TS MATCHING | T S4 | |
CABINET SERIES | Toshiba G8000 Series | |
|
BOTTOM VIEWSIDE VIEWFRONT VIEW
System Sizing Matrix
|
|
| UPS KVA RATING |
|
|
|
|
| |
# OF | TOSHIBA | 100 | 150 | 225 | 300 |
| OVERALL DIMENSIONS | WEIGHT | |
| BATTERY KWB |
|
| ||||||
STRINGS | SYSTEM MODEL |
|
|
| (INCHES / MM) |
| (LBS / KG) | ||
86.020 | 129.030 | 193.550 | 258.060 |
|
| ||||
| NUMBER |
|
|
| Net* | ||||
|
|
| RUN TIMES |
| Height | Depth | Width | ||
|
|
|
|
|
| ||||
1 | 5 | – | – | – | 78.7 / 1999 | 29.5 / 749.3 | 36 / 914 | 2375 / 1080 | |
| 6 | – | – | – | 78.7 / 1999 | 29.5 / 749.3 | 36 / 914 | 2624 / 1193 | |
| 9 | – | – | – | 78.7 / 1999 | 29.5 / 749.3 | 36 / 914 | 2921 / 1328 | |
| 16 | 8 | – | – | 78.7 / 1999 | 29.5 / 749.3 | 36 / 914 | 3495 / 1589 | |
2 | 19 | 10 | – | – | 78.7 / 1999 | 29.5 / 749.3 | 2 x (36 / 914) | 4750 / 2159 | |
| 22 | 12 | 5 | – | 78.7 / 1999 | 29.5 / 749.3 | 2 x (36 / 914) | 5248 / 2385 | |
| 27 | 15 | 7 | – | 78.7 / 1999 | 29.5 / 749.3 | 2 x (36 / 914) | 5842 / 2655 | |
| 41 | 24 | 13 | 8 | 78.7 / 1999 | 29.5 / 749.3 | 2 x (36 / 914) | 6990 / 3177 | |
3 | 47 | 27 | 15 | 9 | 78.7 / 1999 | 29.5 / 749.3 | 3 x (36 / 914) | 8788 / 3995 | |
| 65 | 41 | 24 | 16 | 78.7 / 1999 | 29.5 / 749.3 | 3 x (36 / 914) | 10485 / 4766 | |
4 | 69 | 41 | 24 | 16 | 78.7 / 1999 | 29.5 / 749.3 | 4 x (36 / 914) | 11684 / 5311 | |
| 89 | 60 | 35 | 24 | 78.7 / 1999 | 29.5 / 749.3 | 4 x (36 / 914) | 13980 / 6355 | |
5 | 133 | 70 | 48 | 32 | 78.7 / 1999 | 29.5 / 749.3 | 5 x (36 / 914) | 17475 / 7943 |
* For shipping purposes, add 3% to weight.
Breaker Per String Sizing
# OF STRING | 100KVA | 150KVA | 225KVA | 300KVA | |
SOLUTION | |||||
|
|
|
| ||
1 | H300 | H600 | – | – | |
2 | (2) H150 | (2) H225 | (2) H400 | (2) H600 | |
3 | (3) H100 | (3) H150 | (3) H225 | (3) H300 | |
4 | (4) H100 | (4) H125 | (4) H175 | (4) H225 | |
5 | (5) H60 | (5) H100 | (5) H150 | (5) H175 |
Notes:
1)All systems are 360 volts nominal. Batteries are sized to an end voltage of 1.67 VPC up to 90 minutes and to 1.75 above 90 minutes at 25°C.
2)All KWB ratings are calculated at 0.8 power factor. The inverter efficiency rating is 93%.
3)Toshiba Battery System Model Number example: a 100 KVA two string cabinet system with a breaker, auxiliary contacts and 24 volt shunt trip for a
runtime of 19 minutes :
4)The TS series of cabinets are designed for multiple cabinet