WATER SYSTEMS
Features |
|
| Thermostats |
• 6 speed fan |
|
| CSL00 (Built in) |
|
| ||
• Cabinet factory fitted |
|
| CSR00 (Wall mounted) |
|
| Fan speed selector | |
• Valve factory fitted |
|
| |
|
| CML00 (Built in) | |
|
| ||
|
| ||
• Electrical heater factory fitted |
|
| |
|
| CMR00 (Wall mounted) | |
• Thermal or modulating valve |
|
| Thermostat with manual fan speed and S/W |
|
| change over | |
• Service valve |
|
| |
|
| CEL00 (Built in) | |
|
| ||
|
|
| |
|
|
| CER00 (Wall mounted) |
|
|
| Thermostat with manual fan speed and automatic |
|
|
| change over |
|
|
| |
|
|
| CEL20 (Built in) |
|
|
| CER20 (Wall mounted) |
|
|
| Thermostat with auto. fan speed and automatic |
|
|
| change over |
CEL30 (Built in)
CER30 (Wall mounted)
Fan Coil Unit Thermostat with auto. fan speed and automatic change over for modulating valve
LOW BODY (2 & 4 pipe system)
A complete range from 0.8 kW up to 2.7 kW
Selection software
Technical features
|
|
|
|
|
| YLVR - YLIVR |
|
|
|
|
|
|
|
|
|
|
|
Model |
|
|
| 110 | 112 | 114 | 216 | 218 |
|
|
|
|
|
|
|
|
|
Cooling capacity | (1) | 2 rows | W | 832 | 1054 | 1493 | 2041 | 2356 |
|
|
|
|
|
|
|
|
|
Cooling capacity | (1) | 3 rows | W | 913 | 1266 | 1790 | 2327 | 2714 |
|
|
|
|
|
|
|
| |
Heating capacity (2) | 1 row | W | 1167 | 1691 | 2319 | 3029 | 3552 | |
|
|
|
|
|
|
|
|
|
Pressure drop (3) |
|
| kPa | 7 | 1.7 | 3.8 | 9 | 11.7 |
|
|
|
|
|
|
|
|
|
Power supply |
|
| V/Ph/Hz |
|
| 230 / 1 / 50 + E |
|
|
Sound power level (3) | dB(A) | 49 | 50 | 53 | 53 | 55 | ||
|
|
|
|
|
|
| ||
Sound pressure level at 3 m | dB(A) | 31 | 32 | 35 | 35 | 37 | ||
|
|
|
|
|
|
|
| |
Water connections |
| inch |
|
| 1/2 “ |
|
|
Dimensions indicated next page
(1)Cooling capacities based on 7ºC EWT ∆t 5ºC indoor temperature 27ºC DB / 19ºC WB - (2 pipes - high speed fan)
(2)Heating capacities based on 70ºC EWT ∆t 10ºC indoor temperature 20ºC - (2 pipes - high speed fan)
(3)In cooling mode 2 rows
For other conditions contact York international