3M 5317, 5319, 5316 instruction sheet Kit Contents kit contains 3 splices, Technical Information

Page 1

Motor Lead Pigtail Splice

for 5/8 kV Non-Shielded Cables

for 1000 Volts or less cables (heavy-duty and two-hole lug applications)

Instructions

CSA Certified for 600V or Less

Kit Contents (kit contains 3 splices):

3—Lug Covers 3—Locking Pins 3—Tubes Silicone Grease 3—Bag Solvent Cleaning Cloths 3—Mastic Sealing Strip(s)*

3—Strips Scotch® Linerless Rubber Splicing Tape 130C 3—Instruction Sheet

*Quantity varies with kit number.

Table 1

Kit

Cable Size Range

Cable

 

Max.

Number

(AWG/kcmil)

Insulation

Bolt

 

Feeder

Motor Lead

O.D.Range

Length

5316

8–4

10–4

0.30–0.51 in.

12 in.

5317

2–1/0

4–1/0

0.43–0.65 in.

34 in.

5318

1/0–250

2–250

0.53–0.88

in.

114 in.

5319

250–500

4/0–500

0.75–1.12

in.

112 in.

Technical Information:

•  For non-shielded cables •  Rated 5/8 kV

•  For cables rated 1000 Volts or less (heavy-duty and two hole lug applications)

•  Cable Size Range:  Feeder:  #8 AWG—500 kcmil Motor Lead:  #10 AWG—500 kcmil

•  Copper Conductors

Caution

Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product.

3MMotor Lead Pigtail Splice Kits

for 5/8 kV or less Non-Shielded Cables

5316, 5317, 5318, 5319

78-8096-4634-8-F

Image 1
Contents Technical Information Kit Contents kit contains 3 splicesInstall Lugs Prepare Cable According to Standard ProceduresInstall Lug Cover Scotch Linerless Rubber Splicing Tape 130C Copper Lugs Tooling Index