R-410A QUICK REFERENCE GUIDE

Refer to Installation Instructions for specific installation requirements.

R-410A Refrigerant operates at 50 - 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A.

R-410A Refrigerant cylinders are rose colored.

Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400, or DOT BW400. Recovery equipment must be rated for R-410A.

Do Not use R-410A service equipment on R-22 systems. All hoses, gages, recovery cylinders, charging cylinders and recovery equipment must be dedicated for use on R-410A systems only.

Manifold sets must be at least 700 psig high side, and 180 psig low side, with 550 psig retard. All hoses must have a service pressure rating of 800 psig.

Leak detectors must be designed to detect HFC refrigerants.

Systems must be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.

R-410A can only be used with POE type oils.

POE type oils rapidly absorb moisture from the atmosphere. Vacuum pumps will not remove moisture from POE type oils.

Do not use liquid line driers with a rated working pressure rating less than 600 psig.

Do not install suction line driers in the liquid line.

A liquid line drier is required on every unit.

Do not use a R-22 TXV. If a TXV is to be used, it must be a R-410A TXV. Never open system to atmosphere when under a vacuum.

If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace all filter driers.

Figure 20: R-410A Quick Reference Guide

Subject to change without notice. Printed in U.S.A.

279550-YIM-A-0207

Copyright © 2007 by Unitary Products Group. All rights reserved.

Supersedes: 98811-YIM-C-1006

 

 

 

 

Unitary

5005

Norman

Products

York

OK

Group

Drive

73069

Image 36
Contents DNX024-048 Ton GeneralInspection ReferenceRenewal Parts ApprovalsInstallation Installation Safety InformationNomenclature LimitationsComponent Location Unit Limitations Location Rigging And HandlingClearances Unit 4 Point Load Weight Weights and Dimensions Unit Accessory WeightsUnit Dimensions Unit DimensionsUnit Clearances1 Dimensions Front and Bottom Ductwork Roof CurbFilters Condensate DrainService Access Power And Control WiringThermostat  92/7 75$162505 352*5$00$% +50267$721 Typical Field Power Wiring Diagram Electrical Data DNX024-048 Single Stage Gas Heat ARI Cooling PerformanceDNX024-048 Two Stage Gas Heat Compressors PhasingGas Heat Gas PipingNatural Gas Pipe Sizing Chart1 Propane LP Gas Pipe Sizing Chart1Flue Vent Hood Natural Gas Application Data-Single Stage Natural Gas Application Data-Two StagePropane1 LP Gas Application Data-Single Stage Propane1 LP Gas Application Data-Two StageAirflow Performance Side Duct ApplicationBottom Duct Application 1070 257 300 343 386 430 475 520 565 611 Cool Indoor Blower Specifications Blower Speed SelectionAdditional Static Resistance To Set Cooling CFM for DNX UnitsOperation Heating Sequence Of OperationHeat Blower Off Delay High Temperature Limit SwitchRollout Switch Power InterruptionsSafety Controls Cooling Sequence Of OperationsWelded Gas Valve Relay Response Start-Up Burner Instructions Pilot InstructionAdjustment of Temperature Rise Checking Gas Heat InputNatural Gas Direct Drive BlowerTypical Wiring Diagrams YIM-A-0207 YIM-A-0207 YIM-A-0207 YIM-A-0207 YIM-A-0207 YIM-A-0207 YIM-A-0207 410A Quick Reference Guide
Related manuals
Manual 24 pages 22.74 Kb Manual 68 pages 3.65 Kb Manual 104 pages 7.39 Kb Manual 128 pages 30.42 Kb

R-410A specifications

York R-410A is a widely recognized and highly efficient refrigerant used in modern air conditioning systems. Developed as an environmentally friendly alternative to R-22, R-410A has gained popularity in the HVAC industry due to its numerous advantageous features and characteristics.

One of the main features of York R-410A is its ability to provide superior cooling performance. This refrigerant operates efficiently at both high and low temperatures, allowing systems using it to maintain optimal indoor climates even during extreme weather conditions. Its high energy efficiency ratio (EER) and seasonal energy efficiency ratio (SEER) ratings make it a preferred choice for energy-conscious consumers, resulting in lower energy bills and a reduced carbon footprint.

Technologically, York R-410A systems feature advanced compressor designs that enhance their overall reliability and performance. These compressors are often equipped with variable-speed technology, enabling them to adjust their output to match the cooling demands of the space. This not only improves comfort levels but also leads to efficient energy consumption, reducing wear and tear on the equipment over time.

Another significant characteristic of York R-410A is its non-ozone-depleting properties. Unlike its predecessor R-22, which is being phased out due to its damaging effects on the ozone layer, R-410A is designed to minimize environmental impact. Its lower global warming potential (GWP) further underscores its role in promoting sustainability within the HVAC sector.

Furthermore, York R-410A systems are engineered with enhanced safety features. The refrigerant is non-toxic and non-flammable, which makes it safer for use in both residential and commercial applications. Additionally, its high thermal stability reduces the risk of breakdown or leakage, contributing to longer system lifespans and lower maintenance costs.

In conclusion, York R-410A stands out as a cutting-edge refrigerant that combines efficiency, safety, and environmental responsibility. With its advanced technologies and remarkable characteristics, it meets the demands of modern air conditioning requirements while paving the way for a sustainable future in HVAC systems. Adopting York R-410A not only benefits individual users through improved comfort and lower energy bills but also plays a vital role in protecting our planet's ozone layer and mitigating climate change.