Toshiba Official Manual for G8000 Series Indoor Furnishings TS4 Models

Page 2

TS MATCHING

T S4

CABINET SERIES

Toshiba G8000 Series

100-300 KVA

 

BOTTOM VIEWSIDE VIEWFRONT VIEW

System Sizing Matrix

 

 

 

UPS KVA RATING

 

 

 

 

 

# OF

TOSHIBA

100

150

225

300

 

OVERALL DIMENSIONS

WEIGHT

 

BATTERY KWB

 

 

STRINGS

SYSTEM MODEL

 

 

 

(INCHES / MM)

 

(LBS / KG)

86.020

129.030

193.550

258.060

 

 

 

NUMBER

 

 

 

Net*

 

 

 

RUN TIMES

 

Height

Depth

Width

 

 

 

 

 

 

1

G8-TSXXX5-HXXX

5

78.7 / 1999

29.5 / 749.3

36 / 914

2375 / 1080

 

G8-TSXXX6-HXXX

6

78.7 / 1999

29.5 / 749.3

36 / 914

2624 / 1193

 

G8-TSXXX9-HXXX

9

78.7 / 1999

29.5 / 749.3

36 / 914

2921 / 1328

 

G8-TSXXX16-HXXX

16

8

78.7 / 1999

29.5 / 749.3

36 / 914

3495 / 1589

2

2G8-TSXXX19-HXXX

19

10

78.7 / 1999

29.5 / 749.3

2 x (36 / 914)

4750 / 2159

 

2G8-TSXXX22-HXXX

22

12

5

78.7 / 1999

29.5 / 749.3

2 x (36 / 914)

5248 / 2385

 

2G8-TSXXX27-HXXX

27

15

7

78.7 / 1999

29.5 / 749.3

2 x (36 / 914)

5842 / 2655

 

2G8-TSXXX41-HXXX

41

24

13

8

78.7 / 1999

29.5 / 749.3

2 x (36 / 914)

6990 / 3177

3

3G8-TSXXX47-HXXX

47

27

15

9

78.7 / 1999

29.5 / 749.3

3 x (36 / 914)

8788 / 3995

 

3G8-TSXXX65-HXXX

65

41

24

16

78.7 / 1999

29.5 / 749.3

3 x (36 / 914)

10485 / 4766

4

4G8-TSXXX69-HXXX

69

41

24

16

78.7 / 1999

29.5 / 749.3

4 x (36 / 914)

11684 / 5311

 

4G8-TSXXX89-HXXX

89

60

35

24

78.7 / 1999

29.5 / 749.3

4 x (36 / 914)

13980 / 6355

5

5G8-TSXXX133-HXXX

133

70

48

32

78.7 / 1999

29.5 / 749.3

5 x (36 / 914)

17475 / 7943

* For shipping purposes, add 3% to weight.

Breaker Per String Sizing

# OF STRING

100KVA

150KVA

225KVA

300KVA

SOLUTION

 

 

 

 

1

H300

H600

2

(2) H150

(2) H225

(2) H400

(2) H600

3

(3) H100

(3) H150

(3) H225

(3) H300

4

(4) H100

(4) H125

(4) H175

(4) H225

5

(5) H60

(5) H100

(5) H150

(5) H175

Notes:

1)All systems are 360 volts nominal. Batteries are sized to an end voltage of 1.67 VPC up to 90 minutes and to 1.75 above 90 minutes at 25°C.

2)All KWB ratings are calculated at 0.8 power factor. The inverter efficiency rating is 93%.

3)Toshiba Battery System Model Number example: a 100 KVA two string cabinet system with a breaker, auxiliary contacts and 24 volt shunt trip for a

runtime of 19 minutes : 2G8-TS10019-H150.

4)The TS series of cabinets are designed for multiple cabinet daisy-chain connections.

Image 2
Contents Introduction FeaturesDimensions and weights Options Maximum Quantity of PRC/TC Batteries per CabinetSystem Sizing Matrix Breaker Per String Sizing