1.2Fixed Application Problems
a door is currently open
a door is currently released
user(s) have not yet changed the default PIN
a terminal is enabled for operation e.g. only by key (without a user PIN)
possible attack by running out of power indicates a problem from the attached ADI (MBus addressing unit)

Maintenance Info MI290a: Guarto MP3 SR1

1.2Fixed Application Problems

A CT6C configured for ‘Section operation’ does not crash the system anymore. The internal workspace for the terminal application is now increased so that the function has enough memory available.

A wrong indication “not done” for the execution of a command has been eliminated. This was just indicated for a Section with Exit-Route when it was switched on, in case the configuration did allow switching off/on the sensors.

For the private devices CT6C and DCU6 on the LON bus, the communication has been enhanced. Now the supervision is stable so that random connection tamper messages will be avoided.

1.3Improvements for Management Station

The stability of the communication is improved for the connection of management stations. In fact, a correction in the MM8001 allows now to connect two such sta- tions with Guarto.

New properties are supported in the communication model, which were added in the application of MP3. They are now available on the interface, but have not been added to the exported data in the profiles (due to incompatibility in import).

z‘Door’ object for access control

doorOpen

doorUnlocked

z‘Area’ object

initialPINs

inhibitionTimeNotActive z ‘Terminal’ object

operationFree

z‘PowerSupply’ object

tamperEmergencyPower

faulty

1.4Known Problems

Guarto: Communication with management stations:

The protection for the time synchronization via network is too restrictive. There is currently no way for correcting errors from remote (e.g. wrong daylight saving time). Local access is necessary to put CS6 in Service-Mode.

SWE6-Tool: Configuration and data export:

The dialogues are missing in the Area for setting the delay times of the remote

 

transmission of ‘Security-jeopardizing-faults’ and ‘Major-fault’ (default = 120s!).

The Profile-Generator does not put virtual Sections (without Zones) into the pro-

 

files. Æ Workaround: attach a dummy Zone (linked to ADI) getting both entries.

Mind the improved SWE6 tool V5.0a which became available in March 2005.

4

 

 

 

Building Technologies

MI290a.doc

Fire Safety & Security Products

01.2009

Image 4
Contents Maintenance Info MI290a MP3 - Service Release SR1 Fire Safety & Security ProductsGuarto Multifunctional Security System Building TechnologiesPage 1.1Actual Compatibility Maintenance Info MI290a Guarto MP3 SR11 Maintenance Info MI290a Guarto MP3 SR1 1.2Fixed Application Problems 1.4Known Problems1.3Improvements for Management Station Maintenance Info MI290a Guarto MP3 SR1Maintenance Info MI290a Guarto MP3 SR1 Fire Safety & Security ProductsBuilding Technologies MI290a.docA6V10235239