Sanyo 09KHS71 dimensions Power, 115/1/60, Compressor, Outdoor Unit, Indoor Unit, Refrigerant

Page 1

Print Form

Split System Submittal Data

System: 09KHS71 Indoor/Outdoor: KHS0971/CH0971

Wall Mounted Heat Pump

Job Name:

Location:

Engineer:

Submitted to:

Submitted by:

Reference:

 

General Data (at 115V)

Power

V/PH/Hz

 

115/1/60

Circuit Ampacity

 

(A)

20

Fuse Size, Max.

 

(A)

20

Compressor

 

DC Rotary Inverter

No. used

 

 

1

R.L. Amps - L.R.

 

(A)

6.55/9.25-20

Crankcase Heater

 

(W)

20

Outdoor Unit

 

 

 

Fan type

 

 

Propeller

Dia. (in.) - No. Speeds

 

 

15-3/4-1

Type Drive - No. Speeds

 

 

Direct - 3

No. Poles

(RPM)

 

8-750

No. Motors

(W)

 

30-1

CFM

(High)

 

883

F.L. Amps

(A)

 

0.6

Coil Type

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

Corrugated Plate - Inner Rifed

Rows - F.P.I.

 

 

2-18.1

Face Area

(sq.ft.)

 

3.1

Tube Size

(in.)

 

5/16”

Indoor Unit

 

 

 

Fan type

 

 

Cross Flow

Dia. & Length (in.) - No. Speeds

D3-11/6

L24-31/32-1

No. Speeds

 

 

3 & Auto

No. Poles

(RPM, High)

 

4-1200

No. Motors

(W)

 

13.8-1

CFM

(HI/Med/Lo)

 

282/247/200

Indoor Sound Rating

(Hi) (dB-A)

 

34

F.L. Amps

(A)

 

0.345

Coil Type

Aluminum Plate Fin & Copper Tube

Fin Type - Pipe Type

 

Slit Plate - Inner Rifed

Rows - F.P.I.

 

 

2-19.5

Face Area

(sq.ft.)

 

2.02

Tube Size

(in.)

 

9/32”

Drain Connection Size

(in.)

 

23/32”

Approval:

Date:

Construction:

Unit #:

Drawing #:

Refrigerant

 

 

 

 

R410A

Lbs. - R410a (outdoor unit)

 

 

 

2.09

Control

 

 

Electric Expansion Valve

Connection

 

 

 

 

Flare

Line Length, Max (ft.)

 

 

 

 

50

Lift Difference, Max (ft.)

 

 

 

 

23

Line Size

(in. O.D. Discharge)

1/4”

Line Size

 

(in. O.D. Suction)

3/8”

Dimensions

(in.)

 

 

H x W x D

Indoor Unit

(Uncrated)

11-7/32 x 32-15/32 x 7-7/16

Outdoor Unit

(Crated)

 

13-25/32 x 35-7/16 x 10-1/32

(Uncrated)

21-9/16 x 28-11/32 x 10-7/16

 

(Crated)

23-5/8 x 33-11/16 x 14-1/4

Weight

 

Indoor

 

 

Outdoor

Net

(lbs.)

19.8

 

 

75.0

Shipping

(lbs.)

24.3

 

 

81.6

Shipping Volume

 

Indoor

 

Outdoor

(cu.ft.)

2.82

 

 

6.36

Performance Data @ ARI Standard Conditions (230/208V)

Cooling

 

 

 

 

 

Total Capacity

 

(BTU/H)

9,000 (3,000-9,000)

Sensible Capacity

 

(BTU/H)

 

7,650

Latent Capacity

 

(BTU/H)

 

1,350

SEER

 

 

 

 

16

Dehumidification

 

(Pints/H)

 

3.4

Amps

 

(A)

 

 

-/7.6 (2.5-7.6)

Power Inputs

 

 

(W)

 

-/755 (250-755)

Outdoor Sound Rating

 

(dB-A)

 

 

46

Heating

 

 

 

 

 

Total Capacity

 

(BTU/H)

12,200 (3,000-12,200)

HSPF

 

 

 

 

8.5

Image 1
Contents Dimensions PowerWeight 115/1/60Heating Options FeaturesOperating Range 0F DB