Healthy Climate® Dealer Installation Instructions
Independent Operation:
The HEPA systems can be used independently of any other equipment! The inlet and outlet of the filtration system can be ducted into the same room to create a cleaner environment almost anywhere. The inlet or outlet can also be ducted elsewhere. The inlet and outlet should be installed on opposite sides of the room; however, this varies according to your specific needs.
Preparation: | Example of Single Room Stand Alone System Installation | |||||||||||||
Here are some things to consider as you | For single rooms where increased filtration is desired such as a | |||||||||||||
decide where to install the HEPA system | dedicated ‘smoking room’. | |||||||||||||
independently of other systems. | HEPA System |
|
|
|
|
|
|
|
|
|
| Air should be drawn from | ||
|
|
|
|
|
|
|
|
|
| |||||
Location: |
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| location B if space is avail- | ||
|
|
|
|
|
|
|
|
|
|
|
| |||
• | Make sure there is room to open the |
|
|
|
|
|
|
|
|
|
|
|
| able, otherwise, use loca- |
| HEPA filter access panel for filter |
| A |
|
|
|
|
|
|
|
|
|
| tion A. |
|
|
|
|
|
|
|
|
|
|
|
| |||
| changes/inspections. |
|
|
|
|
|
|
|
|
|
|
|
|
|
• Keep the HEPA system away from |
|
|
|
|
|
|
|
|
|
|
|
|
| |
| possible water damage. |
|
|
|
|
|
|
|
|
|
|
|
|
|
• | Vibration pads will reduce vibration for |
|
|
|
|
|
|
|
|
|
|
|
|
|
| installations where the unit is placed on |
| B |
|
|
|
|
|
|
|
|
|
|
|
| the floor. |
|
|
|
|
|
|
|
|
|
|
|
| |
• | Install HEPA System on floor or suspended |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Figure 11. | ||||||||||||
| platform. If the unit is suspended, screws |
|
| |||||||||||
| must not penetrate through the cabinet. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| noise reduction purposes | |||||||||||
| Make sure that you have the proper |
|
| |||||||||||
| chains/straps/joists and equipment to keep unit | • | For best indoor air quality, do not use ductboard or | |||||||||||
| secure. |
|
| fiberglass inside of ducts. |
Inlet (Marked as ‘Air In’ on unit):
•Inlet ducts should be installed near the floor for optimum airflow (see figure 11). If space does not allow, then the inlet can be installed in the ceiling.
•Inlet duct should be installed at least 8 ft. away from the outlet duct on the main return.
•Inlet duct should be installed at opposite end of the room from the outlet duct(s) if in the same room.
•Diffusers are recommended to help distribute airflow evenly.
Outlet (Marked as ‘Clean Air Out’ on unit):
•Outlet(s) should be installed in the ceiling away from any other air inlet(s)
•Room diffusers are recommended to help distribute airflow evenly in the occupied space.
Ducting:
•If HEPA system is installed where inlet and outlet collars face down, metal elbows must be connected to both inlet and outlet collars.
•Each connection must be sealed with aluminum tape or mastic, including all vent connections.
•Installed duct runs should be as straight as possible (if the duct runs are too long, reduced CFM may result).
•If duct is exposed to unconditioned air, insulated flex duct is highly recommended.
•Externally insulated flex duct can also be used for
Electricity:
•The unit must be plugged into a grounded 120V, 60Hz. outlet.
Required Materials for Installation of Unit:
For Model: HEPA-20
8” diameter flex or rigid duct (as required) 6” diameter flex or rigid duct (as required) 8” diameter vent
6” diameter vent Aluminum tape or mastic
Misc. hanging materials - field provided
For Models: HEPA-40 & HEPA-60
10” diameter flex or rigid duct (as required) 8” diameter flex or rigid duct (as required) 10” diameter vent
8” diameter vent Aluminum tape or mastic
Misc. hanging materials - field provided
NOTE: Be sure to review ‘Rules for Safe Installation and Operation’ on page 1 of this document before
NOTE: For details on the best way to combine HEPA
filtration with other air quality products see: SERVICE
AND APPLICATION NOTE
11