor AIR Intake DamperService Access Power and Control WiringCondensate Drain CompressorsControl Wire SIZES1 Combustion DischargeGAS Piping GAS ConnectionControlwiring Pipe SIZING1 External Supply Connection External SHUT-OFFPower EXHAUST/BAROMETRIC Relief Damper and Rain Hood Option Enthalpy SET Point AdjustmentVent and Combustion AIR Hoods Enthalpy Setpoint Adjustment Physical Data DHG Voltage LIMITATIONS1Minimum Clearances DHG Electrical DataUnit Dimensions DHG180 & 240 Front View Unit Dimensions DHE/DHG180 & 240 Rear View Utilities Entry230/460 Volt and High Speed Drive Accessory DHG 15 TON Supply AIR Blower PerformanceDHG180 Bottom Duct CONNECTIONS1 Volt and Standard DriveVolt and High Speed Drive Accessory DHG 20 TON Supply AIR Blower PerformanceDHG240 Bottom Duct CONNECTIONS1 Power Exhaust Performance Static RESISTANCES1Blower Motor and Drive Data Safety Controls OperationCooling System Preliminary Operation CoolingHeating System Intermittent BlowerStart UP Manifold GAS Pressure Adjustment POST-START Check List GASPilot Checkout To Shut DownBurner AIR Shutter Adjustment Checking Supply AIR CFMChecking GAS Input GAS Rate Cubic Feet PER HOUR1Secure OWNER’S Approval Belt Drive BlowerMaintenance Normal MaintenanceCleaning Flue Passages and Heating ELE- Ments Troubleshooting Typical Flue Baffle INSTALLA- Tion035-17233-000-C-0702 Unitary

DHG180, DHG240 specifications

Energy Tech Laboratories has made significant strides in the realm of energy efficiency and renewable technologies with the introduction of their innovative models, the DHG240 and DHG180. These advanced devices are designed to optimize energy consumption, minimize environmental impact, and enhance overall energy management.

The DHG240 model stands out with its high-capacity performance, delivering a robust output of 240 kW. This unit is ideal for large facilities and industrial applications, where energy demands are high. One of its main features is its advanced algorithm for energy distribution, which allows for optimal load balancing across various operational units. This ensures that energy is used efficiently, reducing waste and lowering operational costs.

Similarly, the DHG180 is designed for medium-sized operations, providing an output of 180 kW. It offers an effective solution for businesses seeking to improve energy efficiency without the excessive overhead costs typically associated with larger systems. The DHG180 incorporates state-of-the-art monitoring systems that provide real-time data on energy consumption, allowing operators to make informed decisions and adjust settings as needed.

Both models integrate cutting-edge technologies such as smart grid capabilities and renewable energy sources. They are equipped to handle integration with solar panels and wind turbines, enabling facilities to harness clean energy and reduce reliance on fossil fuels. This feature not only contributes to sustainability goals but also provides a buffer against fluctuating energy prices.

The design of both the DHG240 and DHG180 prioritizes durability and reliability. They are constructed from high-quality materials that withstand harsh operational conditions, ensuring a long lifespan and reduced maintenance costs. Furthermore, these systems are compliant with various energy efficiency standards, making them a responsible choice for environmentally conscious businesses.

User-friendliness is another hallmark of these devices. An intuitive interface allows operators to easily monitor and control energy usage, while remote access compatibility enables management from off-site locations. This flexibility is crucial in today’s fast-paced business environment.

In conclusion, Energy Tech Laboratories’ DHG240 and DHG180 models represent the forefront of energy technology. By delivering high performance, integrating renewable solutions, and prioritizing ease of use, these units empower businesses to achieve their energy efficiency goals while promoting sustainability. Whether for large industries or medium-sized enterprises, these systems are engineered to meet the dynamic needs of modern energy management.