Roberts Gorden HE-175, HE-60, HE-80, HE-40, HE-100, HE-150, HE-125 Roberts-Gordon, European Office

Page 2

Burner End View

Side View

Top View

 

Reflector

 

13.5"

17.5"

 

(34 cm)

(44 cm)

Turbulator (some models)

 

9.5"

 

 

 

(24 cm)

 

 

Length “A”

 

Overall

Length “C”

18"

(457 mm)

Length “B”

Overall Length “D”

 

 

 

 

 

 

 

VANTAGE® HE

 

 

Model

 

 

 

HE-40

HE-60

HE-80

HE-100

HE-125

HE-150

HE-175

 

 

 

Length of Straight Tube

 

(ft, in) A

10

20

20

30

40

50

60

Length of U-Tube

 

(ft, in) B

N/A

11,7

11,7

16,7

21,7

26,7

31,7

Overall Length of Straight Tube

 

(ft, in) C

11,5.5

21,5.5

21,5.5

31,5.5

41,5.5

51,5.5

61,5.5

Overall Length of U-Tube

 

(ft, in) D

N/A

13,0.5

13,0.5

18,0.5

23,0.5

28,0.5

33,0.5

Input (Btu/h) x (1000)

 

 

 

40

60

80

100

125

150

175

Fuel

 

 

 

 

 

Natural Gas (NG) or Propane Gas (LP)

 

 

Inlet Pressure

(in wc) NG min.

4.6

4.6

4.6

4.6

4.6

4.6

5

 

 

 

LP min.

11

11

11

11

11

11

11

 

 

 

 

 

 

 

14 maximum for NG & LP

 

 

 

Gas Connection

 

NPT

3/4”

3/4”

3/4”

3/4”

3/4”

3/4”

3/4”

Electrical Supply

 

 

 

 

 

120 V, 60 Hz, 1 A (Run) 5 A (Start)

 

 

Heat Exchanger Tubing

 

 

 

 

10 ft Sections, 4" dia, 16 Gauge, First 10 ft ALUMI-THERM®Steel Tubing

 

 

 

 

 

 

 

(Remaining Heat Treated Aluminized Steel Tubing)

 

 

Exhaust Flue

 

 

 

 

 

 

4” dia

 

 

 

Reflector and End Caps

 

 

 

 

.024 Stainless Steel Type 304 (Optional - .024 Aluminum)

 

Control System

 

 

 

Honeywell® SmartValve® II Combines Gas Valve and Hot Surface Electronic Ignition Control

 

 

 

 

 

Fully Automatic, Four-Try, 100% Shut-Off, Prepurge, Auto Reset, LED Indicator Status

 

Approved As

 

 

 

 

 

Indoor and Outdoor (Vented or Unvented)

 

 

Certification

 

 

 

 

 

ANSI Z83.20/CSA 2.34, 2.17, 2.20

 

 

Warranty

 

 

 

Three-Year Limited (Refer to Installation, Operation and Service Manual for Details)

Weights

 

 

 

 

 

 

 

 

 

 

Burner

 

 

(lb)

 

 

 

40

 

 

 

Vent Cap Package Included

 

 

(lb)

 

 

 

4

 

 

 

Overall Length of Tube and Accessory Packages

(ft)

10

20

30

 

40

50

60

 

Aluminized Tube with Aluminum Reflector

 

(lb)

52

86

120

 

161

206

240

 

Aluminized Tube with Stainless Steel Reflector

(lb)

66

113

152

 

208

265

304

 

U-Tube Packages

 

 

(lb)

 

 

 

 

 

 

 

 

Aluminized Tube with Aluminum End Caps

 

 

 

 

 

19

 

 

 

 

Aluminized Tube with Stainless Steel End Caps

 

 

 

 

20

 

 

 

Clearances to Combustibles* (in)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

HE-40

HE-60

HE-80

HE-100

HE-125

HE-150

HE-175

A

Horizontal

A

45°

A

Horiz. 45°

Horiz.45°

Horiz.45°

Horiz.45°

Horiz. 45°

Horiz. 45°

Horiz. 45°

 

 

 

 

 

6

8

6

8

6

8

6

10

6

10

6

12

8

12

 

 

 

 

 

B

27

8

35

8

38

8

40

8

46

8

50

8

52

8

C

B

D

C

 

C

53

51

63

60

66

66

71

74

77

78

80

84

82

85

 

 

 

B

D

D

27

46

35

54

38

60

40

64

46

69

50

74

52

79

 

 

 

 

 

*Clearances B, C, D can be reduced by 50% for locations 25 ft (7m) or more downstream of the burner. For other mounting options and associated clearances, complete installation, operation and service criteria, please see the current issue of the VANTAGE® HE Installation, Operation and Service Manual.

Installation Code: ROBERTS GORDON® products are to be installed only in accordance with local laws, codes and regulations, and only by a contractor qualified in the installation and service of gas-fired heating equipment. This product is not for residential use.

Further Information: Applications, engineering and detailed guidance on systems design, installation and product performance is available through ROBERTS GORDON® North American independent distributors. Please contact us for any further information you may require, including the VANTAGE® HE Installation, Operation and Service Manual.

Roberts-Gordon

Roberts-Gordon

1250 William Street

76 Main Street West

P.O. Box 44

Unit 10

Buffalo, NY 14240-0044 USA

Grimsby, Ontario L3M 1R6 Canada

Telephone: 716.852.4400

Telephone: 905.945.5403

Fax: 716.852.0854

Fax: 905.945.0511

Toll Free: 800.828.7450

European Office:

 

 

Roberts-Gordon

www.rg-inc.com

Telephone: +44(0) 1902 494425

Fax: +44(0) 1902 403200

©2005 Roberts-Gordon All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic or mechanical, including photocopying, recording, taping, or information storage and retrieval systems – without written permission of Roberts-Gordon.

Printed in U.S.A

HESNA

5M 0205 Rev. E

Image 2
Contents Vantage HE Roberts-Gordon European Office
Related manuals
Manual 72 pages 53.49 Kb

HE-125, HE-150, HE-100, HE-40, HE-175 specifications

Roberts Gordon is renowned for its innovative heating solutions, and among its standout offerings are the HE-125, HE-175, HE-100, HE-150, and HE-40 heaters. These products exemplify cutting-edge technology and efficiency designed for commercial and industrial applications.

The HE-125 and HE-175 variants are among the top-rated infrared heaters available. They utilize advanced infrared technology to provide direct heating to objects, reducing the need to heat the entire ambient air volume. This method results in energy savings while delivering consistent warmth where it's needed most. The HE-125 model has a heating capacity of 125,000 BTU, while the HE-175 pushes this to 175,000 BTU, making them suitable for larger spaces like warehouses and manufacturing facilities.

The HE-100 and HE-150 heaters are designed for flexibility and efficiency in a range of operational environments. These models support a wide range of input fuels including natural gas and propane, making them an adaptable choice for various setups. The HE-100 has an output of 100,000 BTU, and the HE-150 follows with 150,000 BTU. Both units are engineered with robust construction materials, ensuring durability and longevity, while also featuring advanced safety systems to prevent overheating and other hazards.

In contrast, the HE-40 heater stands out for smaller spaces, making it an ideal option for garages, workshops, or smaller commercial environments. With a capacity of 40,000 BTU, it effectively delivers consistent warmth without the excessive energy consumption associated with larger units.

All Roberts Gordon models prioritize energy efficiency, often meeting or exceeding current energy codes. They incorporate advanced control systems that allow precise temperature regulation, further optimizing energy use. Additionally, the heaters are designed with minimal maintenance needs, featuring durable components that ensure long-term reliability and performance.

With a legacy of quality and innovation, Roberts Gordon continues to set the standard in infrared heating technology. The HE series exemplifies a commitment to efficiency, safety, and versatility, making them suitable for a wide range of commercial and industrial applications. Whether heating a vast warehouse or a small workshop, these heaters provide reliable performance tailored to user needs.