HP BladeSystem p-Class 1U manual Pdu

Page 19

47U rack

Mounting the PDUs in the 1U configuration requires an additional 3U of vertical space in the rack. Three PDUs must be mounted facing the front of the rack and three PDUs must be mounted facing the back of the rack (Figure 12). This provides 42U of vertical space for the servers and power enclosures and 3U additional space for the PDU mounting. This configuration must be assembled onsite, as it is not available through Factory Express.

Figure 12. Partial diagram of front and back mounted PDUs

FrontBack

PDU

PDU

PDU

PDU

800-mm-wide 42U rack

The 800-mm-wide rack ships standard with vertical blanking panels that block air recirculation back to the front of the rack. Each side of the rack provides 100mm (approximately 4 inches) of space on either side of the rack for access to the 0U space. Access to the PDUs from the front of the rack can be gained by removing the three screws that secure the vertical blanking panels. This configuration must be assembled onsite, as it is not available through Factory Express.

19

Image 19
Contents Technology brief Page Components of the enclosure Hot-plug, redundant power suppliesAbstract IntroductionRedundant AC power Bi-directional electronic e-fuse Features of the enclosureHot-plug power management module Power zonesPage Dynamic power saver Serial port Serial port display Efficient cabling PDU power cables connected to the 1U power enclosure HP BladeSystem p-Class Sizing utility Infrastructure configurationsUsing PDUs with the 1U power enclosure Phase Standard configurations Page Page Risks associated with extreme density Supported configurations for the 40 a PDUPDU Page Conclusion For more information Power-protection/rackups/index.html