York 110, 114, 218, 112, 216 dimensions Technical features, Ylvr Ylivr, Model

Page 1

WATER SYSTEMS

Features

 

 

Thermostats

• 6 speed fan

 

 

CSL00 (Built in)

 

 

• Cabinet factory fitted

 

 

CSR00 (Wall mounted)

 

 

Fan speed selector

• Valve factory fitted

 

 

 

 

CML00 (Built in)

 

 

 

 

• Electrical heater factory fitted

 

 

 

 

CMR00 (Wall mounted)

• Thermal or modulating valve

 

 

Thermostat with manual fan speed and S/W

 

 

change over

• Service valve

 

 

 

 

CEL00 (Built in)

 

 

 

 

 

 

 

 

CER00 (Wall mounted)

 

 

 

Thermostat with manual fan speed and automatic

 

 

 

change over

 

 

 

 

 

 

CEL20 (Built in)

 

 

 

CER20 (Wall mounted)

 

 

 

Thermostat with auto. fan speed and automatic

 

 

 

change over

CEL30 (Built in)

CER30 (Wall mounted)

Fan Coil Unit Thermostat with auto. fan speed and automatic change over for modulating valve

LOW BODY (2 & 4 pipe system)

A complete range from 0.8 kW up to 2.7 kW

Selection software

Technical features

 

 

 

 

 

 

YLVR - YLIVR

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

 

110

112

114

216

218

 

 

 

 

 

 

 

 

 

Cooling capacity

(1)

2 rows

W

832

1054

1493

2041

2356

 

 

 

 

 

 

 

 

 

Cooling capacity

(1)

3 rows

W

913

1266

1790

2327

2714

 

 

 

 

 

 

 

 

Heating capacity (2)

1 row

W

1167

1691

2319

3029

3552

 

 

 

 

 

 

 

 

 

Pressure drop (3)

 

 

kPa

7

1.7

3.8

9

11.7

 

 

 

 

 

 

 

 

 

Power supply

 

 

V/Ph/Hz

 

 

230 / 1 / 50 + E

 

 

Sound power level (3)

dB(A)

49

50

53

53

55

 

 

 

 

 

 

 

Sound pressure level at 3 m

dB(A)

31

32

35

35

37

 

 

 

 

 

 

 

 

Water connections

 

inch

 

 

1/2 “

 

 

Dimensions indicated next page

(1)Cooling capacities based on 7ºC EWT ∆t 5ºC indoor temperature 27ºC DB / 19ºC WB - (2 pipes - high speed fan)

(2)Heating capacities based on 70ºC EWT ∆t 10ºC indoor temperature 20ºC - (2 pipes - high speed fan)

(3)In cooling mode 2 rows

For other conditions contact York international

Image 1
Contents Ylvr Ylivr Technical featuresModel Compatibility table / Codes Fan Coil Unit LOW BodyDimensions and Weights DimensionsLOW Body Ylvr = low body = vertical = without cabinetDim LOW Body Ylivr112 114 216 218 Compatibility tables for FCU Laser and LOW Body Standard LOW Body Laser Concealed Compatibility Options / Accessories / ModelsKrel CBL20