Envision Peripherals Series installation manual Connection to Air Coil, Air Handler Installation

Page 7

NS SPLIT INSTALLATION MANUAL

General Installation Information (cont.)

Connection to Air Coil

Figures 1 and 2 illustrate typical Envision Split installations. The table on page 9 shows typical lineset diameters and maximum length. Linesets over 60 feet are not recommended. If the lineset is kinked or deformed and cannot be reformed, the bad section of pipe should be replaced. A restricted lineset will affect unit performance. As in all R-410A equipment, a reversible liquid line filter drier is required to insure all moisture is removed from the system. This drier should be replaced whenever “breaking into” the system for service. All linesets should be insulated with a minimum of 1/2” closed cell insula- tion. All exterior insulation should be painted with UV resistant paint or covering to insure long insulation life.

Air Handler Installation

Air handlers used with dual capacity units must be capable of operating with a minimum of 2 blower speeds. Refer to the manufacturer’s instructions for the blower coil unit for details on installing the air handling portion of the system. All blower coil units/air coils must be installed as specified by the manufacturer’s installations instructions. However, the following rec- ommendations should be considered to minimize noise and service problems.

An air filter must always be installed upstream of the air coil on the return air side of the air handler of furnace. If there is limited access to the filter rack for normal maintenance, it is suggested that a return air filter grille be installed. Be sure that the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the filter and plugging the air coil.

Ensure that the line set size is appropriate to the capacity of the unit (refer to page 9). Line sets should be routed as di- rectly as possible, avoiding unnecessary bends or turns. All wall penetrations should be sealed properly. Line set should not come into direct contact with water pipes, floor joists, wall studs, duct work, floors, walls and brick. Line set should not be suspended from joists or studs with a rigid wire or strap which comes into direct contact with the tubing. Wide hanger strips which conform to the shape of the tubing are recommended. Isolate hanger straps from line set insulation by using metal sleeves bent to conform to the shape of insulation. Line set insulation should be pliable, and should completely surround the refrigerant line.

Notes: Improper installation of equipment may result in undesirable noise levels in the living areas.

Figure 1: Typical Split System Application - Remote Blower Coil

Supply

Duct

Disconnect

Low

Voltage Wire

Air

r

ndle

 

Ha

 

Insulated

Suction Line

Lineset To Air Handler

Return

Duct

Condensate Drain (must be trapped)

Remote Air Handler

(Maximum Recommended Distance is

50' Between Units)

Image 7
Contents 410A Refrigerant 4, 5, 6 Ton Dual Capacity Geothermal/Water Source Outdoor Split Heat PumpsPage Table of Contents Model Nomenclature Physical CharacteristicsGeneral Installation Information Utilizing Existing Coil or Air Handler Equipment SelectionConnection to Air Coil Air Handler InstallationDual Fuel Systems Electrical Data Thermostat WiringElectrical GeneralWater Piping Closed Loop Earth coupled Systems Outdoor InstallationsConnecting To Earth Loop Flow Center InstallationAir Handler Coil Data Air Handler NomenclatureLine Set Sizes `6O\RZS`RSZcPS`@ST`WUS`O\b  $ ! !$ $ Refrigerant Coil Compatibility Maximum One-Way Line Length Heat Recovery Unit for Domestic Hot WaterWater Tank Preparation Heat Recovery ConnectionsHeat Recovery Startup Plumbing Installation24V Accessory relay see SW2 3 for description of operation Wiring SchematicsMicroprocessor Control Lockout Conditions Fan G onlySTG1 STG2 STG3 Emerg Dual Capacity Units Operation Logic DataFreeze Sensing Setting DIP Switch SettingsCaused by excessive heat RefrigerationCharging the System Leak TestingSystem Evacuation Initial System Charge CalculationDetermining Subcooling Pressure/Temperature Coversion Chart for R-410A Dual Capacity Models Unit Operating ParametersDual Capacity Pressure Drop and Recommended Flow RatesUnit Startup Before Powering Unit, Check The FollowingStartup Steps Final Evaluation Heating Cycle Analysis Unit Startup/TroubleshootingRefrigerant Systems TroubleshootingLED Definitions and Diagnostics Standard Microprocessor ControlsReplacement Procedures Preventive MaintenanceCabinet Dimensions and Refrigerant Piping Connections Physical DimensionsNS026 thru NS072 Installation Notes Page Envision Series NS Outdoor Split

Series specifications

Envision Peripherals, a leading provider of display solutions, offers a wide range of products under its Series lineup tailored to meet diverse consumer needs in the realms of home, office, and gaming. With a focus on quality, performance, and user experience, the Envision Peripherals Series stands out in the crowded display market.

One of the main features of the Envision Peripherals Series is its commitment to high-definition displays. The Series includes a variety of monitors that offer resolutions starting from Full HD (1920x1080) up to 4K Ultra HD (3840x2160). This ensures that users can enjoy crisp and clear visuals whether they are working, watching movies, or gaming. The use of IPS (In-Plane Switching) technology in many of the monitors provides wide viewing angles and accurate color reproduction, making it perfect for creative professionals and content consumers alike.

In terms of technological advancements, the Envision Peripherals Series incorporates adaptive sync technology, such as AMD FreeSync and NVIDIA G-Sync compatibility. This feature reduces screen tearing and stuttering, providing a smoother gaming experience for competitive gamers. Additionally, many models in this series come equipped with high refresh rates, often reaching up to 144Hz, which is essential for fast-paced gaming applications.

The design of Envision Peripherals monitors is nothing to overlook either. Slim bezels and a modern aesthetic are standard across the Series, allowing for a sleek and professional look that fits well in any setting. Furthermore, some models offer ergonomic adjustments such as height, tilt, and swivel options, ensuring comfort during extended use.

Connectivity is another strong suit of the Envision Peripherals Series. Most monitors come with multiple input options, including HDMI, DisplayPort, and even USB-C in select models. This versatility allows easy connection to a variety of devices, from computers to gaming consoles.

Lastly, the emphasis on eye care technology, such as blue light filters and flicker-free screens, highlights Envision Peripherals' commitment to user health and comfort over prolonged periods of use. Overall, the Envision Peripherals Series combines exceptional visual quality, advanced gaming technologies, ergonomic design, and user-friendly connectivity, making it a top choice for consumers seeking a reliable and versatile display solution.