Bryant 224A, 223A Outdoor Unit Connected To Factory Approved Indoor Unit, Accessory Usage

Page 3

Table 1 – Accessory Usage

 

REQUIRED FOR LOW---AMBIENT

REQUIRED FOR

REQUIRED FOR

Accessory

COOLING APPLICATIONS

LONG LINE APPLICATIONS*

SEA COAST APPLICATIONS

 

(Below 55°F / 12.8°C)

(Over 80 ft. / 24.38 m)

(Within 2 miles / 3.22 km)

 

 

 

 

Accumulator

Standard

Standard

Standard

Ball Bearing Fan Motor

Yes{

No

No

Compressor Start Assist Capacitor and

Yes

Yes

No

Relay

 

 

 

 

 

 

 

Crankcase Heater

Yes

Yes

No

 

 

 

 

Evaporator Freeze Thermostat

Yes

No

No

Hard Shutoff TXV

Yes

Yes

Yes

Isolation Relay

Yes

No

No

Liquid Line Solenoid Valve

No

See Long--- Line Application

No

Guideline

 

 

 

 

 

 

 

Motor MasterControl or

Yes

No

No

Low Ambient Switch

 

 

 

 

 

 

 

Support Feet

Recommended

No

Recommended

*For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline Application Guideline.

{Additional requirement for Low---Ambient Controller (full modulation feature) MotorMasterr Control.

Outdoor Unit Connected To Factory Approved Indoor Unit

Outdoor unit contains correct system refrigerant charge for operation with approved ARI rated indoor unit when connected by

15ft (4.57 m) of field-supplied or factory-accessory tubing, and factory supplied filter drier. Check refrigerant charge for maximum efficiency.

Refrigerant Tubing and Sweat Connections

Connect vapor tube to fitting on outdoor unit vapor service valves (see Table 2). Connect liquid tubing to adapter tube on liquid service valve. Use refrigerant grade tubing.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Service valves must be wrapped in a heat-sinking material such as a wet cloth while brazing.

Remove plastic retainer holding outdoor piston in liquid service valve, leaving the piston and piston retainer inside the valve. Connect sweat/flare adapter provided, to valve. (See Fig. 4.) Connect refrigerant tubing to fittings on outdoor unit vapor and liquid service valves. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver bearing or non-silver bearing brazing material. Do not use soft solder (materials which melt below 800°F/427°C). Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.

A05226

Fig. 4 - Liquid Service Valve

Table 2 – Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (In.)

 

 

 

RATED VAPOR

 

LIQUID

up to 80 ft. (24.38 m)*

UNIT SIZE

 

 

 

 

 

Connection

Tube

Connection

Tube

 

Diameter

Diameter

Diameter

Diameter

 

 

 

 

 

018, 024

3/8

3/8

5/8

5/8

030, 036

3/8

3/8

3/4

3/4

042, 048

3/8

3/8

7/8

7/8

060

3/8

3/8

7/8

1-1/8

Notes:

1.Tube diameters are for total equivalent lengths up to 80 ft. (24.38 m)

2.Do not apply capillary tube or fixed orifice indoor coils to these units.

*For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.10 m) vertical differential (250 ft./ 76.2 m)Total Equivalent Length), refer to the Longline Guideline--- Air Conditioners and Heat Pumps using Puronr Refrigerant.

Install Liquid Line Filter Drier Indoor

Refer to Fig. 5 and install filter drier as follows:

1.Braze 5 in. (127 mm) liquid tube to the indoor coil.

2.Wrap filter drier with damp cloth.

3.Braze filter drier to 5 in. (127 mm) long liquid tube from step 1.

4.Connect and braze liquid refrigerant tube to the filter drier.

A05227

Fig. 5 - Liquid Line Filter Drier

Evacuate Refrigerant Tubing and Indoor Coil

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used (see triple evacuation procedure in service manual). Always break a vacuum with dry nitrogen.

223A / 224A

3

Image 3
Contents Safety Considerations Installation RecommendationsElectrical Shock Hazard Operating Ambient Install on a Solid, Level Mounting PadCheck Equipment and Job Site Clearance RequirementsRefrigerant Tubing and Sweat Connections Install Liquid Line Filter Drier IndoorAccessory Usage Outdoor Unit Connected To Factory Approved Indoor UnitMake Electrical Connections Start-Up Install Electrical AccessoriesFinal Wiring Check Compressor Crankcase HeaterFinal Checks Heating Check Chart ProcedureCare and Maintenance Check ChargePuronr R-410A Quick Reference Guide Catalog No. II223A 18---4
Related manuals
Manual 58 pages 61.98 Kb Manual 10 pages 44.99 Kb

224A, 223A specifications

The Bryant 223A is a cutting-edge air conditioning unit that epitomizes modern cooling technology. Designed for both residential and commercial applications, this model stands out for its efficiency, reliability, and user-friendly features. One of the most significant aspects of the Bryant 223A is its energy efficiency, boasting a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16. This high rating means lower energy consumption, translating into reduced utility bills for homeowners and businesses alike.

One prominent feature of the Bryant 223A is its environmentally friendly design. It utilizes Puron refrigerant, which has zero ozone-depleting potential, making it a responsible choice for those looking to minimize their environmental footprint. In addition to being eco-conscious, the unit is equipped with a variable-speed compressor, allowing for improved humidity control and enhanced comfort levels. This technology enables the system to adjust its cooling output based on the current indoor conditions, resulting in more consistent temperatures and quieter operation.

Another noteworthy characteristic of the Bryant 223A is its robust construction. The cabinet is designed with galvanized steel, offering durability and resistance to corrosion. This resilience ensures that the unit can withstand the rigors of various weather conditions, contributing to its longevity. Moreover, the unit features an innovative design that minimizes noise levels, ensuring that it operates quietly without disturbing daily activities.

Ease of installation is yet another advantage of the Bryant 223A. The unit comes with a compact design, allowing for straightforward placement in a variety of settings. Additionally, its integration with modern smart thermostats provides users with enhanced control over their indoor climate. This feature enables homeowners to monitor and adjust their air conditioning settings remotely, adding convenience and efficiency to their energy management.

The Bryant 223A also incorporates advanced filtration systems, which significantly improve indoor air quality. Enhanced filters capture a wide range of airborne particles, including allergens, dust, and pollutants, making it an excellent choice for households with allergy sufferers. Overall, the Bryant 223A combines state-of-the-art technology, eco-friendly operation, and user-centric features, making it a leading choice in air conditioning solutions for a variety of environments.