Lochinvar 402 - 2072 Adjusting combustion air pressure, Checking manifold gas pressure

Page 28

Copper-fin II/IIE Boiler, Water Heater and Pool Service Manual

2 Maintenance

Adjusting combustion air pressure

The following is a recommended method for setting the combustion air pressure. The following pressure settings are for installations up to 4000 feet altitude. Contact the factory for high altitude air pressure settings.

Upon removal of the upper front doors, locate the capped tee in the pressure tubing that connects between the inner top and the gas valves. Remove this cap and connect a hose from the tee to a manometer.

For 399,999 - 750,000 Btu/hr models (reference FIG. 2-2)

1.The combustion air chamber pressure for these models is typically 1.2 - 1.3 inches water column when the fan is at high speed.

2.If adjustment is necessary, slightly loosen the nuts connecting the fan to the inner top.

3.Adjust the air shutter located underneath the fan assembly to obtain the desired chamber pressure. Slide the shutter inward to decrease the chamber pressure or outward to increase the chamber pressure.

For 990,000 - 2,070,000 Btu/hr models (reference FIG. 2-3)

1.The combustion air chamber pressure for these models is typically 1.2 - 1.3 inches water column when the fan is at high speed.

2.If adjustment is necessary, slightly loosen the nut located on the air shutter arm.

3.Adjust the air shutter arm to obtain the desired chamber pressure. Slide the arm inward to decrease the chamber pressure or outward to increase the chamber pressure.

All models

4.Once the adjustment procedure is complete, tighten all connections, disconnect the manometer, and replace the cap at the tee.

5.Check all connections and test fire the unit.

6.Replace all panels.

Checking manifold gas pressure

The gas regulator on the combination gas valve is adjustable to supply the proper manifold pressure for normal operation. The gas valves are factory pre-set and should not need adjusting in most cases. Gas manifold pressures are listed in Table 2B.

Gas manifold pressures may be checked with the use of a manometer. Follow the steps in the Checking Combustion Air Pressure Section prior to checking the manifold pressures.

Checking manifold gas pressure

1.Turn the appliance power switch to the “OFF” position.

2.Remove the upper outer access panels.

3.Remove the 1/8" hex plug from the downstream side of the gas valve (see FIG. 2-4). Install a fitting in the tap and connect a hose from the tap to a manometer.

4.Connect a hose from the tee used to measure the combustion air pressure to the other side of the manometer.

5.Turn the appliance power switch to the “ON” position.

6.With the unit at high fire, check and record the manifold pressure of the valve. The manifold pressure will be the sum of the two pressure readings (reference Table 2B).

7.Repeat this process with each gas valve.

￿WARNING Overfire and underfire hazards! Possible fire, explosion, overheating, and component failure. Do not attempt to adjust firing rate of the appliance. The firing rate must be adjusted only by factory trained personnel.

If you must adjust the gas valve regulator pressure, follow the steps below:

1.Remove the cap covering the manifold pressure adjustment screw (see FIG. 2-4). Note: Once the cap is removed, the pressure shown on the manometer will change and the unit may turn off.

2.Make a slight adjustment to the manifold pressure adjustment screw. Turning the screw clockwise increases manifold pressure and counterclockwise decreases manifold pressure.

3.Replace the cap and check the manifold pressure. Note: Allow the unit to re-light if necessary.

4.Repeat the steps above to match the manifold pressures from Table 2B.

5.Once the adjustment procedure is complete, turn off the appliance, disconnect the manometer, replace and tighten all connections, and replace all panels.

6.Turn on the appliance and test fire the unit.

7.Repeat this process with each gas valve.

28

Image 28
Contents Copper-fin II/IIE Boiler, Water Heater Pool Heater Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid What is in this manual? ServiceMaintenance TroubleshootingService Copper-fin displayControl inputs Control outputs General Operation How the appliance operatesHow the control module operates Sequence of operationSequence of operation OUT 123.8F129HTR Postpurge Display panel menu access Display panel parameter access Functions Settingsdhw Resetoutdoor Parameter tableAnti-cycle Delay Yes Temperature settings boiler only Viewable and changeable control parametersData logging FunctionsDHW settings Outdoor air reset boiler only Anti-cycling Control modes Building Management System BMS CascadeService Notification Circulation pumpsMaintenance Maintenance and annual startup Service technicianOwner maintenance See the User’s Information Manual for instructionsMaintenance Check relief valve Inspect/replace hot surface igniter Inspect/replace hot surface ignitersCheck all wiring Check control settingsInspect and clean burner Perform start-up and checksAccess to the burner will require the following steps Checking combustion air pressureAdjusting combustion air pressure Checking manifold gas pressureValve Fitting Control Knob Review with owner Inspect and clean the heat exchangerOiled bearing circulators Troubleshooting Before troubleshootingCheck control module fuses Check the followingNo Display No BurnerOperation Unit Does NotResistance Temperature Checking temperature sensorsTemperature Resistance Noisy No PumpBoiler Pump System Pump DHW PumpFlame Sequence Flow SwitchAnti-cycling Error No Flame IgnHSI Current Low Flame CKTAuto Reset No FlameRunning High LimitManual Reset Inlet LowSensor Open Sensor ShortedLouver Proving Tank OpenAPS Open APS ClosedTemp O/Shoot Rem Ctrl FltService Blk ParametersProgr Low VoltageWatch Dog Error No Error StoredWrite EEProm Program EEProm
Related manuals
Manual 44 pages 7.23 Kb Manual 44 pages 18.25 Kb Manual 80 pages 43.41 Kb

502 - 2072, 402 - 2072 specifications

The Lochinvar 402 - 2072 is a versatile and highly efficient boiler designed to meet the heating demands of modern residential and commercial applications. This model stands out due to its innovative technologies, advanced features, and a high level of reliability, making it an ideal choice for consumers looking for an enduring and economical heating solution.

One of the primary characteristics of the Lochinvar 402 - 2072 is its impressive energy efficiency. With an exceptional annual fuel utilization efficiency (AFUE) rating, this boiler ensures minimal energy waste, allowing homeowners and business operators to save significantly on their energy bills. The model incorporates advanced condensing technology that enables it to extract heat from the combustion gases, maximizing heat transfer and reducing emissions.

The Lochinvar 402 - 2072 is built with a robust stainless steel construction that enhances durability and resilience against corrosion and other environmental factors. This material not only prolongs the lifespan of the unit but also contributes to its outstanding thermal efficiency. Additionally, the boiler's compact design allows for flexible installation options, making it suitable for various spaces, including tight utility rooms and basements.

Equipped with a user-friendly control interface, the Lochinvar 402 - 2072 allows for easy monitoring and adjustment of settings. Its advanced digital display provides real-time data on system performance, ensuring the operator can maintain optimal performance and efficiency.

Another noteworthy feature is the unit's quiet operation. The design includes sound-dampening insulation and high-efficiency circulators, keeping noise to a minimum, which is an essential trait for both residential and commercial settings.

The Lochinvar 402 - 2072 is also designed with safety in mind. It incorporates multiple safety features including an automated vent damper, low water cutoff, and a comprehensive control system that monitors various operating conditions. This proactive approach to safety ensures that potential issues are identified and addressed before they become critical.

In conclusion, the Lochinvar 402 - 2072 boiler presents an exceptional combination of efficiency, durability, and user-friendly features. Its advanced condensing technology, stainless steel construction, and focus on safety make it a leading choice in the competitive boiler market, catering to the heating needs of a diverse range of applications while ensuring environmental responsibility. For those in search of a dependable and efficient heating solution, the Lochinvar 402 - 2072 is certainly worth considering.