York LD11554, LD11556, LD11555 warranty Sequence of Operation

Page 9

FORM 115.20-NOM6 (1106)

SEQUENCE OF OPERATION

YCW With a Chilled Water Coil

The unit will respond to a cooling command from the thermostat by powering a water control valve open. The fan will operate at the speed selected at the thermostat. When the space reaches the temperature setpoint at the thermostat, the cooling valve will close and the fan will continue to operate.

When using the T420 manual C/O thermostat and the TB3-3/TB2-5 jumper is in place, the fan will con- tinue to operate at the fan speed selected. Removing the jumper will cause the fan to shut down when the thermostat is satisfied.

When using the T200 thermostat, the stat will auto- matically regulate the fan speed based on the differ- ence between the space temp and setpoint - @ 4˚F off setpoint, the fan will run @ HI; @ 3˚F off setpoint, the fan will run @ MED; @ 2˚F off setpoint, the fan will run @ LO. When the thermostat is satisfied, the water valve will be deenergized and the fan will revert to LO speed.

The YCW-HW with Both a Chilled Water Coil and a Hot Water Coil.

The unit control thermostat, on a call for heating, will energize the hot water control valve. When the ther- mostat is set for cooling, it will energize the chilled water valve on a call for cooling. The fan will operate at the speed selected at the thermostat. When the space reaches the temperature setpoint at the thermostat, the cooling valve will close (on cooling) or the heating valve will close (on heating) and the fan will continue to operate.

When using the T420 manual C/O thermostat and the TB3-3/TB2-5 jumper is in place, the fan will con- tinue to operate at the fan speed selected. Removing the jumper will cause the fan to shut down when the thermostat is satisfied.

When using the T421 auto C/O thermostat and the TB3-3/TB2-5 jumper is in place, the fan will con- tinue to operate at the fan speed selected. Removing the jumper will cause the fan to shut down when the thermostat is satisfied.

When using the T200 thermostat, the stat will auto- matically regulate the fan speed based on the differ- ence between the space temp and setpoint - @ 4˚F off setpoint, the fan will run @ HI; @ 3˚F off setpoint, the fan will run @ MED; @ 2˚F off setpoint, the fan will run @ LO. When the thermostat is satisfied, the water valve will be deenergized and the fan will revert to LO speed.

The YCWE With Both a Chilled Water Coil and Electric Heating Coil.

The unit control thermostat, on a call for heating, will energize the heater contactor(s). When the thermostat is set for cooling, it will energize the chilled water valve on a call for cooling. The fan will operate at the speed selected at the thermostat. When the space reaches the temperature setpoint at the thermostat, the cooling valve will close (on cooling) or the heat- ing contactors will open (on heating) and the fan will continue to operate.

When using the T420 manual C/O thermostat and the TB3-3/TB2-5 jumper is in place, the fan will con- tinue to operate at the fan speed selected. Removing the jumper will cause the fan to shut down when the thermostat is satisfied.

When using the T421 auto C/O thermostat and the TB3-3/TB2-5 jumper is in place, the fan will con- tinue to operate at the fan speed selected. Removing the jumper will cause the fan to shut down when the thermostat is satisfied.

When using the T200 thermostat, the stat will auto- matically regulate the fan speed based on the differ- ence between the space temp and setpoint - @ 4˚F off setpoint, the fan will run @ HI; @ 3˚F off setpoint, the fan will run @ MED; @ 2˚F off setpoint, the fan will run @ LO. When the thermostat is satisfied, the water valve will be deenergized (on cooling) or the heating contactor will open (on heating) and the fan will revert to LO speed.

JOHNSON CONTROLS

9

Image 9
Contents Models YCW Series FAN Coil AIR ConditionersTable of Contents Installation See for unit details and dimensions Refer to for access locations Electrical Data Pipe Chilled Water-Hot Water 190 1085 CFM Chilled Water with Electric Heat Sequence of Operation Clean or replace air filters regularly MaintenanceThis Page Intentionally Left Blank Install Checklist FAN Coils START-UP Checklist