Sanyo SPW-UMR94EXH56 Insulating the Refrigerant Tubing Tubing Insulation, Insulation material

Page 14

5-3. Insulating the Refrigerant Tubing

Tubing Insulation

Thermal insulation must be applied to all unit tub- ing, including distribution joint (purchased sepa- rately).

*For gas tubing, the insulation material must be heat resistant to 120°C or above. For other tubing, it must be heat resistant to 80°C or above.

Insulation material thickness must be 10 mm or greater.

If the conditions inside the ceiling exceed DB 30°C and RH 70%, increase the thickness of the gas tubing insulation material by 1 step.

Two tubes arranged together

Narrow tubing

Wide tubing

Insulation

Three tubes arranged together

Cosmetic

(finishing) tape Wide tubing

Narrow tubing

CAUTION

Taping the flare nuts

If the exterior of the outdoor unit valves has been finished with a square duct covering, make sure you allow suffi- cient space to use the valves and to allow the panels to be attached and removed.

Insulation

Balance tubing

 

 

 

 

 

Fig. 5-7

Sealer (supplied)

 

Wind the white insulation tape around the flare nuts at the wide tube connections. Then cover up the tubing connections with the flare insulator, and fill the gap at the union with the supplied black insulation tape. Finally, fasten the insulator at both ends with the sup- plied vinyl clamps. (Fig. 5-8)

Insulation material

The material used for insulation must have good insu- lation characteristics, be easy to use, be age resis- tant, and must not easily absorb moisture.

After a tube has been insu-

CAUTION lated, never try to bend it into a narrow curve

because it can cause the tube to break or crack.

 

Insulation tape (white)

 

(supplied)

 

Flare insulator (supplied)

Unit side

Tube insulator

(not supplied)

insulator

Heat resistant

 

120°C or above

Flare nut

Vinyl clamps (supplied)

 

 

Fig. 5-8

 

Refrigerant tubing and insulator

Drain insulator

(not supplied)

Drain pipe and insulator

and clamp.

Large

(not supplied)

(supplied)

 

Packing

 

clamp.

Insulation

Small

tape

hose band

Vinyl

(supplied)

Flare clamp

 

 

insulator

 

Seal

 

The procedure used for

 

installing the insulator for

 

both wide and narrow

 

tubes is the same.

Fig. 5-9

Never grasp the drain or refrigerant connecting outlets when moving the unit.

14

Image 14
Contents Sanyo Airconditioners Europe S.r.l Outdoor UnitsOptional Controllers …In Moist or Uneven Locations For safe installation and trouble-free operation, you must…In a Room …In an area with High WindsCheck of Density Limit Contents HOW to Install the Unit Duct for fresh air 16/18/22 Power supply Time delay fuse or circuit capacity General Precautions on WiringIndoor unit Power supply Time delay fuse or Wire size Use shielded wiringWiring System Diagrams 7P terminal boardOutdoor unit Indoor unit How to connect wiring to the terminal For stranded wiring Deburring Connecting the Refrigerant Tubing Use of the Flaring MethodFlaring Procedure with a Flare Tool Tube diameter Tightening torque Tube thickness Approximate Three tubes arranged together Insulating the Refrigerant Tubing Tubing InsulationTwo tubes arranged together Insulation materialFinishing the Installation Taping the TubesName of Parts Indoor Unit Care and CleaningHow to clean the filter Type PeriodTroubleshooting Tips for Energy SavingType Période Nom des pièces unité intérieureEntretien et nettoyage Comment nettoyer le filtreEntretien avant une période d’inactivité prolongée Choses à faire Guide de dépannageConseils pour économiser l’énergie Typ Zeitraum Care and Cleaning Pflege und ReinigungBezeichnungen der Teile Reinigen des LuftfiltersZeit nicht verwendet wurde Zeit nicht verwendet werden sollFehlersuche Nützliche Hinweise für EnergieeinsparungTipo Periodo Nome delle parti Unità internaCura e manutenzione Pulizia del filtroPrecauzione Prima di chiamare il tecnico Suggerimenti per risparmiare energiaUnidade interior Pano macio e limpo Nomenclatura das peças unidade interiorCuidados e limpeza Tipo PeríodoPrecaução Resolução de problemas Sugestões para poupar energiaUMR Page Page Cómo limpiar el filtro Nombres de las partes unidad interiorCuidados y limpieza Precaución Localización de averías Sugerencias para ahorrar energía
Related manuals
Manual 36 pages 42.51 Kb Manual 38 pages 26.88 Kb

PW-UMR184EXH56, R410A, SPW-UMR74EXH56, SPW-UMR224EXH56, SPW-UMR164EXH56 specifications

Sanyo R410A is a refrigerant blend that has gained popularity in air conditioning and refrigeration systems due to its efficiency and environmental benefits. Comprised of two main components, difluoromethane (R-32) and pentafluoroethane (R-125), R410A is categorized as an HFC (hydrofluorocarbon) refrigerant. One of its main advantages is its zero ozone depletion potential, making it an eco-friendly alternative to older refrigerants like R22, which are being phased out due to their harmful effects on the ozone layer.

One of the key features of Sanyo R410A is its high efficiency, which translates to lower energy consumption in air conditioning applications. The thermodynamic properties of R410A allow for higher cooling capacity and reduced energy input, yielding higher seasonal energy efficiency ratios (SEER) compared to R22 systems. This efficiency is not just beneficial for users looking to save on energy bills, but it also contributes to a reduced carbon footprint.

The blend's higher pressure capabilities allow manufacturers to design more compact and lightweight systems, which can lead to better utilization of space in residential and commercial settings. These space-saving designs are often equipped with advanced technologies such as inverter-driven compressors, which adjust their operating speed based on the cooling demand, further enhancing system efficiency.

Sanyo R410A also features excellent thermal properties, providing effective cooling performance across a range of ambient temperatures. The refrigerant has a lower volatility compared to older alternatives, which contributes to improved system stability and reliability over time. Additionally, R410A does not contribute to global warming to the extent of previous refrigerants, although its global warming potential is still a consideration for the future.

Among its technological advancements, Sanyo R410A enables the use of innovative HVAC systems that employ enhanced heat exchange methods. These systems often include microchannel coils that improve heat transfer efficiency while reducing refrigerant charge. The compatibility of R410A with various components allows manufacturers to push the boundaries of design and functionality in climate control systems.

In conclusion, Sanyo R410A stands out due to its exceptional efficiency, environmentally friendly characteristics, and compatibility with advanced technologies. As the HVAC industry continues to evolve, R410A's features and properties position it as a reliable choice for modern air conditioning and refrigeration applications. Its adoption marks a significant step towards achieving greater energy efficiency and sustainability in climate control solutions.