Roberts Gorden UHD[S] 75 - 125, UHD[S] 150-400 manual Combat UHDS-Series Technical Data

Page 4

Combat® UHD[S]-Series Technical Data

Model

 

75

100

125

150

175

200

225

250

300

350

400

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Input

[Btu/h] x [1000]

75

100

125

150

175

200

225

250

300

350

385

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Output

[Btu/h] x [1000]

61.5

82

102.5

123

143.5

164

184.5

205

246

288.6

315.7

 

 

 

 

 

 

 

 

 

 

 

 

Efficiency

 

82% - All Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of Burners

 

5

6

7

7

8

9

10

11

12

14

14

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Connection

[in]

½

½

½

½

½

½

¾

¾

¾

¾

¾

 

 

 

 

 

 

 

 

 

 

 

 

 

Inlet Pressure

[in wc] NG Min.

5

 

 

 

 

 

 

 

 

 

 

 

LPG Propane Min.

12

 

 

 

 

 

 

 

 

 

 

NG & LPG Propane Max.

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Supply

 

115 V / 60 Hz / 1 Ø - All Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Air Volume

[CFM]

850

950

1020

1360

1400

2050

2100

2350

2700

3120

3420

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature Rise @

 

68

78

92

83

95

73

80

80

86

86

86

Minimum Air Volume

[°F]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Exchanger Pressure Drop

0.06

0.05

0.06

0.02

0.03

0.025

0.035

0.05

0.02

0.03

0.04

@ Minimum Air Volume

[in wc]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Air Volume

[CFM]

2650

3660

4750

5800

6850

7750

8300

8850

10200

13600

14200

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature Rise @

 

22

22

20

20

20

20

20

22

23

22

22

Maximum Air Volume

[°F]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Exchanger Pressure Drop

0.36

0.55

0.98

0.16

0.29

0.163

0.253

0.35

0.27

0.48

0.53

@ Maximum Air Volume

[in wc]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flue Size

[in]

4 - All Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air Intake

[in]

4

4

4

4

4

4

4

4

5

5

5

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight

[lb]

81

92

97

191

211

239

249

254

325

345

345

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation Code and Annual Inspections:

All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON® equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.

Further Information: Applications, engineering and detailed guidance on systems design, installation and equipment performance is avail- able through ROBERTS GORDON® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.

This product is not for residential use.

This document is intended to assist licensed professionals in the exercise of their professional judgement.

Roberts-Gordon LLC

European Office:

1250 William Street

Roberts Gordon Europe Limited

P.O. Box 44

Telephone: +44(0) 121 506 7700

Buffalo, NY 14240-0044 USA

Fax: +44(0) 121 506 7701

Telephone: 716.852.4400

 

Fax: 716.852.0854

 

Toll Free: 800.828.7450

 

www.rg-inc.com

 

© 2008 Roberts-Gordon LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical, including photocopying, recording, taping, or information storage

and retrieval systems – without written permission of Roberts-Gordon LLC.

Printed in U.S.A.

UHDSNA

5M 0308 Orig.

Image 4