York TCGD18 THRU 60 warranty AHP18, AHP30, AHP36, AHP42, AHP/SHP48, TCGD60S41S1 AHP/SHP60

Page 6

359315-YTG-B-0408

COOLING CAPACITY - With Air Handler Coils (Continued)

UNIT

AIR HANDLER

 

COIL

 

 

 

COOLING

 

 

 

 

 

RATED

 

NET MBH

 

 

MODEL

MODEL

 

W

MODEL1

 

SEER

EER

 

CFM

 

TOTAL

SENS.

 

 

 

 

 

 

 

 

 

 

 

13

SEER AC WITH AHP

/ SHP / F*FP

 

 

 

 

 

TCGD18S41S1(H)

AHP18

 

17

650

 

17.5

12.9

13.00

11.00

F4FP024

 

18

600

 

17.5

12.9

13.00

11.00

 

 

 

TCGD24S41S1(H)

AHP30

 

17

795

 

24.0

16.8

13.00

11.00

F4FP036

 

21.5

800

 

24.0

16.7

13.00

11.00

 

 

 

 

AHP30

 

17

1015

 

29.0

21.0

13.00

11.00

TCGD30S41S1(H)

 

 

 

 

 

 

 

 

 

 

AHP36

 

21

1040

 

29.0

21.0

13.00

11.00

 

F4FP040

 

18

1050

 

29.0

21.0

13.00

11.00

 

AHP36

 

21

1235

 

35.0

24.8

13.00

11.00

TCGD36S41S1(H)

 

 

 

 

 

 

 

 

 

 

AHP42

 

21

1255

 

35.0

24.8

13.00

11.00

 

F5FP048

 

24

1235

 

35.0

24.8

13.00

11.00

TCGD42S41S1(H)

AHP42

 

21

1485

 

41.0

29.2

13.00

11.00

F5FP048

 

24

1455

 

41.0

29.2

13.00

11.00

 

 

 

 

AHP/SHP48

 

24

1675

 

48.0

34.4

13.00

11.00

TCGD48S41S1(H)

AHP/SHP60

 

24

1600

 

48.0

35.0

13.50

11.00

F5FP048

 

24

1600

 

48.0

34.4

13.00

11.00

 

 

 

 

F5FP060

 

24

1600

 

48.0

34.4

13.00

11.00

TCGD60S41S1

AHP/SHP60

 

24

1850

 

57.0

38.5

13.00

11.00

F5FP060

 

24

1900

 

57.0

38.5

13.00

11.00

 

 

 

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

1.MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.

— = Not applicable.

6

Johnson Controls Unitary Products

Image 6
Contents Listed Model TCGD18 TCGD24 TCGD30 TCGD36 TCGD42 TCGD48 TCGD60 FC/MC/PC32A3X FC/MC/PC/UC18A3X FC/MC/PC/UC18B3X FC/MC/PC35B3XProcedures FootnotesSeer EER CFM Unit AIR HandlerCooling Rated NET MBH Model SensAHP36 AHP18AHP30 AHP42Furnace Cooling Unit Model CFM Range Rated NET MBH SEER1Variable Speed Cooling Unit Model Furnace Model MODEL1 RatedSeer AC with Variable Speed FURNACES2 FC/MC/PC48D FC/PC60CFC/MC/PC60D Accessories TBDIndoor Coil Model no TemperatureAIR Conditioner Model no CondensingFC/MC/PC32 FC/MC/PC35 FC/MC/PC37 FC/MC/PC43 MV12B FC/MC36B MA08B FC/MC35B FC/MC43BFC/MC/PC35 FC/MC/PC37 FC/MC/PC43 AHP30 AHP36MV12B FC/MC35B MV16C FC/MC35C MA12B FC/MC43B FC/MC43C Indoor Coil Model no FC/MC/PC43 Condensing FC/MC/PC43 FC/MC/PC48AHP36 AHP42 AHP42 MV16C FC/MC43C MA16C FC/MC48C MV20D FC/MC48D MA14D Indoor Coil Model no FC/MC/PC48 Condensing FC/PC/UC60C Indoor Coil Model no FC/MC/PC60 CondensingAHP/SHP60 AV/SV60 MV20D FC/MC60D MA20D FC/MC62D FC/MC/PC/UC60DJohnson Controls Unitary Products York Drive Norman, OK