1 . A l l g r o u n d e d , c o r d - c o n n e c t e d t o o l s : In the event of a malfunction or breakdown, grounding provides a path of least resistance for electric current to reduce the risk of electric shock. This tool is equipped with an electric cord having an equipment-grounding conductor and a grounding plug. The plug must be plugged into a matching outlet that is properly installed and grounded in accordance with all local codes and ordinances.
Do not modify the plug provided - if it will not fit the outlet, have the proper outlet installed by a qualified electrician.
Improper connection of the equipment-grounding conductor can result in risk of electric shock. The conductor with insulation having an outer surface that is green with or without yellow stripes is the equipment- grounding conductor. If repair or replacement of the electric cord or plug is necessary, do not connect the equipment-grounding conductor to a live terminal.
Check with a qualified electrician or service personnel if the grounding instructions are not completely understood, or if in doubt as to whether the tool is properly grounded.
Use only 3-wire extension cords that have 3-prong grounding type plugs and 3-hole receptacles that accept the tool’s plug, as shown in Fig. 10.
Repair or replace damaged or worn cord immediately.
GROUNDED OUTLET BOX
CURRENT
CARRYING
PRONGS
GROUNDING BLADE
IS LONGEST OF THE 3 BLADES
HOLES
Fig. 10
EXTENSION CORDS
Use proper extension cords. Make sure your extension cord is in good condition and is a 3-wire extension cord which has a 3-prong grounding type plug and a 3-hole receptacle which will accept the tool’s plug. When using an extension cord, be sure to use one heavy enough to carry the current of the tool. An undersized cord will cause a drop in line voltage, resulting in loss of power and overheating. Fig. 12, shows the correct gauge to use depending on the cord length. If in doubt, use the next heavier gauge. The smaller the gauge number, the heavier the cord.
2.Grounded, cord-connected tools intended for use on a supply circuit having a nominal rating less than 150 volts:
This tool is intended for use on a normal 120-volt circuit and has a grounded plug that looks like the plug illustrated in Fig. 10.
If a properly grounded outlet is not available, a temporary adapter, shown in Fig. 11, may be used for connecting the 3-prong grounding type plug to a 2-hole receptacle. The temporary adapter should be used only until a properly grounded outlet can be installed by a qualified electrician. The green colored rigid ear, lug, or the like extending from the adapter must be connected to a permanent ground such as a properly grounded outlet box cover. Whenever the adapter is used, it must be held in place with a metal screw.
NOTE: In Canada, the use of a temporary adapter is not permitted by the Canadian Electric Code.
WARNING: IN ALL CASES, MAKE CERTAIN THE RECEPTACLE IN QUESTION IS PROPERLY GROUNDED. IF YOU ARE NOT SURE HAVE A CERTIFIED ELECTRICIAN CHECK THE RECEPTACLE.
HOLES
GROUNDED OUTLET BOX
GROUNDING
MEANS
ADAPTER
Fig. 11
MINIMUM GAUGE EXTENSION CORD
RECOMMENDED SIZES FOR USE WITH STATIONARY ELECTRIC TOOLS
Ampere | Volts | Total Length of | Gauge of |
Rating | | Cord in Feet | Extension Cord |
0-6 | 120 | up to 25 | 18 AWG |
0-6 | 120 | 25-50 | 16 AWG |
0-6 | 120 | 50-100 | 16 AWG |
0-6 | 120 | 100-150 | 14 AWG |
6-10 | 120 | up to 25 | 18 AWG |
6-10 | 120 | 25-50 | 16 AWG |
6-10 | 120 | 50-100 | 14 AWG |
6-10 | 120 | 100-150 | 12 AWG |
10-12 | 120 | up to 25 | 16 AWG |
10-12 | 120 | 25-50 | 16 AWG |
10-12 | 120 | 50-100 | 14 AWG |
10-12 | 120 | 100-150 | 12 AWG |
12-16 | 120 | up to 25 | 14 AWG |
12-16 | 120 | 25-50 | 12 AWG |
12-16 | 120 | GREATER THAN 50 FEET NOT RECOMMENDED |
| | | |
Fig. 12